Specifications
10
CLEARANCE
"A"
CLEARANCE
"B"
CLEARANCE
36.000
DUCT CONNECTION
SPACE IF NO HOODS
"C"
SEE NOTE 3
FIELD TERMINAL STRIP
ACCESS
OUTSIDE AIR
HOOD
EXHAUST
HOOD
WHEEL AND FILTER
ACCESS
ROOF CURB
ROOF CURB
DI
SCONNECT
LOCATION
OUTSIDE AIR
HOOD
EXHAUST
HOOD
DUCT CONNECTION
SPACE
"G"
"F"
"E"
DUCT O.D.
"D"
"H"
"I" "J"
DUCT O.D.
"D"
DUCT I.D.
"D" - 2.000
DUCT I.D.
"K"
DUCT I.D.
"K"
S/A
R/A
ONLY DUCT SLEEVE AND
ERV AIR DIVIDER SHOWING
NOTES:
1. Clearance above cabinet is 24 inches.
2. Dimensions are in inches.
3. Size the roof curb to allow for a clearance of 10-in. (minimum) between
the bottom of the exhaust hood and the top of the insulated roof material.
62E UNIT TYPE
DIMENSIONS (in.)
A BCD E F G H I J K
7 36.000 36.000 1.869 28.995 31.734 36.375 32.176 31.186 11.984 36.905 12.813
2 18.000 36.000 1.179 36.495 39.171 43.875 39.663 38.673 16.215 41.239 16.497
3 18.000 40.000 3.795 42.295 44.847 49.675 45.463 44.473 16.215 41.099 19.272
4 18.000 50.000 4.238 52.495 55.066 59.875 55.673 54.673 21.132 49.631 23.997
5 24.000 64.000 4.516 64.915 67.486 72.295 68.093 67.093 27.131 53.013 30.207
6 18.000 75.000 9.542 75.495 78.066 82.875 78.673 77.673 27.131 58.963 35.247
Fig. 10 — 62E2-62E7 Unit Cabinet Dimensions