VISTA--15PMT VISTA VISTAVISTA-20PMT Programming Guide 1 OFF ARMED 4 MAX READY 7 INSTANT READY 2 AWAY 5 TEST 8 CODE 0 3 STAY 6 BYPASS 9 CHIME # ARMED READY ON OFF 1 OFF 2 AWAY 4 MAX 5 7 INSTANT READY TEST 8 CODE 0 3 STAY 6 BYPASS 9 CHIME # This control is a certified SIA-compliant control that meets SIA specifications for False Alarm Reduction. K5305-1MTPRV9 3/11 Rev.
TABLE OF CONTENTS PROGRAMMING MODE COMMANDS ................................................................................................. 3 DATA FIELD PROGRAMMING FORM.................................................................................................. 4 CONFIGURABLE ZONE TYPES WORKSHEETS............................................................................... 13 ∗56 ZONE PROGRAMMING MENU MODE ........................................................................................
PROGRAMMING MODE COMMANDS TO ENTER PROGRAMMING MODE (using an alpha keypad connected to the control): A. POWER UP, then press [✱] and [#] at the same time, within 50 seconds of powering up (this method must be used if ✱98 was used to exit program mode). OR B. Initially, key: Installer Code (4 + 1 + 1 + 2) plus 8 + 0 + 0. PROGRAMMING MODE COMMANDS Task Command/Explanation Go to a Data Field Entering Data Press [∗ ∗] + [Field Number], followed by the required entry.
DATA FIELD PROGRAMMING FORM Entries apply to both the VISTA-15PMT and VISTA-20PMT controls, except entries shown in dashed boxes apply only to the VISTA-20PMT (partition entries) and are not applicable to the VISTA-15PMT. Entry of a number other than one specified will give unpredictable results. Values shown in brackets are factory defaults. SIA Features: The VISTA-15PMT and VISTA-20PMT are certified SIA-compliant controls that meet SIA specifications for False Alarm Reduction.
∗35 Entry Delay #1 [30,30] | ∗42 Secondary Phone No. | 30 - 96 = 30 - 96 seconds Part. 1 Part. 2 97 = 120 secs 98 = 180 secs 99 = 240 secs Upon entering, the system must be disarmed before the time entered expires, otherwise it sounds an alarm. NOTE: Entries less than 30 will result in a 30-second delay. Common zones use same delay as partition 1. For UL Residential Burglary Alarm installations, must be set for a maximum of 30 seconds; entry delay plus dial delay should not exceed 1 min.
∗50 Burglary Dialer Delay ∗56, ∗57, ∗58 Menu Modes [2,0] Delay Time Delay Disable Delay Time: 1 = 15 seconds; 2 = 30 seconds; 3 = 45 seconds Provides delay of “BURGLARY ALARM” report to the central station, which allows time for the subscriber to avoid a false alarm transmission. This delay does not apply to zone type 24 alarms (silent burglary) or to 24-hour zone types 6, 7, and 8 (silent panic, audible alarm, auxiliary alarm), which are always sent as soon as they occur.
∗64 Test Report Code [10] ∗73 AC Restore Rpt Code | Use Scheduling mode to set periodic test reports, or use the following key commands: installer code +[#] + [0] + 0 = test report sent every 24 hours installer code +[#] + [0] + 1 = test report sent once per week installer code +[#] + [0] + 2 = test report sent every 28 day Each mode sets schedule 32 (VISTA-20PMT) or schedule 08 (VISTA-15PMT) to the stated repeat option; first test report sent 12 hours after command†.
∗86 Cancel Verify Keypad Display [1] 0 = no; 1 = yes This feature causes a “ALARM CANCELED” display on the LCD keypad under the following conditions: • After the kissoff of the cancel message to the Central Station, indicating a successful transmission. • When an alarm is successfully canceled before the Central Station received the Alarm message. E.g., if an alarm is incorrectly triggered and the user presses code + OFF before the dial delay time has expired, the message will never go out to the CS.
