Specifications
APPENDIX A -- LOCAL DISPLAY AND CCN TABLES (cont)
MODE -- CONFIGURATION (cont)
ITEM I EXPANSION
CONFIGURATION (cont)
HMZR HumJdimizer Config
REHT Humidimizer Equipped
R, DEC Reheat2 Stage Decr Time
R.INC Reheat2 Stage _ncr. Time
RH.FN Reheat Fan Control
RF, LV Reheat20DP Fan On Level
R_ON Reheat20DF Fan On Tamp
R,_OF
RA.LO
RA.LR
RA.HP
RB.LO
RB.LR
RB.HP
HEAT
HT.TY
N.HTR
MRT.H
MOT.N
H.DEC
H.INC
FOD.E
FOD.G
HT.LO
SAT.H
SPT
HT.PD
HT.ND
H.LAG
ECON
EC.EN
E.CTL
EC.MN
EC.MX
EH.LO
ELLO
UEFC
FC.TM
FC.LO
PE.EN
PE.'t
PE.2
EN.SW
Reheat20DF Fan Off Tamp
Reheat2 OAT Limit A
Reheat2 SSP Lo Limit A
Reheat2 SSP Hi Limit A
Reheat2 OAT Limit B, C
Reheat2 SSP Lo Limit B, C
Reheat2 SSP Hi Limit B, C
Heating Configuration
Type of Heat Installed
RANGE UNITS DEFAULT
Yes/No No: no Humidi-MiZer FiOP
Yes: Humidi-MiZer FlOP
O to 999 secs 60
O to 999 secs 300
Yes/No Yes
0to3 2
O to 100 F 93 (20)
93 (24)
85 (28)
O to 100 F 83 (20)
88 (24)
80 (28)
20 to 70 F 40
50 to 100 ps!g 80
50 to 108 pslg 98
20 to 70 F 50
50 to 100 ps!g 80
50 to 100 pslg 90
E.TRV
E.MXB
E.MXM
E.MXT
E.DBD
EC.P
EC.I
EC.D
EC.DT
LEGEND
Number of Heat Stages
Heat MlNmum On Time
Heat Minimum Off Time
Heat Stage Decrease Rate
Heat Stage Increase Rate
Fan-off Delay, Elect Heat
Fan-off Delay, Gas Heat
Heating Lockout Tamp
SAT Heat Mode Sensing
Space Temperature Sensor
SPT Heat Demand (+) Level
SPT Heat Demand (-) Level
Heat ThermN Lag Factor
Economizer Configuration
Economizer InstNled
Economizer Control Type
Econo Minimum Position
Econo Cool Max Position
Econo Cool Hi Temp Limit
Econo Cool Lo Temp Limit
Unoccupied Free Cooling
Free Cool PreOcc Time
Free Cool Low Temp Limit
Power Exhaust Installed
PE Stage1 Econo Position
PE Stage2 Econo Position
Enthalpy Switch
Economizer Travel Time
Bottom Stage Max Econo
Middle Stage Max Econo
Top Stage Max Econo
Economizer PID Deadband
Economizer PID -- kP
Economizer PID -- kt
Economizer PID -- kD
Economizer PiD -- rate
O = No Heat
= Gas
2 = Electric
to 2
60 to 999 sec
80 to 999 sec
120 to 999 sec
120 to 999 sec
10 to 600 sec
45 to 600 sec
40 to 125 dF
EnaNe/DisaNe
0.5 to 5 ^P
-5 to -05 ^F
0 to 5 min
Yes/No
1=Digital, Position Feedback
2=Digital, Command Feedback
3=Analog Control
O to 100 %
O to 100 %
40 to 100 dF
-30 to 50 dF
O=DisaNed
l=Entire Unoccupied Period
2=PreOccupancy Time
to 9999 min
0 to 70 dF
Yes/No
10 to 100
10 to 100
0=No Switch
1=Normally Open
2=Normally Closed
5 to 300
O to 100
to 100
O to 100
0to25
00 to 99.9
00 to 99.9
0.0 to 99.9
100 to 180.0
sec
%
%
%
%
sec
sec
sec
sec
0 (50 series with no
electric heat)
1 (48 series)
2 (50 series with electric
heat)
1 (48 series 1-phase,
50 series <15kW)
2 (48 series 3-phase,
50 series >=15kW)
120
120
30O
45O
30
45
75
DisaNe
No: no FlOP
Yes: FlOP
1
3O
100
65
0
2
120
5O
No: no FlOP
Yes: FlOP
4O
75
0: no FlOP
1: FlOP
15o
5o
35
25
3
2.5
01
1
15
CCN TABLE/SUB-TABLE
HMZR CFG
HEAT_CFG
ECON_CFG
CCN POINT
REHEAT
RSTAGDEC
RSTAGINC
RHFANCTL
RHFANLEV
RHFANON
RHFANOFF
OATLRH_A
RHSSPL_A
RHSSPH A
OATLRH
RHSSPL_B
RHSSPH_B
HEATTYPE
NUM_HEAT
HMIN_ON
HMIN_OFF
HSTAGDEC
HSTAGINC
ELEC FOD
GAS FOD
OAT_HEAT
SAT_HEAT
HDEM_POS
HDEM_NEG
HEAT_LAG
ECONO
ECON_CTL
ECONOMIN
ECONOMAX
OATLECLH
OATLECLL
UEFC_CFG
UEFCTIME
OATLUEFC
PE_ENABL
PEI_POS
PE2 POS
ENT-HLCPG
ECONOTRV
ECONMAXB
ECONMAXM
ECONMAXT
ECONBAND
ECONO P
ECONO-I
ECONO_D
ECONO_DT
PAGE NO.
42, 47
47, 56
47
47
47, 56
47
47
47
47
47
47
47
47
42,44,82
42,44
42,44
43,44
43,44
44
43
42
44
44,82
36,45,57
44
44,45
45
45
45,82
FlOP -- Factory-lnstaNed Option
99