ARCHITECTS AND ENGINEERS’ MANUAL PREMIER SERIES 52P COMFORT SERIES 52C PACKAGED TERMINAL AIR CONDITIONERS AND HEAT PUMPS CONTENTS Page Page APPLICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3,4 Seamless Basepan . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Condensate Drain Valve. . . . . . . . . . . . . . . . . . . . . . . . 11 Condensate Removal System. . . . . . . . . . . . . . . . . . . . 11 Heat Pumps Pay Their Own Way. . . . . . . . . . . . . . . . .
Valued Carrier Customer, Carrier’s Architects and Engineer’s manual has been specifically developed to make your product and accessory selection easier and faster. This manual will help you customize your application to ensure the greatest comfort for your guests and the highest reliability and lowest costs for you. Enjoy the ultimate in comfort, humidity control, and energy savings with Carrier’s complete line of Packaged Terminal Air Conditioning (PTAC) products.
APPLICATIONS Whether you are designing a new structure or replacing packaged terminal air conditioning units in an existing building, Carrier will meet your needs.
APPLICATIONS (cont) APPLICATION CONSIDERATIONS Oversizing If a PTAC unit is oversized (cooling capacity is greater than required capacity for the specific application), the unit will cool the space down to the desired temperature too quickly. The unit will cycle on and off, however, dehumidification only takes place when the unit is operating. The result of this type of application in a hot and/or humid climate would be a cool, yet excessively humid, space.
PRODUCT OVERVIEW (52P AND 52C) This section summarizes product features covered in detail in later sections of this manual: 2 AIR FILTERS LOUVERED FRONT PANEL 2-WAY DISCHARGE GRILLE WIRE SCREEN FRESH AIR CONTROL ARM BI-MOLDED CONDENSER SHROUD CONTROL DOOR INDOOR COIL THERMOSTAT WITH TEMPERATURE LIMITER MODE SELECTION SWITCH ACCESS TO ELECTRICAL COMPONENTS THROUGH CONTROL BOX DOOR COPPER TUBE ALUMINUM FIN COILS BASEPAN FOR CONDENSATE REMOVAL ROTARY COMPRESSORS WALL SLEEVE Polymer, Metal or Ext
PRODUCT FEATURES AND BENEFITS (52P AND 52C) The 52P and 52C models are a single-package, through-the-wall unit for heating and cooling hotel rooms, offices, apartments, condominiums, and residential additions.
NO-RUST WEATHER LAST™ WALL SLEEVE AND FRONT PANEL The indoor front panel and polymer wall sleeve use nonmetallic compounds that never rust or corrode, do not support combustion, and do not give off toxic fumes. The weather-resistant feature exceeds requirements of Underwriters’ Laboratories and resists damage caused by impact and scratching. The Weather Last feature also insulates and has up to 10 times the acoustic absorption of metal cabinets.
PRODUCT FEATURES AND BENEFITS (cont) TWO-PIECE LIFETIME INDOOR FILTER New two-piece removable filters easily slide in and out from the front of the PTAC unit and are interchangeable. The front panel does not need to be removed to access or change the filters. The filters are washable and permanent. Two-Piece Indoor Filter WASHABLE VENT AIR FILTER The unique vent system is activated by a two-position control. Fresh outside air is redirected by the vent door to an inside low-pressure area.
POWER CORD FOR 265-V UNITS A power cord is included for 265-v units. The power cord is 18 in. long (cord extends 15 in. from bottom of front panel) and per UL and National Electrical codes must plug into an electrical subbase. 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 265-V Unit with Power Cord BI-MOLDED CONDENSER SHROUD BI-MOLDED CONDENSER SHROUD The bi-molded condenser shroud provides easy access for service and maintenance of the condenser coil and related components.
PRODUCT FEATURES AND BENEFITS (cont) EASY ACCESS TO CHASSIS Access to the chassis simply requires removing four screws and then sliding the chassis out of the sleeve for service. CHASSIS ATTACHMENT SCREWS (SAME LOCATION ON OPPOSITE SIDE) Easy Service Access HIDDEN CONTROLS Fan Cycle Switch The factory-wired control box houses all control components and is quickly accessible without removing the chassis from the wall sleeve.
