Specifications
3
SEQUENCE OF OPERATION
50HJQ004-012 Units
COOLING, UNITS WITHOUT ECONOMIZER — When
thermostat calls for cooling, terminals G and Y1 are energized.
The indoor-fan contactor (IFC), reversing valve solenoid
(RVS1) and compressor contactor no. 1 (C1) are energized and
indoor-fan motor, compressor no. 1, and outdoor fans start. The
outdoor-fan motor(s) run continuously while unit is cooling.
HEATING, UNITS WITHOUT ECONOMIZER (Sizes
004-007) — Set system switch at AUTO. or HEAT position.
Set thermostat at desired temperature.
When the thermostat calls for heat, the IFC, outdoor-fan
contactor (OFC), and compressor contactor are energized. The
RVS is deenergized and switches position, and the indoor fan,
outdoor fan, and compressor are energized.
If the thermostat calls for a second stage of heat, the heater
contactor (HC) is energized and starts the electric heaters.
When the space temperature approaches the heating tem-
perature set point, heating stages cycle off.
HEATING, UNITS WITHOUT ECONOMIZER (Sizes
008,012) — Upon a request for heating from the space
thermostat, terminal W1 will be energized with 24 v. The IFC,
outdoor-fan contactor (OFC), C1, and C2 will be energized.
The reversing valves deenergize and switch position and the
indoor fan, outdoor fan, compressor no. 1, and compressor
no. 2 are energized.
If the space temperature continues to fall while W1 is
energized, W2 will be energized with 24 v, and the heater
contactor(s) (HC) will be energized, which will energize the
electric heater(s).
When the space thermostat is satisfied, W2 will be
deenergized first, and the electric heater(s) will be deenergized.
Upon a further rise in space temperature, W1 will be
deenergized, and the compressors will turn off.
COOLING, UNITS WITH DURABLADE ECONO-
MIZER — When the outdoor-air temperature is above the
outdoor-air thermostat (OAT) setting and the room thermostat
calls for cooling, compressor contactor no. 1 is energized to
start compressor no. 1 and the outdoor-fan motor(s). RVS1
(reversing valve solenoid) is energized. The indoor-fan motor
is energized and the economizer damper moves to the
minimum position. Upon a further call for cooling, compressor
contactor no. 2 will be energized (50HJQ008,012), starting
compressor no. 2. RVS2 is energized. After the thermostat is
satisfied, the damper moves to the fully closed position. When
using continuous fan, the damper moves to minimum position.
When the outdoor-air temperature is below the OAT setting
and the thermostat calls for cooling, the economizer dampers
move to the minimum position. If the supply-air temperature is
above 57 F, the damper continues to open until it reaches the
fully open position or until the supply-air temperature drops
below 52 F.
When the supply-air temperature falls to between 57 F and
52 F, the damper will remain at an intermediate open position.
If the supply-air temperature falls below 52 F, the damper will
modulate closed until it reaches the minimum position or until
the supply-air temperature is above 52 F. When the thermostat
is satisfied, the damper will move to the fully closed position.
When using continuous fan, the damper moves to minimum
position.
If the outdoor air alone cannot satisfy the cooling require-
ments of the conditioned space, economizer cooling is integrated
with mechanical cooling, providing second-stage cooling.
Compressor no. 1, reversing valve solenoid (RVS1) and the
outdoor fan will be energized and the position of the economizer
damper will be determined by the supply-air temperature.
Compressor no. 2 (50HJQ008,012) is locked out.
When the second stage of cooling is satisfied, the compres-
sor, RVS2, and outdoor-fan motor(s) will be deenergized.
The damper position will be determined by the supply-air
temperature.
When the first stage of cooling is satisfied, the damper will
move to fully closed position. When using continuous fan, the
damper moves to minimum position.
COOLING UNITS WITH ECONOMI$ER (EconoMi$er,
Johnson Actuator, was produced from Unit Serial Numbers
from 2009Gxxxxx to 0702Gxxxxx) (Sizes 004-007) — When
the outdoor-air temperature (OAT) is above the ECON SP set
point and the room thermostat calls for Stage 1 cooling, termi-
nals G and Y1 are energized. The indoor-fan contactor (IFC),
reversing valve solenoid (RVS1) and compressor contactor
no. 1 (C1) are energized and indoor-fan motor, compressor
no. 1, and outdoor fans start. The EconoMi$er damper
modulates to minimum position. The outdoor-fan motor(s) run
continuously while unit is cooling. After the thermostat is
satisfied, the damper modulates to the fully closed position
when the IFM is deenergized.
When the OAT is below the ECON SP setting and the room
thermostat calls for Stage 1 cooling (R to G + Y1), the
EconoMi$er modulates to the minimum position when the
IFM is energized. The EconoMi$er provides Stage 1 of cooling
by modulating the return and outdoor-air dampers to maintain
a 55 F supply air set point. If the supply-air temperature (SAT)
is greater than 57 F, the EconoMi$er modulates open, allowing
a greater amount of outdoor air to enter the unit. If the SAT
drops below 53 F, the outdoor air damper modulates closed to
reduce the amount of outdoor air. When the SAT is between 53
and 57 F, the EconoMi$er maintains its position.
If outdoor-air alone cannot satisfy the cooling requirements
of the conditioned space, and the OAT is above the MECH
CLG LOCKOUT set point, the EconoMi$er integrates free
cooling with mechanical cooling. This is accomplished by the
strategies below.
NOTE: Compressor has a 2-minute Minimum On, Minimum
Off, and Interstage delay timer.
1. If Y1 is energized, and the room thermostat calls for Y2
(2-stage thermostat), the compressor, RVS1 and OFM are
energized. The EconoMi$er damper is maintained at its
current position.
2. If Y1 is energized for more than 20 minutes, and Y2 is
not energized (whether or not a 2-stage thermostat is
used), the compressor, RVS1 and OFM are energized.
The EconoMi$er damper is maintained at its current
position.
3. If Y1 is energized, the compressors and RVS1 are already
energized (see Step 2) and the room thermostat calls for
Y2, the compressor continues to operate.
4. If compressor and RVS1 are energized and the thermostat
is satisfied, the compressor, RVS1, the OFM, and IFM are
deenergized and the EconoMi$er modulates closed.
When the OAT is below the MECH CLG LOCKOUT set
point, the compressors remain off.
COOLING, UNITS WITH ECONOMI$ER (EconoMi$er,
Johnson Actuator, was produced from Unit Serial Numbers
from 2009Gxxxxx to 0702Gxxxxx) (Sizes 008-014) — When
the outdoor-air temperature (OAT) is above the ECON SP set
point and the room thermostat calls for Stage 1 cooling, termi-
nals G and Y1 are energized. The indoor-fan contactor (IFC),
reversing valve solenoid (RVS1) and compressor contactor
no. 1 (C1) are energized and indoor-fan motor, compressor
no. 1, and outdoor fans start. The EconoMi$er damper
modulates to minimum position. The outdoor-fan motor(s) run
continuously while unit is cooling. After the thermostat is satis-
fied, the damper modulates to the fully closed position when
the IFM is deenergized.