∗93 Reports In Armed Period PAGER OPTIONS (✱160- ✱172) [1,0] Per Zone (Swinger Suppression) Restrict Report Pairs The system can send various reports to several pagers (MTV20P = up to 4; MTV15P = up to 2). To program pager reporting, do the following: 1. Enter the pager phone number(s), preface characters, and pager report options in data fields *160 - *171. 2. Enable Pager Delay, if desired, in field *172 (delays alarm reporting for ALL pagers). 3.
∗163 Pager 2 Phone No. | | | | | | | | | MISCELLANEOUS SYSTEM FIELDS (*174-*181) | | | | | | | | | ∗174 Clean Me Reporting Options | Enter up to 20 digits. 0–9; #+11 = 'Q'; #+12 = '#'; #+13 = 2sec pause. If entering fewer than 20 digits, exit by pressing [∗] + next field number. To clear entries, press ∗163∗. ∗164 Pager 2 Characters | | | | | | | | | | | | | | | Enter the optional prefix characters, up to 16 digits. 0–9; #+11 = '✱'; #+12 = '#'; #+13 = 2-second pause.
Configurable Zone Type Options (continued) Bell Timeout (entry 9): Alarm sounding on zones set for this option remain for the duration set in fields *32 / *33. Fire Zone (entry 9): Zones set for this option respond in the same manner as if programmed for zone type 9. Do not set fire zones to respond as a “fault” in entries 1-6. Trouble Sounds (entry 10): Selects the type of trouble sounds for zones set for this zone type (periodic beeps = once every 30 seconds; trouble beeps = rapid beeping).
∗197 Exit Time Display Interval KEYPAD OPTIONS ∗190 Keypad 2 Device Address 17 [0] [0] VISTA-20PMT V20P Partition/ Sound Partition: V15P Enable Enter the desired option for the keypad’s home partition. For Touchscreen device usage 0 = disable 1 = partition 1 2 = part. 2 3 = part. 3 (common) For Remote Services device usage 5 = part. 1 (auto-stay arm disabled) 6 = part. 2 (auto-stay arm disabled) 7 = part. 3 (common; auto-stay arm disabled) Sound: Enter the desired sound option for this keypad.
CONFIGURABLE ZONE TYPES WORKSHEETS Configurable zone types 90 and 91 can be programmed via downloader software or from a keypad using data fields*182*185. Configurable zone types 92 and 93 (VISTA-20PMT only) can only be programmed using the downloader software. Programming Configurable Zone Type options involves making 10 entries in data field *182 for zone type 90 and field *184 for zone type 91, where each entry represents the sum of the values of the various options shown in the tables below.
∗56 ZONE PROGRAMMING MENU MODE (press *56 while in Program mode) The Zone Programming Worksheet is on page 28. Zones and Partitions Each protection zone needs to be programmed with various attributes using *56 Zone Programming mode or ✱58 Expert Programming Mode. Using this mode, enter the zone number to be programmed and make appropriate entries at the prompts. Finally, Confirm the serial number of wireless transmitter zones.
INPUT S/N Enroll the transmitter’s serial number and loop number as follows: 1. a. Transmit two open/close sequences (for button-type transmitters, press and release the button twice, waiting about 4 seconds before pressing the button the second time). OR b. Manually enter the 7-digit serial number printed on the label of the transmitter. Press the [∗] key to move to the “L” position, then enter the loop number. Use the [A] (Advance) and [B] (Back) keys to move the cursor forward and back within the screen.
WIRELESS KEY PROGRAMMING TEMPLATES (press the [D] key from *58 Menu mode Summary Screen) This procedure programs the wireless keys, but a key is not active for arming/disarming until it is assigned to a user number (see System Operation section, Assigning Attributes Command in the Installation Instructions). TEMPLATE ? ENTER START ZONE Enter desired template number 1–6 (see chart below), then press [∗] to continue. To exit the Template screen, press [#].
