Specifications

6. Remove screw attaching burner rack assembly to base-
pan and slide out burner rack assembly from unit. See
Fig. 1. Save screw.
7. Using a
5
16
-in. nut driver, remove the screws holding
each burner on rack. Remove burners from rack. Save
screws. See Fig. 2.
8. Remove screws fastening the burner rack to the burner
bracket, and the burner bracket to the gas manifold
(8 screws total). Save screws.
9. Remove rack and burner bracket from unit. Replace the
burner bracket from the unit with the burner bracket from
the kit. There are 3 burner brackets included in the kit;
select the correct burner bracket based on the number of
burners.
10. Reattach burner rack to the burner bracket, and the burner
bracket to the gas manifold with the 8 screws saved in
Step 8.
11. Remove natural gas burner orifice(s) from manifold and
replace with LP gas orifice(s) from kit. See Fig. 2. Refer
to Tables 2 and 3 for the correct orifice sizes based on
input and altitude.
12. Replace burners in rack using screws saved from
Step 7.
13. Attach warning label from LP conversion kit to visible
side of gas valve as shown on Fig. 1.
14. Attach conversion label (Fig. 3) from LP conversion kit
above unit rating plate on exterior of unit.
Table 2 Rated Gas Inputs at Indicated Manifold Pressures
UNIT
SIZES
LP
NOMINAL
HEATING
INPUT
(Btuh)*
NUMBER OF
ORIFICES
GAS SUPPLY PRESSURE
(in. wg)
(LP)
MANIFOLD PRESSURE
(in. wg)
(LP)
LP GAS
ORIFICE PART NO.
Min Max 0-2000 Ft
2000-
5000 Ft
018040
024040
030040
40,000 1 4.0 13.0 3.1
LH32RF096
No. 41
LH32RF089
No. 43
024060
030060
036060
042060
54,000 2 4.0 13.0 3.3
LH32RF079
No. 47
LH32RF073
No. 49
030080
036080
036100
042080
042100
048080
048100
060080
060100
80,000 2 4.0 13.0 3.4
LH32RF094
No. 42
LH32RF089
No. 43
036100†
042100†
048100†
060100†
96,000 3 4.0 13.0 3.4
LH32RF086
No. 44
LH32RF082
No. 45
036120
042120
048120
060120
115,000 3 4.0 13.0 3.5
LH32RF094
No. 42
LH32RF089
No. 43
048140
060140
133,000 3 4.0 13.0 3.4
LH32RF098
No. 40
LH32RF096
No. 41
LEGEND
LP Liquid Propane
*At 0 to 2000 ft.
†Three-burner units with LP Nominal Heating Input of 96,000 Btuh will become
available in early 1998.
NOTE: Unit size 018 is for units 48SS and 588A only; unit size 024 not appli-
cable to units 48HX and 658A.
ATTACH
WARNING
LABEL
PRESSURE
TAP
PLUG
BURNERS
MANIFOLD
BURNER
RACK
SCREW SECURING
BURNER RACK ASSEMBLY
TO BASEPAN
Fig. 1 Gas Section of Unit
PRESSURE
TAP PLUG
GAS
VALVE
ASSEMBLY
BURNER
ORIFICES
BURNERS
SCREWS HOLDING
BURNERS ON
RACK (HIDDEN)
Fig. 2 Burner Rack Assembly
(54,000 and 80,000 Btuh Units Shown)
2