ENHANCED COPPER TUBING Enhanced copper tubing is more efficient and durable and can be repaired in the field, if required. Because copper is a very stable metal, it is durable and resists corrosion.
PRODUCT FEATURES AND BENEFITS (cont) HEAT PUMPS PAY THEIR OWN WAY How The Heat Pump Works Heat pump models are available at a nominal additional cost. In many locales, the payback is realized in just a few months. Cost and payback details are provided on the next page. Special Features Two-Stage Indoor Thermostat: In Hot Weather: The indoor thermostat senses the indoor temperature and automatically turns on the electric heat to warm the room quickly.
HEAT PUMP ENERGY SAVINGS Heat pumps save more on operating costs during the heating cycle than heat/cool models. The table below shows that the higher initial cost of purchasing a heat pump is quickly made up in lower operating costs. Use the map to identify the climate zone’s designated number. Reading down the left-hand column of the table, select the cost/kWh rate in this zone that most closely approximates your local rate.
ORDERING DATA (52P AND 52C) For immediate assistance, call 1-800-827-7435 or contact your local Carrier dealer. Standard Unit • Chassis with front panel • Electro-mechanical controls • Cord-connected chassis for 230/208-v and 265-v units Lead-time: Many models are in stock for immediate delivery; call for lead-times.
FACTORY-INSTALLED OPTIONS (52P AND 52C) WALL THERMOSTAT CONTROL (RC,RP) Carrier’s wall thermostat control option includes: • a standard chassis with front panel • factory-installed low voltage controls for remote thermostat operation • indoor coil freeze protection • user accessible selector switch for high or low fan speed A wall thermostat must be ordered separately. See page 50 for a diagram of multiple PTAC units controlled by a single thermostat.
FIELD-INSTALLED ACCESSORIES (52P AND 52C) WALL SLEEVES The sleeve's alpine mist color (a shade of beige) closely matches the front panel and blends in well with any inside or outside decor. The polymer wall sleeve comes in both insulated (factory installed) or non-insulated, to meet the requirements of every application. Weather Last™ Wall Sleeve For the best performance and longest life, Carrier recommends genuine Carrier wall sleeves for all installations.
Insulated Metal Wall Sleeves 42 IN. Part No.: SLEEVE-STEEL-1PK Part No.: SLEEVE-EXT24-1PK Part No.: SLEEVE-EXT26-1PK Part No.: SLEEVE-EXT28-1PK Carrier's metal wall sleeves are available in a variety of sizes for most applications and difficult installations. Choose from 141/2″, 24″, 26″, or 28″ standard depth sizes. All metal wall sleeves come with factoryinstalled insulation, designed to minimize heat loss, reduce outdoor noise transmissions into the room and prevent sleeve sweating.
FIELD-INSTALLED ACCESSORIES (52P AND 52C) (cont) OUTDOOR GRILLES Polymeric Architectural Outdoor Grilles (Louvered) Carrier recommends only the use of Carrier-supplied grilles for use on the 52P and 52C series units. However, the architectural designs of a building may dictate the use of special or oversized grilles and/or louvers.
Outdoor Grille Selection IMPORTANT: If you wish to use a grille not made by Carrier for your Carrier unit(s), contact the Carrier Application Engineering Group at 1-800-894-6449. X Y The following guidelines must be followed in the initial selection of any alternate exterior grille or louver: 1. The louver must have a minimum of 65% free area. Free area is the minimum area of the opening in an air inlet or outlet in which air can pass. Free Area (%) = X/Y. 2.
FIELD-INSTALLED ACCESSORIES (52P AND 52C) (cont) SUBBASE Part No.: SUBBASE-NON-ELEC Part No.: SUBBASE-230V-15A Part No.: SUBBASE-230V-20A Part No.: SUBBASE-230V-30A Part No.: SUBBASE-265V-15A Part No.: SUBBASE-265V-20A Part No.: SUBBASE-265V-30A Part No.: SUBBASE-HARDWIRE Part No.: LEVELING-LEGS This decorative subbase supports the unit and is available in three basic models: non-electrical, electrical, and hardwired.
