50TCA04---A07 Nominal 3 to 6 Tons With Puron® (R410A) Refrigerant Service and Maintenance Instructions TABLE OF CONTENTS SAFETY CONSIDERATIONS SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . 1 Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.
! Routine Maintenance WARNING ELECTRICAL OPERATION HAZARD Failure to follow this warning could result in personal injury or death. Units with convenience outlet circuits may use multiple disconnects. Check convenience outlet for power status before opening unit for service. Locate its disconnect switch, if appropriate, and open it. Tag-- out this switch, if necessary.
located on the rear side of the unit, above the evaporator/return air access panel. (See Fig. 1.) To remove the filters: 1. Grasp the bottom flange of the upper panel. 2. Lift up and swing the bottom out until the panel disengages and pulls out. 3. Reach inside and extract the filters from the filter rack. 4. Replace these filters as required with similar replacement filters of same size. To re-- install the access panel: C07156 Fig.
inside surfaces. Check belt tension by using a spring-- force tool (such as Browning’s Part Number “Belt Tension Checker” or equivalent tool); tension should be 6-- lbs at a 5/8-- in. deflection when measured at the centerline of the belt span. This point is at the center of the belt when measuring the distance between the motor shaft and the blower shaft. To change fan speed: 1. Shut off unit power supply. 2. Loosen belt by loosening fan motor mounting nuts. (See Fig. 5.) 3.
When replacing the motor, also replace the external-- tooth lock washer (star washer) under the motor mounting base; this is part of the motor grounding system. Ensure the teeth on the lock washer are in contact with the motor’s painted base. Tighten motor mounting bolts to 120 +/-- 12 in-- lbs. Changing fan wheel speed by changing pulleys: The horsepower rating of the belt is primarily dictated by the pitch diameter of the smaller pulley in the drive system (typically the motor pulley in these units).
Two-- Row Coils Clean coil as follows: 1. Turn off unit power, tag disconnect. 2. Remove top panel screws on condenser end of unit. 3. Remove condenser coil corner post. See Fig. 8. To hold top panel open, place coil corner post between top panel and center post. See Fig. 9. 6. Use a water hose or other suitable equipment to flush down between the 2 coil sections to remove dirt and debris. Clean the outer surfaces with a stiff brush in the normal manner. 7.
Evaporator Coil Cleaning the Evaporator Coil 1. Turn unit power off. Install lockout tag. Remove evaporator coil access panel. 2. If economizer or two-- position damper is installed, remove economizer by disconnecting Molex plug and removing mounting screws. 3. Slide filters out of unit. 4. Clean coil using a commercial coil cleaner or dishwasher detergent in a pressurized spray canister. Wash both sides of coil and flush with clean water.
To Use Cooling Charging Charts EXAMPLE: Model 50TC*A06 Outdoor Temperature . . . . . . . . . . . . . . . . . . 85_F (29_C) Suction Pressure . . . . . . . . . . . . . . . . . 130 psig (896 kPa) Take the outdoor ambient temperature and read the suction pressure gauge. Refer to chart to determine what suction temperature should be. If suction temperature is high, add refrigerant. If suction temperature is low, carefully recover some of the charge. Recheck the suction pressure as charge is adjusted.
50TC COOLING CHARGING CHARTS C08203 Fig.
50TC COOLING CHARGING CHARTS (cont) C08228 Fig. 12 - Cooling Charging Charts (cont.
Compressor The suction and discharge pressure levels should now move to their normal start-- up levels. The compressor is charged with the correct amount of oil at the factory. ! CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in damage to components. The compressor is in a PuronR refrigerant system and uses a polyolester (POE) oil. This oil is extremely hygroscopic, meaning it absorbs water readily.
Table 1 – Cooling Service Analysis PROBLEM Compressor and Condenser Fan Will Not Start. Compressor Will Not Start But Condenser Fan Runs. CAUSE Power failure. Fuse blown or circuit breaker tripped. Defective thermostat, contactor, transformer, or control relay. Insufficient line voltage. Incorrect or faulty wiring. Thermostat setting too high. Faulty wiring or loose connections in compressor circuit. Compressor motor burned out, seized, or internal overload open.
