Product data
14
600 700 900 1000 1100 1200800 1300 1500 1600 1700 1800 1900 2000 21001400
0
0.1
0.2
0.3
0.4
0.5
EXTERNAL STATIC PRESSURE (IWC)
CFM
0.6
0.7
0.8
0.9
1045
1035
1630
1750
1935
1685
1215
1225
1400
1430
LO (3 TONS COOLING)
M-LO (3-
1
/2 TONS COOLING)
HI (5 TONS COOLING)
M-HI (4 TONS COOLING)
M-HI (LOW-GAS HEAT 39°F AIR TEMP RISE)*
HI (LOW-GAS HEAT 44°F AIR TEMP RISE)*
HI (HIGH-GAS HEAT 51°F AIR TEMP RISE)*
M-HI (HIGH-GAS HEAT 45°F AIR TEMP RISE)*
MID (HIGH-GAS HEAT 40°F AIR TEMP RISE)*
MID (LOW-GAS HEAT 30°F AIR TEMP RISE)*
FURNACE SIZE
100,000 BTUH HEATING INPUT
60,000 BTUH COOLING
TWO-STAGE GAS HEATING WITH FILTER
SINGLE-SPEED COOLING WITH FILTER
COOLING AIRFLOW SELECTION IS APPROXIMATELY 350 CFM PER TON
Airflow shown is with factory supplied 1-in. washable filter(s). An airflow reduction of up to 7% may
occur when using the factory specified 4 5/16-inch wide, high-efficiency media filter.
3-14-96
*See Air Delivery Table for
jumper positions.
A96023