Leveling legs Part No.: LEVELING-LEGS Leveling legs attach easily to Carrier’s wall sleeve and offer accurate leveling and support for units without a subbase. Leveling legs are adjustable from 31/4 in. to 51/2 in. Leveling-Legs Subbase Fuse Kit Part No.: SUBBASE-FUSE-15A Part No.: SUBBASE-FUSE-20A Part No.: SUBBASE-FUSE-30A The fuse kit provides in-line overcurrent protection at the unit when required by NEC (National Electric Code) or local codes.
FIELD-INSTALLED ACCESSORIES (52P AND 52C) (cont) THERMOSTATS Carrier’s full line of wall thermostats are designed to enhance every PTAC application. Wall thermostats are simple and easy to use. Wall thermostats provide better temperature and humidity control as they can be placed in an optimal position in the room. NOTE: See page 50 for a wiring diagram of multiple PTAC units controlled by one thermostat. Digital Programmable Thermostat Part No.: TSTATCCPAC01-B (for heat/cool models) Part No.
Wall Thermostat Interface Retrofit Kit Part No.: RC-FIELDKIT230HC Part No.: RC-FIELDKIT230HP Part No.: RC-FIELDKIT265HC Part No.: RC-FIELDKIT265HP The Wall Thermostat Interface Retrofit Kit allows PTAC units with standard unit-mounted controls to be field converted for use with wall thermostat controls. WA L L T MO HER S TA OM T C FOR T Wall Thermostat Interface Retrofit Kit 2-Speed Fan Control from Wall Thermostat 2 4 5 Part No.
FIELD-INSTALLED ACCESSORIES (52P AND 52C) (cont) Condensate Drain Kit Part No.: DRAIN-KIT-4PK This universal drain kit may be used internally or externally to route condensate to a drainage system. It can be field-installed on any Carrier wall sleeve. Although Carrier’s units are designed to dissipate all the condensate generated during normal cooling, there may be times when abnormal conditions cause more condensate than the unit can dissipate.
Power Vent with Power Door Kit Part No.: PWR-VENT-DOOR230 Part No.: PWR-VENT-DOOR265 Carrier's power vent kit, utilizing a specially designed fan, when installed in the unit's fresh air vent, will supply up to 95 CFM of outside air into the room. The power vent will only operate when the unit fan runs, and the unit will automatically open or close the vent door, depending on the operation of the fan. The kit comes pre-assembled from the factory and is very easy to install.
FIELD-INSTALLED ACCESSORIES (52P AND 52C) (cont) Replacement Filters Part No.: AIR-FILTER-10PK The Carrier 52P and 52C model replacement air filters come in packages of 10. The filters save energy by preventing the evaporator coils from being plugged with dirt and lint. These economical and sturdy filters are interchangeable and may be washed, vacuumed, and reused. Easily Replaceable Filters Energy Management Kit Part No.
DIMENSION DRAWINGS AND INSTALLATION DATA — NEW CONSTRUCTION TYPICAL WALL INSTALLATION If practices are unknown, consult your local architect or building contractor. Installed wall sleeve must be level from side to side and front to back. Proper building practices must be used when constructing a wall opening to support a PTAC wall sleeve and chassis. DISCHARGE GRILLE 3’-6” (1067) ACCESSORY WALL SLEEVE HINGED CONTROL ACCESS DOOR REMOVABLE FRONT PANEL (SEE NOTE #8) 208/230-V SERVICE CORD 1’-10” (558.
DIMENSION DRAWINGS AND INSTALLATION DATA — NEW CONSTRUCTION (cont) WALL SLEEVE MOUNTING DIMENSIONS FOR STANDARD AND ACCESSORY GRILLES JACK STUDS MAIN STUD HEADER- 4’ x 4’ OR (2) 2’ x 4’ ON EDGE 16 1/4” 42 1/8” Standard Polymer Non-Insulated Wall Sleeve Standard Polymer Insulated Wall Sleeve Standard Metal Insulated Wall Sleeve JACK STUD 42” CRIPPLE 16” FLOOR SUB-FLOOR Framing and Minimum Wall Sleeve Opening 24”/26”/28” Extended Metal Insulated Wall Sleeve NOTES (ALL SLEEVES): 1.
