Specifications
Scrolling Marquee Display i This device is the key-
pad interface used to access rooftop information, read sensor
values, and test the unit. See Fig. 26. The Scrolling Marquee
display is a &key, 4-charactm; 16-segment LED (light-emitting
diode) display. Eleven mode LEDs are located on the display
as well as an Alarm Status LED. See Scrolling Marquee
section on page 2 for further details.
Accessory Navigator TM Display i The accessory
hand-held Navigator display can be used with the 48/50PG
series units. See Fig. 27. The Navigator display operates the
stone way as the Scrolling Marquee device. The Navigator
display plugs into the LEN port on either TB2 or the ECB
board.
Carrier Comfort Network® (CCN) Interface i
The 48/50PG units can be connected to the CCN it"desired.
The communication bus wiring is a shielded, 3-conductor
cable with drain wire and is field supplied and installed. The
system elements are connected to the co_rnnunication bus in a
daisy chain arrangement. See Fig. 28. The positive pin of each
system element communication connector must be wired to the
positive pins of the system elements on either side of it. This is
also required for the negative and siNmt ground pins of each
system element. Wiring connections for CCN should be made
at TB2. See Fig. 14-17. Consult the CCN Contractor's Manual
for further information.
NOTE: Conductors and drain wire must be 20 AWG (Ameri-
can Wire Gage) minimum stranded, tinned copper, hldividuat
conductors must be insulated with PVC, PVC/nyton, vinyl,
Teflon, or polyethylene. An aluminmn/polyester 100% Ibil
shield and an outer jacket of PVC, PVC/nylon, chrome vinyl, or
Teflon with a minimum operating temperature range of _0 C
to 60 C is required. See the table below for acceptable wiring.
MANUFACTURER PART NO.
Alpha 2413 or 5463
Belden 6772
Carol C2528
West Penn 302
It is important when connecting to a CCN colrnnunication
bus that a color-coding scheme be used for the entire network
to simplit) the installation. It is recolrnnended that red be used
for the siNml positive, black for the signal negative and white
for the sisal ground. Use a similar scheme for cables contain-
ing different colored wires.
At each system element, the shields of its colrnnunication
bus cables must be tied together. The shield screw on TB2 can
be used to tie the cables together. If the communication bus is
entirely within one building, the resulting continuous shield
must be connected to a ground at one point only. The shield
screw on TB2 is not acceptable for grounding. If the colrnnuni-
cation bus cable exits fiom one building and enters another,
the shields must be connected to grounds at the lighming sup-
pressor in each building where the cable enters or exits the
building (one point per building only). To connect the unit to
the network:
1. Turn offpower to the control box.
2. Cut the CCN wire and strip the eMs of the red (_), white
(ground), and black () conductors. (Substitute appropri-
ate colors for different colored cables.)
3. Connect the red wire to (+) terminal on TB2, the white
wire to COM terminal, and the black wire to the @)
terminal.
4. The RJ14 CCN connector on TB2 can also be used, but is
only inteMed tbr temporary connection (for example, a
laptop computer running Carrier net_xx_rksot_vare).
Fig. 26 1 Scrolling Marquee
Fig. 27 1 Accessory Navigator TM Display
5. Restore power to unit.
IMPORTANT: A shorted CCN bus cable will prevent
some routines fiom running and may prevent the unit fiom
starting. If abnormal conditions occur, unplug the connec-
tor. If conditions remm to normal, check the CCN connec-
tor and cable. Run new cable if necessary. A short in one
section of the bus can cause problems with all system ele-
ments on the bus.
Subcooler Heat Exchanger (SHX) i The purpose
of the subcooler heat exchanger (SHX) and the subcooler TXV
is to increase the capacity of the evaporator by sending sub-
cooled liquid refi-igerant into the evaporator. Normally, the
condenser subcools the liquid refi-igerant by approximately
10F. The SHX adds another 10 F to 15F degrees of subcooling
before the refi-igerant reaches the evaporator. This allows the
refi-igerant to absorb more heat fiom the mixed air, thereby pro-
viding more cooling capacity.
The subcooler functions by taking a small percentage of the
high pressure, medium temperature liquid refiigerant which
exits the condenser and converting it into a low pressure, low
temperature gas. This is accomplished by using the subcooler
TXM The gas is then routed thiough a reverse-flow heat
ex&anger (SHX), which transI_rs heat from the remaining
liquid refiigerant in the liquid line to the reverse flow gas
refrigerant. The moderate temperature gas is then sent to the
compressor to complete the loop and the cooler liquid refiiger-
ant continues its normal path to the main TXV and the
evaporator. See Fig. 29.
80