Product data

19
Electrical data
* Length shown is as measured 1 way along wire path between unit and service panel for maximum 2% voltage drop.
Permissible limits of the voltage range at which the unit will operate satisfactorily.
Time-delay fuse is recommended.
Typical installations
UNIT SIZE 060-12 080-16 100-20 120-20
UNIT VOLTS HERTZ PHASE 115 60 1
MINIMUM WIRE SIZE 14 14 14 14
MAXIMUM WIRE LENGTH (Ft)
* 36 34 29 26
MAXIMUM UNIT AMPS 10.1 10.6 12.6 13.9
OPERATING VOLTAGE RANGE (Min Max) 104 127
MAX FUSE CKT BKR (Amps) 15
TRANSFORMER (24v) 40va
EXTERNAL CONTROL POWER AVAILABLE Heating 19va
Cooling 35va
AIR CONDITIONING BLOWER RELAY Standard
A89242