Specifications
XR03CX-HF.doc   XR03CX& 2/2 
dP  Defrost start  after Power failure: (n - y) n= the defrost  clock will reset;  y= start  defrost after a  power 
failure 
Fd  Defrost indicator delay: (0 – 99 min)  the time delay that  the  defrost indicator light will stay on after a 
defrost 
ALARMS 
AU  Maximum temperature alarm: (AL÷99°C) when this temperature is reached  the alarm is enabled, after 
the “Ad” delay time. 
AL  Minimum temperature alarm: (-55÷AU°C) when this temperature is reached the alarm is enabled, after 
the “Ad” delay time. 
Ad  Temperature  alarm  delay:  (0÷99  min)  time  interval  between  the  detection  of  an alarm condition and 
alarm signalling. 
dA  Exclusion of  temperature alarm  at  startup:  (0÷99  min)  time  interval between  the detection  of  the 
temperature alarm condition after instrument power on and alarm signalling. 
OTHER 
d2  Evaporator probe display (read only) 
Pt  Parameter code table 
rL  Software release 
8.  INSTALLATION AND MOUNTING 
Instrument  XR03CX  shall  be  mounted  on  vertical  panel,  in  a 
29x71 mm hole, and fixed using the special bracket supplied. 
The temperature range allowed for correct operation is 0÷60 °C. 
Avoid  places  subject  to  strong  vibrations,  corrosive  gases, 
excessive  dirt  or  humidity.  The same  recommendations  apply to 
probes. Let air circulate by the cooling holes. 
9.  ELECTRICAL CONNECTIONS 
The instrument is provided with Fast-on connections. Before connecting cables make sure  the power  supply 
complies with  the instrument’s requirements. Separate the probe cables from  the  power supply cables, from 
the outputs and the power connections. Do not exceed the maximum current allowed on each relay, in case of 
heavier loads use a suitable external relay. 
9.1  PROBES 
The probes shall be mounted with the bulb angled upward to prevent damages due to casual liquid infiltration. 
It is recommended to place the thermostat probe away from air streams to correctly measure the average room 
temperature. Place the defrost termination probe among the evaporator fins in the coldest place, where most 
ice is formed to prevent premature defrost termination. 
10.  HOW TO USE THE HOT KEY 
10.1  HOW TO PROGRAM THE HOT KEY FROM THE INSTRUMENT (UPLOAD) 
1.  Program one controller with the front keypad. 
2.  When the controller is ON, insert the “Hot key” and push   key; the  "uP" message appears followed a 
by flashing “En” 
3.  Push “SET” key and the “En” will stop flashing. 
4.  Turn OFF the instrument remove the “Hot Key”, then turn it ON again. 
NOTE:  the “Er”  message  is  displayed  for failed  programming. In  this  case  push  again  o key  if  you want  to 
restart the upload again or remove the “Hot key” to abort the operation. 
10.2  HOW TO PROGRAM AN INSTRUMENT USING HOT KEY (DOWNLOAD) 
1.  Turn OFF the instrument. 
2.  Insert a programmed “Hot Key” into the 5 PIN receptacle and then turn the Controller ON. 
3.  Automatically  the  parameter  list  of  the  “Hot  Key”  is  downloaded  into  the  Controller  memory,  the  “do” 
message is blinking followed a by flashing “En”. 
4.  After 10 seconds the instrument will restart working with the new parameters. 
5.  Remove the “Hot Key”.. 
NOTE:  the “Er”  message  is  displayed  for failed  programming. In  this  case push  again  o  key if  you  want to 
restart the upload again or remove the “Hot key” to abort the operation. 
11.  ALARM SIGNALLING 
Mess. 
Cause 
Outputs 
"P1" 
Room probe failure 
Compressor output according to “Cy” e “Cn” 
"P2" 
Evaporator probe failure 
Defrost end is timed 
"HA" 
Maximum temperature alarm 
Outputs unchanged 
"LA" 
Minimum temperature alarm 
Outputs unchanged 
“EA” 
External alarm 
Outputs unchanged 
“CA” 
Serious external alarm 
All outputs OFF. 