TYPICAL WALL INSTALLATION NOTES: 1. Sleeve may be flush mounted to floor, but front panel may have to be notched to accommodate service cord. 2. If more than 4 in. of sleeve projects into room, an accessory subbase must be used for support. 3. For walls 2 in. thick or less, an accessory subbase must be used for support. 4. Caulk around sleeve on both indoor and outdoor sides.
DIMENSION DRAWINGS AND INSTALLATION DATA — NEW CONSTRUCTION (cont) MINIMUM CLEARANCE FOR INDOOR AND OUTDOOR DISCHARGE AIR Blocking indoor or outdoor discharge air could cause premature failure of unit. 15” MINIMUM DISTANCE FROM FRONT PANEL TO OBJECTS IN ROOM 36" MINIMUM DISTANCE FROM SLEEVE TO BUILDING WALLS, SHRUBS, etc. 52P and 52C Indoor and Outdoor Discharge Air Circulation OUTDOOR VIEW GRILLE MOUNTING HOLES WALL S L EEVE 2 3/8” (60.
TYPICAL LATERAL DUCT INSTALLATION WALL REGISTER ALTERNATE EXTENSION POSITION* LATERAL DUCT EXTENSION PLENUM END CAP 3’-8” (117.6) WALL MOLDING 3’-11 1/2” (1206.5) MAX. REVERSIBLE AIR GRILLE 3’-11 1/2” (1206.5) MAX. *Only one Lateral Duct Extension may be installed per unit. Lateral duct extensions may be installed on either side of the unit. NOTE: For all applications with an accessory lateral duct, sleeve must extend into the room a minimum of 3 inches.
DIMENSION DRAWINGS AND INSTALLATION DATA — NEW CONSTRUCTION (cont) 52P AND 52C WITH SUBBASE 0’-3 1/4” MIN. (83) 0’-5 1/2” MAX. (140) 0’-0 7/8” (22) SUBBASE ACCESS COVERS OUTSIDE WALL SEE NOTES 1 9/16” (39.7) SIDE 19 1/2” (495.3) (3) 7/8” (22.2) DIA. KNOCKOUTS (3) 1 1/8” (28.6) DIA. KNOCKOUTS REAR VIEW ACCESSORY SUBBASE ELECTRICAL CONNECTIONS SUBBASE LEVELING BOLTS ACCESSORY DRAIN (EXTERNAL OR INTERNAL) NOTES: 1.
WALL THERMOSTAT CONNECTIONS FAN SPEED CONTROL KNOB COVER FOR TERMINAL CONNECTION POWER CORD ACCESS COVER R Y W G O C POWER CORD THERMOSTAT Terminal Connector Removal and Replacement Control Box Terminal Cover for Wall Thermostat Models 33
PRODUCT DATA (52P) PERFORMANCE AND ELECTRICAL DATA MODEL 52PQ (230/208-1-60) MODEL NUMBER 52PQ 207---3 307---3 209---3 309---3 212---3 312---3 512---3 215---3 315---3 515---3 CAPACITY* (Btuh) AMPS WATTS VOLTAGE HEATER EER COP† RANGE Heating kW Cooling Heating (Volts) Cooling Heating** Cooling Rev. Cyc. Electric 7,200/ 7,100 6,300/ 6,300 7,800/ 6,400 2.3 12.7/12.7 3.4/3.4 2.7/2.9 10.4/ 9.5 567/ 559 2393/1985 7,200/ 7,100 6,300/ 6,300 11,600/ 9,700 3.4 12.7/12.7 3.4/3.4 2.7/2.9 15.2/14.
PERFORMANCE AND ELECTRICAL DATA MODEL 52PQ (265-1-60) MODEL NUMBER 52PQ 207---4 307---4 209---4 309---4 212---4 312---4 512---4 215---4 315---4 515---4 CAPACITY* (Btuh) Heating Cooling Rev. Cycle Electric 7,200 6,300 7,800 7,200 6,300 11,600 9,100 7,700 7,800 9,100 7,700 11,600 12,100 10,800 7,800 12,100 10,800 11,600 12,100 10,800 17,000 14,700 14,100 7,800 14,700 14,100 11,600 14,700 14,100 17,000 FAN MOTOR MODEL POWER Full NUMBER FACTOR Horsepower Load 52PQ % Amps 207---4 97 0.075 0.