CONVENIENCE OUTLETS ! or HACR switch is open. Other connection methods will result in the convenience outlet circuit being de-- energized when the unit disconnect or HACR switch is open. See Fig. 15. WARNING ELECTRICAL OPERATION HAZARD Failure to follow this warning could result in personal injury or death. Units with convenience outlet circuits may use multiple disconnects. Check convenience outlet for power status before opening unit for service.
operation are factory-- provided and mounted. The unit is factory-- configured for immediate smoke detector shutdown operation; additional wiring or modifications to unit terminal board may be necessary to complete the unit and smoke detector configuration to meet project requirements. System inspections without having to disassemble the sensor. The cover attaches to the sensor housing using four captive screws and forms an airtight chamber around the sensing electronics.
For installations using two sensors, the duct smoke detector does not differentiate which sensor signals an alarm or trouble condition. Smoke Detector Locations 50TC Supply Air — The Supply Air smoke detector sensor is located to the left of the unit’s indoor (supply) fan. See Fig. 18. Access is through the fan access panel. There is no sampling tube used at this location. The sampling tube inlet extends through the side plate of the fan housing (into a high pressure area).
6. For units with an economizer, the sampling tube is integrated into the economizer housing but the connection of the flexible tubing to the sampling tube is the same. Highlight B: Smoke detector NC contact set will open on smoke alarm condition, de-- energizing the ORN conductor. Highlight C: 24-- v power signal via ORN lead is removed at Smoke Detector input on LCTB; all unit operations cease immediately.
Sensor and Controller Tests The sensor alarm test checks a sensor’s ability to signal an alarm state. This test requires that you use a field provided SD-- MAG test magnet. OPERATIONAL TEST HAZARD Failure to follow this caution may result in personnel and authority concern. Pressing the controller’s test/reset switch for longer than seven seconds will put the duct detector into the alarm state and activate all automatic alarm responses.
50TC Changing the Dirt Sensor Test 12 By default, sensor dirty test results are indicated by: S The sensor’s Dirty LED flashing. S The controller’s Trouble LED flashing. S The controller’s supervision relay contacts toggle. The operation of a sensor’s dirty test can be changed so that the controller’s supervision relay is not used to indicate test results. When two detectors are connected to a controller, sensor dirty test operation on both sensors must be configured to operate in the same manner.
Table 3 – Detector Indicators Alarm LED Trouble LED Dirty LED Power LED ! DESCRIPTION Resets the sensor when it is in the alarm or trouble state. Activates or tests the sensor when it is in the normal state. Indicates the sensor is in the alarm state. Indicates the sensor is in the trouble state. Indicates the amount of environmental compensation used by the sensor (flashing continuously = 100%) Indicates the sensor is energized.
S If a wiring fault between a sensor and the controller, the controller’s Trouble LED turns on but not the sensor’s. Trouble Alarm 2. Check the wiring between the sensor and the controller. If wiring is loose or missing, repair or replace as required. Controller’s Power LED is Off 1. Make sure the circuit supplying power to the controller is operational. If not, make sure JP2 and JP3 are set correctly on the controller before applying power. 2.
The High Static option supply fan motor is equipped with a pilot-- circuit Thermix combination overtemperature/overcurrent protection device. This device resets automatically. Do not bypass this switch to correct trouble. Determine the cause and correct it. DISCONNECT MOUNTING LOCATION EMT OR RIGID CONDUIT SINGLE (FIELD-SUPPLIED) POINT BOX CENTER MANUAL RESET POST LIMIT SWITCH HEATER COVERS Condenser Fan Motor Protection The condenser fan motor is internally protected against overtemperature.
Single Point Boxes and Supplementary Fuses — When the unit MOCP device value exceeds 60-- A, unit-- mounted supplementary fuses are required for each heater circuit. These fuses are included in accessory Single Point Boxes, with power distribution and fuse blocks. The single point box will be installed directly under the unit control box, just to the left of the partition separating the indoor section (with electric heaters) from the outdoor section. The Single Point Box has a hinged access cover.
50TC C08199 Fig. 33 - PremierLink Controller PREMIERLINKT CONTROL The PremierLink controller (see Fig. 33) is compatible with Carrier Comfort Networkr (CCN) devices. This control is designed to allow users the access and ability to change factory-- defined settings, thus expanding the function of the standard unit control board. CCN service access tools include System Pilot (TM), Touch Pilot (TM) and Service Tool.
