Product data
9
I Determine job requirements.
Given:
Room Sensible Cooling Load . . . . . . . .8,200 Btuh
Room Total Cooling Load . . . . . . . . .11,000 Btuh
Entering-Air Temperature . . . . . . 80 F at 50% RH
Entering Water Temperature . . . . . . . . . . . . .45 F
Temperature Rise . . . . . . . . . . . . . . . . . . . . .10 F
Nominal Air Delivery . . . . . . . . . . . . . . . . 350 cfm
II Determine unit size and nominal cfm.
For an initial selection, choose a unit size that will
provide the required airflow (cfm). Refer to the
Physical Data table on page 3. At high speed, a
42WKN12 unit will provide 350 cfm.
III Determine total cooling capacity.
Refer to the cooling capacity table for 42WKN12
on page 10. Locate required entering dry bulb (edb)
and relative humidity (RH) conditions. Locate the
entering water temperature required. Under Total
Cooling (TC) column, a 42WKN12 unit at an enter-
ing-air temperature of 80 F dry bulb at 50% RH, an
entering water temperature of 45 F, and a water
temperature rise of 10 F, will provide 11,236 Btuh.
IV Determine sensible cooling capacity.
In cooling capacity table for 42WKN12, locate the
sensible cooling (SC) column and find that the
42WKN12 at the required conditions will provide
8,200 Btuh of sensible cooling at a water tempera-
ture rise of 10 F. The 42WKN12 will satisfy the job
requirements.
If additional SC were required, a larger unit or a
lower entering water temperature would be needed.
Selection procedure (42WKN12 unit example)