PRODUCT DATA (52P) (cont) PERFORMANCE AND ELECTRICAL DATA MODEL 52PC AND PE (230/208-1-60) 52PC performance and electrical data is the same as 52PE without electric heat.
PERFORMANCE AND ELECTRICAL DATA MODEL 52PC AND PE (265-1-60) 52PC performance and electrical data is the same as 52PE without electric heat. MODEL NUMBER 52PE 207---4 307---4 209---4 309---4 212---4 312---4 512---4 215---4 315---4 515---4 CAPACITY* (Btuh) Cooling Heating HEATER kW EER 7,200 7,200 9,100 9,100 12,100 12,100 12,100 15,100 15,100 15,100 7,800 11,600 7,800 11,600 7,800 11,600 17,000 7,800 11,600 17,000 2.3 3.4 2.3 3.4 2.3 3.4 5.0 2.3 3.4 5.0 12.7 12.7 11.5 11.5 11.1 11.1 11.1 10.0 10.
PRODUCT DATA (52C) PERFORMANCE AND ELECTRICAL DATA MODEL 52CQ (230/208-1-60) MODEL NUMBER 52CQ 207---3 307---3 209---3 309---3 212---3 312---3 512---3 215---3 315---3 515---3 CAPACITY* (Btuh) AMPS WATTS VOLTAGE HEATER EER COP† RANGE Heating kW Cooling Heating (Volts) Cooling Heating** Cooling Rev. Cyc. Electric 7,000/ 6,900 6,100/ 6,000 7,800/ 6,400 2.3 11.1/11.1 3.1/3.1 2.7/2.9 10.4/ 9.5 631/ 622 2393/1985 7,000/ 6,900 6,100/ 6,000 11,600/ 9,700 3.4 11.1/11.1 3.1/3.1 2.7/2.9 15.2/14.
PERFORMANCE AND ELECTRICAL DATA MODEL 52CQ (265-1-60) MODEL NUMBER 52CQ 207---4 307---4 209---4 309---4 212---4 312---4 512---4 215---4 315---4 515---4 CAPACITY* (Btuh) Heating Cooling Rev. Cycle Electric 7,000 6,100 7,800 7,000 6,100 11,600 8,900 7,700 7,800 8,900 7,700 11,600 12,000 10,800 7,800 12,000 10,800 11,600 12,000 10,800 17,000 14,600 14,100 7,800 14,600 14,100 11,600 14,600 14,100 17,000 FAN MOTOR MODEL POWER Full NUMBER FACTOR Horsepower Load 52CQ % Amps 207---4 97 0.075 0.
PRODUCT DATA (52C) (cont) PERFORMANCE AND ELECTRICAL DATA MODEL 52CE (230/208-1-60) MODEL NUMBER 52CE 207---3 307---3 209---3 309---3 212---3 312---3 512---3 215---3 315---3 515---3 MODEL NUMBER 52CE 207---3 307---3 209---3 309---3 212---3 312---3 512---3 215---3 315---3 515---3 CAPACITY* (Btuh) Cooling Heating HEATER kW EER 7,000/ 6,900 7,000/ 6,900 9,000/ 8,900 9,000/ 8,900 12,000/11,900 12,000/11,900 12,000/11,900 14,600/14,300 14,600/14,300 14,600/14,300 7,800/ 6,400 11,600/ 9,700 7,800/ 6,400 11
PERFORMANCE AND ELECTRICAL DATA MODEL 52CE (265-1-60) MODEL NUMBER 52CE 207---4 307---4 209---4 309---4 212---4 312---4 512---4 215---4 315---4 515---4 CAPACITY* (Btuh) Cooling Heating HEATER kW EER 7,000 7,000 8,900 8,900 12,000 12,000 12,000 14,600 14,600 14,600 7,800 11,600 7,800 11,600 7,800 11,600 17,000 7,800 11,600 17,000 2.3 3.4 2.3 3.4 2.3 3.4 5.0 2.3 3.4 5.0 11.1 11.1 10.7 10.7 10.1 10.1 10.1 9.5 9.5 9.5 FAN MOTOR MODEL POWER Full NUMBER FACTOR Horsepower Load 52CE % Amps 207---4 97 0.