24 Fig.
TEMP (C) --- 40 --- 35 --- 30 --- 25 --- 20 --- 15 --- 10 --- 5 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 TEMP (F) --- 40 --- 31 --- 22 --- 13 --- 4 5 14 23 32 41 50 59 68 77 86 95 104 113 122 131 140 149 158 RESISTANCE (Ohms) 335,651 242,195 176,683 130,243 96,974 72,895 55,298 42,315 32,651 25,395 19,903 15,714 12,494 10,000 8,056 6,530 5,325 4,367 3,601 2,985 2,487 2,082 1,752 Field connections — Field connections for accessory sensor and input devices are made at the 16-- pole terminal block (TB1) l
Table 6 – PremierLink Sensor Usage APPLICATION 50TC Differential Dry Bulb Temperature with PremierLink (PremierLink requires 4--- 20 mA Actuator) Single Enthalpy with PremierLink (PremierLink requires 4--- 20mA Actuator) Differential Enthalpy with PremierLink (PremierLink requires 4--- 20mA Actuator) OUTDOOR AIR TEMPERATURE SENSOR RETURN AIR TEMPERATURE SENSOR OUTDOOR AIR ENTHALPY SENSOR RETURN AIR ENTHALPY SENSOR Included --CRTEMPSN001A00 Required --33ZCT55SPT or equivalent --- --- Included --No
Table 7 – Space Sensor Mode INPUT SIGNAL Analog (10k thermistor) Discrete, 24VAC Analog (10k thermistor) Discrete, 24VAC Analog (10k thermistor) Discrete, 24VAC Analog, 24VDC Discrete, 24VAC Analog, 4--- 20mA Discrete, 24VAC Analog, 4--- 20mA Digital, , 5VDC Analog, 4--- 20mA Digital, 5VDC (Output)Discrete 24VAC Digital, 5VDC 50TC TB1 TERMINAL FIELD CONNECTION 1 T55--- SEN/T56--- SEN 2 RMTOCC 3 T55--- SEN/T56--- SEN 4 CMPSAFE 5 T56--- SET 6 FSD 7 LOOP--- PWR 8 SPS 9 IAQ --- SEN 10 FILTER 11 IAQ --- COM/OA
Connect T-- 56 - See Fig. 38 for T-- 56 internal connections. Install a jumper between SEN and SET terminals as illustrated. Connect T-- 56 terminals to TB1 terminals 1, 3 and 5 (see Fig. 39). PremierLink Configuration screen for Operating Mode. Default setting is Sensor Mode (value 1). Change the value to 0 to reconfigure the controller for Thermostat Mode.
The enthalpy control receives the outdoor air enthalpy from the outdoor air enthalpy sensor and provides a dry contact switch input to the PremierLink controller. A closed contact indicates that outside air is preferred to the return air. An open contact indicates that the economizer should remain at minimum position. levels. This information is used to monitor IAQ levels.
IAQ Sensor SEN TB1 9 PL J5-5 COM TB1 7 J5-6 24 VAC C08274 Fig. 44 - Indoor CO2 Sensor (33ZCSENCO2) Connections 50TC Refer to Form 33CS-- 58SI, PremierLink Installation, Start-- up, and Configuration Instructions, for detailed configuration information Outdoor Air Quality Sensor (PNO 33ZCSENCO2 plus weatherproof enclosure) — The outdoor air CO2 sensor is designed to monitor carbon dioxide (CO2) levels in the outside ventilation air and interface with the ventilation damper in an HVAC system.
sequence will prevent (or interrupt) operation of unit cooling, heating and economizer functions until the pressure switch contacts are closed indicating proper supply fan operation. Install the differential pressure switch in the supply fan section according to switch manufacturer’s instructions. Arrange the switch contact to be open on no flow and to close as pressure rises indicating fan operation. Connect one side of the switch’s NO contact set to LCTB’s THERMOSTAT-- R terminal.
(typically WHT) to the unit’s TB1-- 14 terminal. Connect the CCN (-- ) lead (typically BLK) to the unit’s TB1-- 16 terminal. See Fig. 51. ECONOMI$ER IV CONTROLLER WIRING HARNESS CCN Bus ACTUATOR + (RED) TB1 12 PL J2-1 GND (WHT) TB1 14 J2-2 – (BLK) TB1 16 J2-3 50TC Fig. 51 - PremierLink CCN Bus Connections OUTSIDE AIR TEMPERATURE SENSOR LOW AMBIENT SENSOR C08276 C06021 Fig.
