Product data
107
ACCESSORY/FIOP STATIC PRESSURE* (in. wg) — 50HJQ004-007
LEGEND
FIOP — Factory-Installed Option
*The static pressure must be added to external static pressure. The sum and the evaporator
entering-air cfm should then be used in conjunction with the Fan Performance tables to deter-
mine blower rpm and watts.
ACCESSORY/FIOP STATIC PRESSURE* (in. wg) — 50HJQ008-012
LEGEND
FIOP — Factory-Installed Option
*The static pressure must be added to external static pressure. The sum and the evaporator
entering-air cfm should then be used in conjunction with the Fan Performance tables to deter-
mine blower rpm and watts.
FAN RPM AT MOTOR PULLEY SETTINGS* — 50HJQ004-012
*Approximate fan rpm shown.
COMPONENT
CFM
900 1200 1400 1600 1800 2000 2200 2400 2600 3000
1 Heater Module 0.05 0.07 0.09 0.09 0.10 0.11 0.11 0.12 0.13 0.15
2 Heater Modules 0.15 0.16 0.16 0.16 0.17 0.17 0.17 0.18 0.18 0.19
Durablade Economizer 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05
EconoMi$er 0.05 0.09 0.13 0.17 0.22 0.27 0.32 0.39 0.45 0.53
COMPONENT
CFM
2250 2500 3000 3500 4000 4500 5000 5500 6000 6250
1 Heater Module 0.02 0.03 0.05 0.07 0.08 0.10 0.12 0.14 0.16 0.17
2 Heater Modules 0.03 0.05 0.07 0.09 0.12 0.14 0.16 0.19 0.21 0.20
Durablade Economizer 0.02 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.09
EconoMi$er 0.07 0.09 0.13 0.18 0.23 0.30 0.36 — — —
UNIT
50HJQ
MOTOR PULLEY TURNS OPEN
0
1
/
2
11
1
/
2
22
1
/
2
33
1
/
2
44
1
/
2
55
1
/
2
6
004 1090 1055 1025 990 960 925 890 860 825 795 760 — —
005 1185 1150 1115 1080 1045 1015 980 945 910 875 840 — —
006 1460 1425 1385 1350 1315 1275 1240 1205 1165 1130 1095 1055 1020
007 1585 1540 1490 1445 1400 1350 1305 1260 1210 1165 1120 — —
008 925 905 888 865 845 825 805 785 765 745 725 — —
012 1080 1060 1035 1015 990 970 950 925 905 880 860 — —
50TFQ004-01250HJQ004-012