OUTPUT DEVICE PROGRAMMING GENERAL INFORMATION (*79/*80 Menu Mode) Output Devices: The VISTA-20PMT system supports up to 16 relays and/or Powerline Carrier devices (X-10 devices) plus 2 built-in trigger outputs in any combination. These 18 “outputs” are assigned to system-wide output numbers (01-18). Use *79 Menu Mode to assign output numbers and map them to device addresses. The VISTA-15PMT supports 8 relays and 2 built-in trigger outputs (total 10 outputs).
∗80 OUTPUT FUNCTION MENU MODE (press ∗80 while in Programming mode) The Output Definition Worksheet is on page 30. Use this mode to program output function definitions (up to 48 functions) that provide automated control of any of the output devices, based on events occurring on individual zones or zones with certain zone types. Each output definition is identified by an output function number, and includes the following components: Output Definition Components Component Output Function No.
“C” (if zone number was selected) ENTER ZN NO. Enter the desired zone number, then press [∗] to continue. At the ENTER EVENT prompt, enter the zone event that will activate this output (0 = restore; 1 = alarm/fault/trouble).
∗82 ALPHA DESCRIPTOR MENU MODE The system lets you assign zone descriptors for protection zones, keypad panics, and RF receiver supervision faults. Each description can be composed of a combination of up to 3 words selected from a vocabulary of words stored in memory (see Alpha Vocabulary List page). In addition, up to 10 installer-defined words can be added to those already in memory, plus 3 additional words can be assigned as partition descriptors.
ALPHA VOCABULARY LIST (For Entering Zone Descriptors) 000 • 001 • 002 004 005 • 006 • 007 • 009 010 • • • • • • • 012 013 014 016 017 018 019 020 • 021 • 022 023 025 • 026 028 • 029 030 031 033 034 035 036 • 037 038 • 040 • 046 047 • 048 049 • 050 051 • 052 • 053 054 055 Note: (Word Space) –A– AIR ALARM ∗ ALLEY AMBUSH AREA APARTMENT ATTIC ∗ AUDIO –B– BABY ∗ BACK ∗ BAR BASEMENT ∗ BATHROOM ∗ BED BEDROOM ∗ BELL BLOWER BOILER BOTTOM BREAK BUILDING –C– CABINET CALL CAMERA CAR CASH CCTV CEILING CELLAR CENTRAL
SETTING SCHEDULES (Installer Code + [#] + [6] [4]) The system provides schedules, which can be used to automatically control 11 types of system events at pre-defined times. Some events are reserved for the installer only. NOTES: • The master code can only access schedules 01-16 (VISTA-15PMT = 01-04) and events 00-07. • System clock must be set before schedules can take effect. • Programmed schedules do not take effect until the next scheduled “start” time. (e.g.
AVS SYSTEM ENABLE and QUICK PROGRAMMING COMMANDS Applies to an AVS system using an ECP connection to the control. 1. Install the AVS module according to its instructions. 2. Use one of the control’s AVS Quick Program commands as follows (see Quick Program Command Results below for results of each command): • installer code + [#] + 0 + 3: enable AVS operation without panel sounds on the AVST speaker • installer code + [#] + 0 + 4: enable AVS operation and enable panel sounds on the AVST speaker 3.
∗29 COMMUNICATION DEVICE MENU MODE (Pass-Through Programming) This mode is for programming an IP, GSM, or IP/GSM Communicator Module using an alpha keypad. Alternatively, these options can be programmed via the AlarmNet Direct website. After programming is complete, the module must be registered with AlarmNet before reporting via the communication device can occur. Refer to the device’s instructions for registration procedures. NOTE: The module must be set to device address 3.
ZONE TYPE DEFINITIONS Zone types define the way in which the system responds to faults in each zone. Type 00 Zone Not Used Program a zone with this zone type if the zone is not used. Type 01 Entry/Exit Burglary #1 • Assign to zones that are used for primary entry and exit. • Provides entry delay when zone is faulted if control is armed in the Away, Stay, or Night-Stay modes. • No entry delay provided when the panel is armed in the Instant/Maximum mode.
