Refrigerator User Manual

37
Table 16 PremierLink Sensor Usage
APPLICATION
OUTDOOR AIR
TEMPERATURE
SENSOR
RETURN AIR
TEMPERATURE
SENSOR
OUTDOOR AIR
ENTHALPY SENSOR
RETURN AIR
ENTHALPY SENSOR
Differential Dry Bulb
Tem pera t u re wit h
PremierLink
(PremierLink requires
4---20 mA Actuator)
I n c l u d e d ---
CRTEMPSN001A00
R e q u i r e d ---
33ZCT55SPT
or equivalent
--- ---
Single Enthalpy with
PremierLink
(PremierLink requires
4 --- 2 0 m A A c t u a t o r )
I n c l u d e d ---
Not Used
---
R e q u i r e s ---
HH57AC077
or equivalent
---
Differential Enthalpy
with PremierLink
(PremierLink requires
4 --- 2 0 m A A c t u a t o r )
I n c l u d e d ---
Not Used
---
R e q u i r e s ---
HH57AC077
or equivalent
Requires ---
HH57AC078
or equivalent
NOTES:
CO
2
Sensors (Optional):
33ZCSENCO2 --- Room sensor (adjustable). Aspirator box is required for duct mounting of the sensor.
33ZCASPCO2 --- Aspirator box used for duct---mounted CO
2
room sensor.
33ZCT55CO2 --- Space temperature and CO
2
room sensor with override.
33ZCT56CO2 --- Space temperature and CO
2
room sensor with override and setpoint.
Table 17 Space Sensor Mode
TB1 TERMINAL FIELD CONNECTION INPUT SIGNAL
1 T55---SEN/T56---SEN Analog (10k thermistor)
2 RMTOCC Discrete, 24VAC
3 T55---SEN/T56---SEN Analog (10k thermistor)
4 CMPSAFE Discrete, 24VAC
5 T56---SET Analog (10k thermistor)
6 FSD Discrete, 24VAC
7 LOOP---PWR Analog, 24VDC
8 SPS Discrete, 24VAC
9 IAQ---SEN Analog, 4--- 20mA
10 FILTER Discrete, 24VAC
11 I A Q --- C O M / O A Q --- C O M / R H --- C O M Analog, 4--- 20mA
12 CCN + (RED) Digital,,5VDC
13 O A Q --- S E N / R H --- S E N Analog, 4 ---20mA
14 CCN Gnd (WHT) Digital, 5VDC
15 AUX OUT(P ower Exhaust) (Output)Discrete 24VAC
16 CCN --- (BLK) Digital, 5VDC
LEGEND:
T55 --- Space Temperature Sensor
T56 --- Space Temperature Sensor
CCN --- Carrier Comfort Network (communication bus)
CMPSAFE --- Compressor Safety
FILTER --- Dirty Filter Switch
F S D --- F i r e S h u t d o w n
IAQ --- Indoor Air Quality (CO
2
)
OAQ --- Outdoor Air Quality (CO
2
)
RH --- Relative Humidity
SFS --- Supply Fan Status
48TC