BLACK 4 TRANSFORMER GROUND 3 5 BLUE 500 OHM RESISTOR 2 8 VIOLET 6 NOTE 1 PINK 7 RUN OAT SENSOR RED NOTE 3 1 24 VAC 10 YELLOW 11 9 DIRECT DRIVE ACTUATOR 4-20mA SIGNAL WHITE 12 4-20 mA TO J9 ON PremierLink BOARD ECONOMISER2 PLUG NOTES: 1. Switch on actuator must be in run position for economizer to operate. 2. PremierLink™ control requires that the standard 50HJ540569 outside-air sensor be replaced by either the CROASENR001A00 dry bulb sen sor or HH57A077 enthalpy sensor. 3.
50TC Fig. 56 - EconoMi$er IV Functional View EconoMi$er IV Table 11 provides a summary of Economizer IV. Troubleshooting instructions are enclosed. A functional view of the EconoMi$er is shown in 56. Typical settings, sensor ranges, and jumper positions are also shown. An EconoMi$er IV simulator program is available from Carrier to help with EconoMi$er IV training and troubleshooting.
and D. See Fig. 59 for the corresponding temperature changeover values. Differential Dry Bulb Control For differential dry bulb control the standard outdoor dry bulb sensor is used in conjunction with an additional accessory dry bulb sensor (part number CRTEMPSN002A00). The accessory sensor must be mounted in the return airstream. (See Fig. 61.) Wiring is provided in the EconoMi$er IV wiring harness. (See Fig. 52.) ECONOMI$ERIV CONTROLLER GROMMET C06034 Fig.
46 85 90 95 100 105 110 (29) (32) (35) (38) (41) (43) 44 CONTROL CONTROL POINT CURVE APPROX. deg. F (deg.
To determine the minimum position setting, perform the following procedure: 1. Calculate the appropriate mixed air temperature using the following formula: RANGE CONFIGURATION (ppm) 5000 4000 800 ppm 900 ppm 1000 ppm 1100 ppm 3000 2000 1000 0 2 3 4 5 6 7 8 DAMPER VOLTAGE FOR MAX VENTILATION RATE C06039 Fig.
50TC timeclock function in place of the jumper between TR and N. (See Fig. 52.) When the timeclock contacts are closed, the EconoMi$er IV control will be in occupied mode. When the timeclock contacts are open (removing the 24-- v signal from terminal N), the EconoMi$er IV will be in unoccupied mode. Demand Control Ventilation (DCV) When using the EconoMi$er IV for demand controlled ventilation, there are some equipment selection criteria which should be considered.
This procedure is used to prepare the EconoMi$er IV for troubleshooting. No troubleshooting or testing is done by performing the following procedure. NOTE: This procedure requires a 9-- v battery, 1.2 kilo-- ohm resistor, and a 5.6 kilo-- ohm resistor which are not supplied with the EconoMi$er IV. IMPORTANT: Be sure to record the positions of all potentiometers before starting troubleshooting. 1. Disconnect power at TR and TR1. All LEDs should be off. Exhaust fan contacts should be open. 2.
PRE--START--UP 2. Set the Enthalpy potentiometer to A. The Free Cool LED turns on. The actuator should drive to between 20 and 80% open. 3. Remove the 5.6 kilo-- ohm resistor and jumper T to T1. The actuator should drive fully open. 4. Remove the jumper across T and T1. The actuator should drive fully closed. 5. Return EconoMi$er IV settings and wiring to normal after completing troubleshooting.
4. Verify the following conditions: a. Make sure that condenser-- fan blade are correctly positioned in fan orifice. See Condenser-- Fan Adjustment section on page 11 for more details. b. Make sure that air filter(s) is in place. c. Make sure that condensate drain trap is filled with water to ensure proper drainage. d. Make sure that all tools and miscellaneous loose parts have been removed.