UL NOTICES 1. Entry Delay No. 1 and No. 2 (fields ∗35, ∗36) cannot be greater than 30 seconds for UL Residential Burglar Alarm installations, and entry delay plus dial delay should not exceed 1 minute. For UL Commercial Burglar Alarm installations, total entry delay may not exceed 45 seconds. 2. For UL Commercial Burglar Alarm and UL Residential Burglar Alarm installations with line security, total exit delay time must not exceed 60 seconds. 3.
WORKSHEET for SCHEDULES (installer code + [#] + [6] [4]; master code can only access schedules 01-16 for VISTA-20PMT, 01-04 for VISTA-15PMT, and events 00-07 for both controls; VISTA-15PMT supports up to 8 schedules, VISTA-20PMT supports up to 32 schedules ) No. 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 Event Device No. Group No.
WORKSHEET for ∗56 ZONE PROGRAMMING (VISTA-15PMT supports up to 32 zones: 1-6, 9-34, 49-56) [default shown in brackets] Zone 1 2 3 4 5 6 7 8 Zone NOTES: Zone Type: see chart in ∗56 Zone Programming Menu Mode section; Report Code: enabled if any digit entered as 1st digit; Hardwire Type (zns 2-8): 0 = EOL 3 = ZD 1 = NC 4 = DB 2 = NO Input Type: 2 = AW (zones 9-48) 3 = RF (zones 9-48) 4 = UR (zones 9-48) 5 = BR (zones 49-64) NOTE: Zones 9-16 not available if zone doubling enabled.
WORKSHEET for ∗57 FUNCTION KEY PROGRAMMING A Option Function P1 P2 B com P1 P2 C com P1 P2 Comments D com P1 P2 com 01 02 03 04 05 06 07 08 09 10 11 12 00 Paging Time Display Arm AWAY Arm STAY Arm NIGHT-STAY Step Arming Device Activation Device: Comm. Test Macro Key 1 Assign each macro key to only a single partition. † Macro Key 2 Assign each macro key to only a single partition. † Macro Key 3 Assign each macro key to only a single partition.
WORKSHEET for ∗80 OUTPUT FUNCTION PROGRAMMING Fill in the required data on the worksheet below and follow the programming procedure in the installation manual as you enter the data during the displays and prompts that appear in sequence. Notes: 1. For Relays, 4229 and 4204 devices are programmed in *79, *80, and *81 modes. 2. For Powerline Carrier devices (plcd), field ✱27 must be programmed with a House Code. 3. Tampers of expansion units cannot be used to operate devices.
TABLE OF DEVICE ADDRESSES This Device Uses Address RF Receiver 00 AUI (touchscreen) 1 01 AUI (touchscreen) 2 02 AUI (touchscreen) 3 05** AUI (touchscreen) 4 06** Communication Device (LRR) 03 4286 Voice Module 04 Zone Expanders (4219/4229): 07 module 1 (for zones 09 - 16) 08 module 2 (for zones 17 - 24) 09** module 3 (for zones 25 - 32) 10** module 4 (for zones 33 - 40) 11** module 5 (for zones 41 - 48) Relay Modules (4204): module 1 12 module 2 13 module 3 14** module 4 15** Keypads: keypad 1 16 keypad 2 1
USE UL LISTED LIMITED ENERGY CABLE FOR ALL CONNECTIONS 12801 North Stemmons Freeway, Suite 821 Dallas, Texas 75234 Copyright © 2006 Honeywell International Inc. CONNECTION OF THE FIRE ALARM SIGNAL TO A FIRE ALARM HEADQUARTERS OR A CENTRAL STATION SHALL BE PERMITTED ONLY WITH THE PERMISSION OF THE LOCAL AUTHORITY HAVING JURISDICTION. THE BURGLAR ALARM SIGNAL SHALL NOT BE CONNECTED TO A POLICE EMERGENCY NUMBER.