Specifications
UNIT
50DJ,DK
WEIGHT* A B C D E F
Lb Kg mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in.
024 2440 1107 1244.6 4-1 1680.0 5-6
1
⁄
8
3141.0 10-3
11
⁄
16
525.5 1-8
11
⁄
16
807.0 2-7
3
⁄
4
2048.0 6- 8
5
⁄
8
028 2900 1315
1346.2 4-5 1956.0 6-5 3397.0 11-1
3
⁄
4
382.5 1-3
1
⁄
16
935.0 3-0
13
⁄
16
2131.0 6-11
7
⁄
8
030 2930 1329
*Weights include economizer but not rainhood.
LEGEND
CONN — Connection
DIM — Dimension
NOTES:
1. Dimensions in [ ] are in millimeters.
2. Center of gravity.
3. Allow 128-09 (3658) at top and 68-09 (1829) on sides
for service and operational clearance.
4. On multiunit applications allow 128-09 (3658) be-
tween adjacent condensers and economizers.
5. For smaller service and operational clearances, con-
tact your local representative.
6. Bottom ducts designed to be attached to acces-
sory roof curb. If unit is mounted on dunnage, it is
recommended the ducts be supported by cross
braces as done on the accessory roof curb.
7. Always line up condenser end of unit tight against
the roof curb.
8. Units with power exhaust and/or electric heat re-
quire a 90° elbow in return-air duct.
Fig. 3A — Base Unit Dimensions, 50DJ,DK
9