Use the Carrier network communication software to start up and configure the PremierLink controller. Refer to Installation Instruction 33CS-- 58SI for full discussion on configuring the PremierLink control system. Changes can be made using the ComfortWORKSr software, ComfortVIEWt software, Network Service Tool, System Pilott device, or Touch Pilott device.
outdoor-- air dampers closed to maintain the proper supply-- air temperature. compressors 1 and 2 will be cycled based on Y1 and Y2 inputs respectively. HEATING, UNITS WITH ECONOMI$ER IV — When the room temperature calls for heat, the heating controls are energized as described in the Heating, Units Without Economizer section. Any time the compressors are running, the PremierLink controller will lock out the compressors if the SAT becomes too low.
50TC Heating may also be energized when an IAQ sensor installed and has overridden the minimum economizer damper position. If the OAT < 55_F and an IAQ sensor is installed and the IAQ minimum position > minimum damper position causing the SAT to decrease below the SPT - 10_F, then the heat stages will be cycled to temper the SAT to maintain a temperature between the SPT and the SPT + 10_F.
The fan will also continue to run as long as compressors are on when transitioning from occupied to unoccupied with the exception of Fire Shutdown mode. If the Fire Shutdown input point is closed or forced in the STATUS01 points display table, the fan will be shutdown immediately regardless of the occupancy state or demand. The PremierLink controller has an optional Supply Fan Status input to provide proof of airflow.
return to normal when the indoor relative humidity drops 3% below the active humidity setpoint. 50TC Economizer — The economizer dampers are used to provide free cooling and indoor air quality if optional CO2 sensor is installed and when the outside conditions are suitable. Temperature control is accomplished by controlling the SAT to a certain level determined by the Economizer PID Loop by calculating a submaster reference (ECONSR) value.
The maximum number of stages available is dependent on the type of heat and the number of stages programmed in the CONFIG and SERVICE configuration tables. Staging will occur as follows for gas electric units, Carrier heat pumps with a defrost board, or cooling units with electric heat: For Heating PID STAGES = 2 HEAT STAGES = 1 (50% capacity) - energize HS1. HEAT STAGES = 2 (100% capacity) - energize HS2.
equal to OCSP and Enthalpy = Low then PURGEMP = 100%. S If the OAT < NTLO then PURGEMP = LTMP (Low Temperature Minimum Position - defaults to 10%) S If the OAT > 65_F or (OAT ≥ NTLO and OAT > OCSP) or Enthalpy = High then PURGEMP = HTMP (High Temperature Minimum Position defaults to 35%). 50TC The LTMP and HTMP are user adjustable values from 0 to 100% in the SETPOINT table.
S Supervisory Element S Supervisory Bus S Supervisory Block S Average Occupied Heat Setpoint S Average Occupied Cool Setpoint S Average Unoccupied Heat Setpoint S Average Unoccupied Cool Setpoint S Average Zone Temp S Average Occupied Zone Temp S Occupancy Status In return, the PremierLink controller will provide its SAT and operating mode to the linked device. It will convert its operating modes to Linkage modes. See Table 14.
Table 16 – Torque Values 120 +/--- 12 in--- lbs 120 +/--- 12 in--- lbs 72+/--- 5 in--- lbs 72+/--- 5 in--- lbs 72+/--- 5 in--- lbs 65--- 70 in--- lbs 65--- 75 in--- lbs 20 +/--- 2 in--- lbs 84 +/--- 12 in--- lbs 50TC Supply fan motor mounting Supply fan motor adjustment plate Motor pulley setscrew Fan pulley setscrew Blower wheel hub setscrew Bearing locking collar setscrew Compressor mounting bolts Condenser fan motor mounting bolts Condenser fan hub setscrew Fig.
Fig.
APPENDIX I. MODEL NUMBER SIGNIFICANCE Model Number Nomenclature Unit Heat Type 50 = Elec heat pkg rooftop 1 2 3 5 0 T C -- A 0 ____ 4 5 6 ____ 7 8 9 10 11 12 13 14 15 16 17 18 6 A 0 A 5 A 0 A 0 A 0 ____ Brand / Packaging 0 = Standard 1 = LTL Tier / Model TC = Entry tier (with Puron) Electrical Options A = None C = Non--- fused disc D = Thru the base F = Non--- fused & thru the base 50TC Heat Size --- = No heat Refrig. System Options A = Standard refrigeration system D = 2 comp.
