Table 7 — Electrical Data — 50DK,DY030
NOMINAL
V-PH-HZ
VOLTAGE
RANGE
COMPR
NO. 1
COMPR
NO. 2
OFM IFM
POWER EXHAUST
FAN MOTOR*
ELECTRIC
HEAT
POWER SUPPLY
Min Max RLA LRA RLA LRA
Total
FLA
Hp FLA FLA kW FLA MCA
MOCP
Fuse Only
208/230-3-60 187 254 63.6 266 44.3 228 10.8
10.0† 26.4
— — — 161.0/161.0 200/200
6.6/6.0 — — 167.6/167.0 225/225
— 16/18 40.9/45.2 161.0/161.0 200/200
6.6/6.0 16/18 40.9/45.2 167.6/167.0 225/225
— 33/36 81.8/90.4 161.0/161.0 200/200
6.6/6.0 33/36 81.8/90.4 167.6/167.0 225/225
15.0† 42.0
— — — 176.6/176.6 225/225
6.6/6.0 — — 183.2/182.6 225/225
— 16/18 40.9/45.2 176.6/176.6 225/225
6.6/6.0 16/18 40.9/45.2 183.2/182.6 225/225
— 33/36 81.8/90.4 176.6/176.6 225/250
6.6/6.0 33/36 81.8/90.4 183.2/182.6 225/250
10.0** 24.2
— — — 158.8/158.8 200/200
6.6/6.0 — — 165.4/164.8 225/225
— 16/18 40.9/45.2 158.8/158.8 200/200
6.6/6.0 16/18 40.9/45.2 165.4/164.8 225/225
— 33/36 81.8/90.4 158.8/158.8 200/200
6.6/6.0 33/36 81.8/90.4 165.4/164.8 225/225
15.0** 36.6
— — — 171.2/171.2 225/225
6.6/6.0 — — 177.8/177.2 225/225
— 16/18 40.9/45.2 171.2/171.2 225/225
6.6/6.0 16/18 40.9/45.2 177.8/177.2 225/225
— 33/36 81.8/90.4 171.2/171.2 225/225
6.6/6.0 33/36 81.8/90.4 177.8/177.2 225/225
460-3-60 414 508 30.0 120 22.1 114 5.4
10.0† 12.5
— — — 77.5 100
3.0 — — 80.5 110
— 18 22.6 77.5 100
3.0 18 22.6 80.5 110
— 36 45.2 77.5 100
3.0 36 45.2 80.5 110
15.0† 20.0
— — — 85.0 110
3.0 — — 88.0 110
— 18 22.6 85.0 110
3.0 18 22.6 88.0 110
— 36 45.2 85.0 125
3.0 36 45.2 88.0 125
10.0** 12.2
— — — 77.2 100
3.0 — — 80.2 110
— 18 22.6 77.2 100
3.0 18 22.6 80.2 110
— 36 45.2 77.2 100
3.0 36 45.2 80.2 110
15.0** 18.3
— — — 83.3 110
3.0 — — 86.3 110
— 18 22.6 83.3 110
3.0 18 22.6 86.3 110
— 36 45.2 83.3 110
3.0 36 45.2 86.3 110
575-3-60 518 632 22.9 96 17.9 91 4.8
10† 11.6
— — — 62.9 80
2.4 — — 65.3 80
— 36 36.1 62.9 80
2.4 36 36.1 65.3 80
15† 15.4
— — — 66.7 80
2.4 — — 69.1 90
— 36 36.1 66.7 90
2.4 36 36.1 69.1 90
FLA — Full Load Amps MCA — Minimum Circuit Amps (for wire sizing) *50DK units only.
Hp — Nominal Horsepower MOCP — Maximum Overcurrent Protection †Standard efficiency.
IFM — Evaporator (Indoor) Fan Motor OFM — Condenser (Outdoor) Fan Motor **High efficiency.
LRA — Locked Rotor Amps RLA — Rated Load Amps
(208/230, 460 V Only)
23