Electrical data
* Length shown is as measured 1 way along wire path between unit and service panel for maximum 2% voltage drop.
† Permissible limits of the voltage range at which the unit will operate satisfactorily.
‡ Time-delay fuse is recommended.
Typical installations
UNIT SIZE 060-12 080-16 100-20 120-20
UNIT VOLTS — HERTZ — PHASE 115 — 60 — 1
MINIMUM WIRE SIZE 14 14 14 14
MAXIMUM WIRE LENGTH (Ft)
* 36 34 29 26
MAXIMUM UNIT AMPS 10.1 10.6 12.6 13.9
OPERATING VOLTAGE RANGE (Min — Max)† 104 — 127
MAX FUSE CKT BKR (Amps)‡ 15
TRANSFORMER (24v) 40va
EXTERNAL CONTROL POWER AVAILABLE Heating 19va
Cooling 35va
AIR CONDITIONING BLOWER RELAY Standard