APPENDIX II. PHYSICAL DATA 50TC**05 50TC**06 50TC**07 1 / 1 / Scroll 5.6 25 Acutrol 630 / 505 54 / 117 1 / 1 / Scroll 8.5 42 Acutrol 630 / 505 54 / 117 1 / 1 / Scroll 10.7 42 Acutrol 630 / 505 54 / 117 1 / 1 / Scroll 14.1 56 Acutrol 630 / 505 54 / 117 Cu / Al 3/8” RTPF 2 / 15 5.5 3/4” Cu / Al 3/8” RTPF 2 / 15 5.5 3/4” Cu / Al 3/8” RTPF 4 / 15 5.5 3/4” Cu / Al 3/8” RTPF 4 / 15 7.
APPENDIX III. FAN PERFORMANCE General Fan Performance Notes: 50TC 1. Interpolation is permissible. Do not extrapolate. 2. External static pressure is the static pressure difference between the return duct and the supply duct plus the static pressure caused by any FIOPs or accessories. 3. Tabular data accounts for pressure loss due to clean filters, unit casing, and wet coils. Factory options and accessories may add static pressure losses.
APPENDIX III. FAN PERFORMANCE (cont.) CFM 900 975 1050 1125 1200 1275 1350 1425 1500 CFM 900 975 1050 1125 1200 1275 1350 1425 1500 1 Phase 3 Ton Horizontal Supply 0.2 RPM BHP Field Supplied Drive1 554 0.14 575 0.16 597 0.18 620 0.21 643 0.23 666 0.27 690 0.30 714 0.34 738 0.38 1.2 RPM BHP 1017 1035 1053 1071 1089 1107 1126 1145 1164 0.64 0.68 0.73 0.78 0.84 0.90 0.96 1.03 1.10 RPM 681 701 721 741 762 784 805 827 849 AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG) 0.4 0.6 0.8 1.
APPENDIX III. FAN PERFORMANCE (cont.) 50TC**04 CFM 50TC 900 975 1050 1125 1200 1275 1350 1425 1500 CFM 900 975 1050 1125 1200 1275 1350 1425 1500 3 Phase 3 Ton Horizontal Supply 0.2 RPM BHP Field Supplied Drive1 554 0.14 575 0.16 597 0.18 620 0.21 643 0.23 666 0.27 690 0.30 714 0.34 738 0.38 1.2 RPM BHP 1017 1035 1053 1071 1089 1107 1126 1145 1164 0.64 0.68 0.73 0.78 0.84 0.90 0.96 1.03 1.10 RPM 681 701 721 741 762 784 805 827 849 AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG) 0.4 0.6 0.8 1.
APPENDIX III. FAN PERFORMANCE (cont.) CFM 1200 1300 1400 1500 1600 1700 1800 1900 2000 CFM 1200 1300 1400 1500 1600 1700 1800 1900 2000 1 Phase 4 Ton Horizontal Supply AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG) 0.4 0.6 0.8 BHP RPM BHP RPM BHP RPM BHP Standard Static Option Medium Static Option 0.23 762 0.35 860 0.46 944 0.58 0.28 791 0.40 887 0.52 970 0.65 0.33 820 0.45 914 0.59 997 0.72 0.38 849 0.52 942 0.66 1024 0.80 0.44 879 0.59 971 0.74 1051 0.89 0.51 910 0.66 1000 0.82 1079 0.98 0.59 941 0.
APPENDIX III. FAN PERFORMANCE (cont.) 50TC**05 CFM 50TC 1200 1300 1400 1500 1600 1700 1800 1900 2000 CFM 1200 1300 1400 1500 1600 1700 1800 1900 2000 3 Phase 4 Ton Horizontal Supply AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG) 0.4 0.6 0.8 BHP RPM BHP RPM BHP RPM BHP Standard Static Option Medium Static Option 0.23 762 0.35 860 0.46 944 0.58 0.28 791 0.40 887 0.52 970 0.65 0.33 820 0.45 914 0.59 997 0.72 0.38 849 0.52 942 0.66 1024 0.80 0.44 879 0.59 971 0.74 1051 0.89 0.51 910 0.66 1000 0.82 1079 0.
APPENDIX III. FAN PERFORMANCE (cont.) CFM 1500 1625 1750 1875 2000 2125 2250 2375 2500 CFM 1500 1625 1750 1875 2000 2125 2250 2375 2500 1 Phase 5 Ton Horizontal Supply 0.2 RPM BHP Field Supplied Drive1 724 0.33 765 0.40 806 0.48 849 0.57 892 0.67 935 0.79 980 0.92 1024 1.06 1069 1.22 1.2 RPM BHP 1188 1213 1239 1267 ----------- 1.09 1.18 1.28 1.40 ----------- RPM 837 873 909 947 986 1025 1066 1107 1149 AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG) 0.4 0.6 0.