EXPANDED RATINGS DATA (52P AND 52C) COOLING PERFORMANCE ALL 7000 NOMINAL BTUH MODELS Evaporator entering air temp. — 80 F Evap. air — 260 CFM TEMP (F) AIR ENT. COND (40% RH) 80 85 90 95 100 105 110 115 MBtuh kW I MBtuh kW I MBtuh kW I MBtuh kW I MBtuh kW I MBtuh kW I MBtuh kW I MBtuh kW I 57.00 7.05 0.54 2.35 6.93 0.56 2.45 6.85 0.59 2.56 6.76 0.61 2.67 6.70 0.64 2.79 6.57 0.67 2.91 6.42 0.70 3.03 6.28 0.73 3.17 EVAP AIR — EWB (F) 62.00 67.00 7.23 8.04 0.54 0.55 2.36 2.37 7.08 7.90 0.57 0.57 2.
COOLING PERFORMANCE (cont) 52PQ 12,000 NOMINAL BTUH MODELS Evaporator entering air temp. — 80 F Evap. air — 350 CFM TEMP (F) AIR ENT. COND (40% RH) 80 85 90 95 100 105 110 115 MBtuh kW I MBtuh kW I MBtuh kW I MBtuh kW I MBtuh kW I MBtuh kW I MBtuh kW I MBtuh kW I 57.00 11.79 0.97 4.29 11.60 1.02 4.49 11.39 1.07 4.69 11.17 1.12 4.90 11.66 1.17 5.12 12.16 1.22 5.34 12.69 1.27 5.57 13.23 1.32 5.81 EVAP AIR — EWB (F) 62.00 67.00 11.95 12.65 0.97 0.95 4.27 4.17 11.74 12.48 1.02 1.00 4.48 4.38 11.49 12.
SOUND DATA (52P AND 52C) INDOOR SOUND DATA (52P AND 52C) The tables below indicate the approximate indoor and outdoor sound levels. Tests were conducted in the Carrier Sound Testing Laboratory according to ARI (Air Conditioning and Refrigeration Institute) Noise Rating Standard 300 for non-ducted indoor airconditioning equipment.
WIRING DIAGRAMS (52P AND 52C) COMPONENT LEGEND Component Connection (Marked) CAP COMP FM FCS HTR IT OFT OL PLS RVS SLS ST SW — — — — — — — — — — — — — Component Connection (Unmarked) Accessory or Optional Wiring To Indicate Common Potential Only Not To Represent Wire Capacitor Compressor Fan Motor Fan Cycle Switch Heater Indoor Thermostat Outdoor Frost Thermostat Overload Primary Limit Switch Reversing Valve Solenoid Secondary Limit Switch Start Thermistor Switch NOTES: 1.
WIRING DIAGRAMS (52P AND 52C) (cont) TYPICAL THERMOSTAT INTERFACE T’STAT OUTPUT: RC CONTROLER OUTPUT: UNIT OPERATION: ‘G’ — 24 VAC ‘FR’ — LINE VAC FAN ‘G’ — 0 VAC ‘FR’ — 0 VAC ‘Y’ — 24 VAC ‘HR1 & HR2’ — LINE VAC HEATING ‘O’ — 0 VAC ‘RVR’ — LINE VAC ‘W’ — 24 VAC ‘HR1 & HR2’ — LINE VAC HEATING ‘Y’ — 24 VAC ‘CR’ — LINE VAC COOLING ‘O’ — 24 VAC ‘RVR’ — 0 VAC ‘R’ — 24 VAC ‘R’ — 24 VAC OUTPUT POWER TO WALL ‘C’ — COMMON ‘C’ — COMMON THERMOSTAT 1.