“nP’ 
No Parameters in L1 
Outputs unchanged 
“dA” 
Door Open 
Compressor and fans restart 
11.1  ALARM RECOVERY 
Probe alarms P1” and “P2” start a few seconds after the fault in the related probe; they automatically stop a 
few seconds after the probe restarts normal operation. Check connections before replacing the probe, 
 Temperature alarms “HA” and “LA” automatically stop as soon when temperature returns to normal values. 
Alarms “EA” and “CA” (with iF=bL) recover as soon as the digital input is disabled. 
12.  TECHNICAL DATA 
Housing: self extinguishing ABS. 
Case: frontal 32x74 mm; depth 60mm; 
Mounting: panel mounting in a 71x29mm panel cut-out 
Protection: IP20; Frontal protection: IP65 
Connections: disconnectable terminal block ≤ 2,5 mm
2
 wiring and 6.3mm fast-on’s 
Power supply: according to the model ±10%; 230Vac ±10%, 50/60Hz, 110Vac ±10%, 50/60Hz 
Power absorption: 3.5 VA max 
Display: 2 digits, red LED, 14,2 mm high; Inputs: 2 NTC Probes 
Relay outputs: compressor; 16FLA/96LRA, AUX: 10A 
Data storing: on the non-volatile memory (EEPROM). 
Kind of action: 1B; Pollution grade: 2; Software class: A.; 
Rated impulsive voltage: 2500V; Overvoltage Category: II 
Ambient temperature: 0÷60 °C; Storage temperature: -30÷85 °C. 
Relative humidity: 20÷85% (no condensing) 
Measuring and regulation range: NTC -40÷110°C (-40÷230°F);  
Resolution: 0,1 °C or 1°C or 1 °F (selectable); Accuracy (ambient temp. 25°C): ±0,7 °C ±1 digit 
13.  CONNECTIONS 
NOTE: Fast-on 
maximum current 
16A 
14.  DEFAULT SETTING VALUES 
LBL 
DESCRIPTION 
RANGE 
DEFAULT 
LEVEL 
REGULATION 
Hy 
Differential 
1 ÷ 45°F 
2 °F 
L1 
LS 
Minimum Set Point 
-67°F÷SET 
25°F 
L2 
US 
Maximum Set Point 
SET÷99°F 
40°F 
L2 
ot 
First probe calibration 
-18 +18°F 
0°F 
L2 
P2 
Second probe presence 
n – Y 
y 
L2 
oE 
Second probe calibration 
18 +18°F 
0°F 
L2 
AC 
Anti-short cycle delay 
0 ÷ 50 min 
2 
L2 
Cy 
Compressor ON time faulty probe 
0 ÷ 99 min 
12 
L2 
Cn 
Compressor OFF time faulty probe 
0 ÷ 99 min 
4 
L2 
DISPLAY 
CF 
Measurement units 
°C - °F 
°F 
L2 
rE 
Resolution (only for °C) 
dE – in 
in 
L2 
Ld 
Default Display 
P1 - P2 
P1 
L2 
dy 
Display delay 
0 ÷ 15 min 
0 
L2 
DEFROST 
dE 
Defrost termination temperature 
58÷99°F 
52 °F 
L1 
id 
Interval between defrost cycles 
0 ÷ 99 hours 
4 
L1 
nd 
Maximum length for defrost 
0 ÷ 99 min. 
28 
L1 
dF 
Display during defrost 
rt – it – dF - St 
rt 
L2 
dP 
Defrost After Power Failure 
n- y 
y 
L2 
Fd 
Defrost Indicator delay after defrost 
0 – 99min 
20 
L2 
ALARMS 
AU 
Maximum temperature alarm 
ALL÷99°F 
55 °F 
L2 
AL 
Minimum temperature alarm 
-55°C÷ALU/-
67°F÷ALU 
20 °F 
L2 
Ad 
Temperature alarm delay 
0 ÷ 99 min 
5 
L2 
dA 
temperature alarm delay at startup 
0 ÷ 99 min 
90 
L2 
OTHER 
d2 
Evaporator probe display 
Read Only 
- - - 
L1 
Pt 
Parameter code table 
Read Only 
- - - 
L2 
rL 
Firmware release 
Read Only 
- - - 
L2 