APPENDIX III. FAN PERFORMANCE (cont.) 50TC**06 CFM 50TC 1500 1625 1750 1875 2000 2125 2250 2375 2500 CFM 1500 1625 1750 1875 2000 2125 2250 2375 2500 3 Phase 5 Ton Horizontal Supply 0.2 RPM BHP Field Supplied Drive1 724 0.33 765 0.40 806 0.48 849 0.57 892 0.67 935 0.79 980 0.92 1024 1.06 1069 1.22 RPM 837 873 909 947 986 1025 1066 1107 1149 1.2 RPM BHP RPM 1188 1213 1239 1267 1296 1326 1358 1390 1424 1.09 1.18 1.28 1.40 1.53 1.67 1.83 2.00 2.
APPENDIX III. FAN PERFORMANCE (cont.) CFM 1800 1950 2100 2250 2400 2550 2700 2850 3000 CFM 1800 1950 2100 2250 2400 2550 2700 2850 3000 3 Phase 6 Ton Horizontal Supply 0.2 RPM BHP Field Supplied Drive1 822 0.51 872 0.62 923 0.75 974 0.90 1026 1.06 1079 1.25 1132 1.46 1186 1.69 1240 1.94 RPM 927 973 1019 1067 1115 1164 1214 1264 1315 1.2 RPM BHP RPM 1244 1281 1320 1359 1400 1441 1483 1527 1571 1.33 1.49 1.67 1.87 2.09 2.33 2.59 2.87 3.
APPENDIX III. FAN PERFORMANCE (cont.) Pulley Adjustment 1 phase 3 phase 05 3 phase 3 phase 06 07 50TC 1 phase 3 phase 04 1 phase UNIT MOTOR/DRIVE COMBO 0.0 0.5 1.0 MOTOR PULLEY TURNS OPEN 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.
APPENDIX IV. ELECTRICAL DATA V ---Ph---Hz 3 TONS VOLTAGE RANGE MIN MAX COMP (ea) RLA LRA OFM (ea) WATTS FLA 208--- 1--- 60 187 253 16.6 79 325 1.5 230--- 1--- 60 187 253 16.6 79 325 1.5 208--- 3--- 60 187 253 10.4 73 325 1.5 230--- 3--- 60 187 253 10.4 73 325 1.5 460--- 3--- 60 414 506 5.8 38 325 0.8 575--- 3--- 60 518 633 3.8 37 325 0.
APPENDIX IV. ELECTRICAL DATA (cont.) 50TC**06 V ---Ph---Hz 5 TONS VOLTAGE RANGE 50TC MIN MAX COMP (ea) RLA LRA OFM (ea) WATTS FLA 208--- 1--- 60 187 253 26.2 134 325 1.5 230--- 1--- 60 187 253 26.2 134 325 1.5 208--- 3--- 60 187 253 15.6 110 325 1.5 230--- 3--- 60 187 253 15.6 110 325 1.5 460--- 3--- 60 414 506 7.7 52 325 0.8 575--- 3--- 60 518 633 5.8 39 325 0.
APPENDIX IV. ELECTRICAL DATA (cont.) ELECTRIC HEATER IFM TYPE 208/230--- 1--- 60 STD MED 208/230--- 3--- 60 MED HIGH 460--- 3--- 60 STD MED HIGH 575--- 3--- 60 50TC**04 STD NO C.O. or UNPWR C.O. NO P.E. Nom (kW) FLA None 3.3/4.4 4.9/6.5 6.5/8.7 7.9/10.5 9.8/13.0 None 3.3/4.4 4.9/6.5 6.5/8.7 7.9/10.5 9.8/13.0 None 3.3/4.4 4.9/6.5 6.5/8.7 7.9/10.5 12.0/16.0 None 3.3/4.4 4.9/6.5 6.5/8.7 7.9/10.5 12.0/16.0 None 3.3/4.4 4.9/6.5 6.5/8.7 7.9/10.5 12.0/16.0 None 6.0 8.8 11.5 14.0 None 6.0 8.8 11.