52PE and 52CE — Typical Wiring Schematic for Standard Heat/Cool Units 47
WIRING DIAGRAMS (52P AND 52C) (cont) 52PE and 52CE — Typical Wiring Schematic for Wall Thermostat Control Heat/Cool Units 48
FRONT DESK SWITCH PANEL ROOM 100 ROOM 101 ROOM N FIELD-SUPPLIED 24-V TRANSFORMER (SEE NOTE 1) B W PTAC #1 AWG B PTAC W — — — — B B W W PTAC #N PTAC #2 LEGEND American Wire Gage Black Packaged Terminal Air Conditioner White NOTES: 1. To size transformer, use the following equation: Quantity of PTAC units x 12 va = Transformer Size (va) Example: 110 PTAC Units x 12 va = 1320 vaTransformer 2. Following are recommended wire sizes: AWG WIRE SIZE NO.
WIRING DIAGRAMS (52P AND 52C) (cont) MASTER PTAC R R Y Y W W G G O O C C T’STAT R UNIT 1 Y W G O C R UNIT 2 Y W G O C All units must be connected to same ground source. To accomplish this, be sure to connect all units back to the same breaker box. R UNIT 3 Y W NOTES: 1. Do not daisy chain R (24 VAC). 2. Maximum of 4 PTAC units can be connected to one single wall thermostat.
GUIDE SPECIFICATIONS PACKAGED TERMINAL COOLING UNIT WITH HEAT PUMP OR ELECTRIC HEATING HVAC Guide Specifications Size Range: via an enclosed truck. Chassis must also be able to withstand an impact force of 10 g’s and a random continuous force of 1g, during shipping. B. Chassis, wall sleeves, and grilles shall be shipped in separate cartons. Universal handling instructions shall be defined and visible on the carton, from front, back and sides. C.
GUIDE SPECIFICATIONS (cont) D. E. F. G. H. Safeties: Compressor shall have automatic reset, over temperature and over current protection. The fan motor shall have an inherent, automatic reset over temperature protection. The electric heater shall have two over temperature protectors. I. Front Panel (supplied with chassis): Front panel shall be constructed of a polymer material to resist breakage and corrosion. It shall have a front louvered surface with integrated control door and air filters.
P. LATERAL DUCT SYSTEM (optional): The lateral duct system shall allow one system to heat or cool two adjacent rooms, with up to a maximum of 30% of the discharge air being diverted to the adjoining room (a return air path must be provided from the adjoining room). The lateral duct kit consists of two main components, the plenum and the extension duct. In addition, the Kit includes an adjustable chassis discharge air grille, adjustable wall register and decorative wall molding for duct extension.
NOTE: Service and Maintenance items excluded in this warranty may be covered by a separate service agreement through the seller at time of purchase. CARRIER WILL NOT BE RESPONSIBLE FOR: 1. CLEANING REQUIRED PRIOR TO WARRANTY REPAIR. 2. Standard maintenance, cleaning or damage resulting from failure to perform normal maintenance as outlined in the owner’s manual. 3. Instruction on methods of control and use of air conditioning unit after initial installation. 4.
ACCESSORY LIST ACCESSORY Wall Sleeves FORM NUMBER 52S-48SI 52S-50SI 52S-49SI N/A 52C,P-20SI Exterior Grilles* 52S-59SI 52S-58SI PART NUMBER WALL-SLEEVE-1PK WALL-SLEEVE-9PK SLEEVE-INSUL-1PK SLEEVE-STEEL-1PK SLEEVE-EXT24-1PK SLEEVE-EXT26-1PK SLEEVE-EXT28-1PK SLEEVE MOLDING FR-SLEEVE-EXT 52C,P-11SI GRILLE-ALU-STAMP GRILLE-PLA-ALPIN GRILLE-PLA-BROWN GRILLE-PLA-BEIGE GRILLE-ALU-CLEAR GRILLE-ALU-WHITE GRILLE-ALU-BRONZ GRILLE-ALU-MBRNZ GRILLE-ALU-BROWN GRILLE-ALU-BEIGE GRILLE-ALU-ALPIN GRILLE-ALU-PEACH GRIL