Product data
110
INDOOR-FAN MOTOR DATA — 50HJQ004-012
LEGEND
*Extensive motor and electrical testing on these units ensures that the full horsepower and watts range of the motors
can be utilized with confidence. Using your fan motors up to the ratings shown in this table will not result in nuisance
tripping or premature motor failure. Unit warranty will not be affected.
UNIT
50HJQ
UNIT
PHASE
MAXIMUM
CONTINUOUS BHP*
MAXIMUM
OPERATING WATTS*
UNIT VOLTAGE
MAXIMUM
AMP DRAW
MOTOR
EFFICIENCY (%)
004
Single 1.20 1000 208/230 5.1
75
Three 1.20 1000
208/230 5.1
460 2.3
005
Single 1.20 1000 208/230 5.1
75
Three 1.20 1000
208/230 5.1
460 2.3
006
Single 1.80 1921 208/230 9.2
74
Three 1.80 1921
208/230 6.1
460 2.7
007 Three 2.40 2120
208/230 6.1
84
460 2.7
008 Three 2.90 2615
208/230 7.9
80
460 3.6
012 Three 4.20 3775
208/230 11.1
85
460 5.0
Bhp — Brake Horsepower Input to Fan
Performance data (cont)
50TFQ004-01250HJQ004-012