APPENDIX IV. ELECTRICAL DATA (cont) NOM. V--- PH--- HZ UNIT MCA/MOCP DETERMINATION NO C.O. OR UNPWRD C.O. (cont) ELECTRIC HEATER IFM TYPE 50TC 208/230--- 1--- 60 STD MED 208/230--- 3--- 60 MED HIGH 460--- 3--- 60 STD MED HIGH 575--- 3--- 60 50TC**05 STD NO C.O. or UNPWR C.O. NO P.E. Nom (kW) FLA None 3.3/4.4 6.5/8.7 9.8/13.0 13.1/17.4 15.8/21.0 None 3.3/4.4 6.5/8.7 9.8/13.0 13.1/17.4 15.8/21.0 None 4.9/6.5 6.5/8.7 12.0/16.0 15.8/21.0 None 4.9/6.5 6.5/8.7 12.0/16.0 15.8/21.0 None 4.9/6.
APPENDIX IV. ELECTRICAL DATA (cont) ELECTRIC HEATER IFM TYPE FLA None 4.9/6.5 6.5/8.7 9.8/13.0 13.1/17.4 15.8/21.0 None 4.9/6.5 6.5/8.7 9.8/13.0 13.1/17.4 15.8/21.0 None 4.9/6.5 7.9/10.5 12.0/16.0 15.8/21.0 19.9/26.5 None 4.9/6.5 7.9/10.5 12.0/16.0 15.8/21.0 19.9/26.5 None 4.9/6.5 7.9/10.5 12.0/16.0 15.8/21.0 19.9/26.5 None 6.0 11.5 14.0 23.0 25.5 None 6.0 11.5 14.0 23.0 25.5 None 6.0 11.5 14.0 23.0 25.5 STD 208/230--- 1--- 60 208/230--- 3--- 60 DISC. SIZE MOCP FLA LRA None 23.5/27.1 31.4/36.3 46.
APPENDIX IV. ELECTRICAL DATA (cont) NOM. V--- PH--- HZ UNIT MCA/MOCP DETERMINATION NO C.O. OR UNPWRD C.O. (cont) ELECTRIC HEATER IFM TYPE 50TC 208/230--- 3--- 60 STD MED 50TC**07 HIGH 460--- 3--- 60 STD MED 575--- 3--- 60 HIGH NO C.O. or UNPWR C.O. NO P.E. Nom (kW) FLA None 4.9/6.5 7.9/10.5 12.0/16.0 15.8/21.0 19.9/26.5 None 4.9/6.5 7.9/10.5 12.0/16.0 15.8/21.0 19.9/26.5 None 4.9/6.5 7.9/10.5 12.0/16.0 15.8/21.0 19.9/26.5 None 6.0 11.5 14.0 23.0 25.5 None 6.0 11.5 14.0 23.0 25.5 None 6.
APPENDIX V. WIRING DIAGRAM LIST Size A04 A05 A06 A07 All 50TC Voltage 208/230---1---60 208/230---3---60 460---3---60 575---3---60 208/230---1---60 208/230---3---60 460---3---60 575---3---60 208/230---1---60 208/230---3---60 460---3---60 575---3---60 208/230---3---60 460---3---60 575---3---60 PremierLink* DRAWING NUMBER.REV CONTROL POWER 48TM500212.04 48TM500211.08 48TM500212.04 48TM500214.07 48TM500212.04 48TM500214.07 48TM500212.04 48TM500214.07 48TM500212.04 48TM500211.08 48TM500212.04 48TM500214.
50TC APPENDIX VI. MOTORMASTER SENSOR LOCATIONS Fig. 67 - 50TC*A04 Outdoor Circuiting Fig. 68 - 50TC*A05/06 Outdoor Circuiting C08259 Fig. 69 - 50TC*A07 Outdoor Circuiting C08260 Fig.
50TC APPENDIX VI. (cont) MOTORMASTER SENSOR LOCATIONS Fig.
50TC Edition Date: 05/08 Catalog No: 50TC ---1SM Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. Replaces: NEW Copyright 2008 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231 Printed in U.S.A.
START-UP CHECKLIST START-UP CHECKLIST (Remove and Store in Job File) I. PRELIMINARY INFORMATION MODEL NO.: SERIAL NO.: DATE: TECHNICIAN: II.