Specifications

DISPLAY MENU/
SUB-MENU/NAME
SERVICE TEST
TEST
INDP
ECON
E.CAL
PE1
PE2
ALRM
CCH
FANS
IDF
OFC1
OFC2
OFC3
COOL
CMRA
CMRB
CMRC
OROV
HMZR
RH1 .A
RH1 .B
RH1 C
RH2.A
RH2.B
RH2C
CRC
RHVA
RHVB
HEAT
HZ1
HT2
Table 36 -- Service Test Modes and Submodes Directory
EXPANDED
NAME
Field Service Test Mode
Test Independent Outputs
Economizer Position Test
Calibrate Economizer
Power Exhaust 1 Test
Power Exhaust 2 Test
Alarm Retay Test
Crankcase Heat Test
Test Fans
Indoor Fan Test
Outdoor Fan 1 Test
Outdoor Fan 2 Test
Outdoor Fan 3 Test
Test Cooling
Cool A Test
Cool B Test
Cool C Test
Outdoor Fan Override
Test Hamidimizer
Reheat1 A Test
Reheat1 B Test
Reheat1 C Test
Reheat2 A Test
Reheat2 B Test
Reheat2 C Test
Cool->Reheat1 Valve Test
Reheat2 Vaive A Test
Reheat2 Valve B Test
Test Heating
Heat Stage 1 Test
Heat Stage 2 Test
VALUES UNITS DEFAULT
On/Off Off
0to100 % 0
On/Off Off
On/Off Off
On/Off Off
On/Off Off
On/Off Off
On/Off Off
On/Off Off
On/Off Off
On/Off Off
On/Off Off
On/Off Off
On/Off Off
On/Off Off
On/Off Off
On/Off Off
On/Off Off
On/Off Off
On/Off Off
On/Off Off
On/Off Off
On/Off Off
On/Off Off
On/Off Off
On/Off Off
CCN TABLE/
SUB-TABLE
MAINTENANCE DISPLAY
TESTINDP
TESTFANS
TESTCOOL
TESTHMZR
TESTHEAT
CCN
NAME
(TEST = display onty)
S ECONO
S-ECOCAL
S-PE 1
S-PE-2
S-ALh4OUT
S-CCH
S IDF
SZOFC_I
S OFC 2
SZOFC:3
S COMP A
S-COMP_B
S COMP C
S:OFC_(SV
S RH1A
S-RH1-B
S-RH1-C
S2 RH2 A
S2 RH2 B
S2 RH2 C
S CRC
S-RH2 A
S:RH2:B
S_HEAT_I
S_H EAT_2
THIRD PARTY CONTROL
Third party controls may interface with the unit
('Ol//Jbrtkink TM controls tba'ough the connections described
belo,a: See other sections of these instructions for more
intbnnation on the related unit control confignrations.
Thermostat -- The therlnostat inputs are provided on the
field connection terlninat board (TB2). The Therlnostat
Connol Type configuration, Configuration -+UNIT---_T.(TL,
selects the unit response to these inputs.
Y1 first stage cooling
Y2 second stage cooling
W1 first stage heating
W2 second stage heating
G indoor tan
Humidistat -- For units with the factory Humidi-MiZer TM
option, the humidistat input is provided on the field connection
terminal board (TB2). The Space Humidity Switch confignra-
tion, Configumtion---_UNIr---_RH.SW, identities the nonnalty
open or normally closed status of this input at high humidity.
Humidistat 1 24 VAC signal input
Hmnidistat 2 24 VAC source for dry contact
Humidity Sensor -- For units with the factory Humidi-
MiZer option and the economizer option with the ECB (econo-
mizer control board), the humidity sensor input is provided on
the field connection terminal board (TB2). The sensor can be
used instead of a humidistat. The RH Sensor on OAQ Input
confignration, Configumtion--_UNIT--_RH, q=YES, identi-
fies the sensor use. Default conversion to 0 to 100% relative
humidity can be changed in the confignrations.
4 4-20 mA + signal input
3 4-20 mA colrnnon
Remote Occupancy -- The remote occupancy input is
provided on the field connection terminal board (TB2). The
Remote Occupancy Switch conlignration, (bnfiguration
--->U_ClT---yRM..SVV,identifies the nonnalty open or normally
closed status of this input when unoccupied.
5 24 VAC signal input
6 24 VAC source for dry contact
Fire Shutdown -- The fire shutdo,a_ input is provided
for unit shutdown in response to a tire alarln or smoke detector.
The Fire Shutdown Switch conlignration, Configuration
-+UNIT-+FS.SW, identifies the norlnalty open or nonnatly
closed status of this input when there is no fire alarln.
For 48/50 units without Humidi-MiZer system, input at field
connection terlninal board (TB2)
Fire Shutdown 1 24 VAC source for dry contact
Fire Shutdo,am 2 24 VAC si_at input
For 50 series units with Humidi-MiZer system, input at wire
harness plug 19 (PL 19)
PL 19-3 24 VAC source for dry contact
PL 19-5 24 VAC signal input for fire shutdown
For 48 series units with Humidi-MiZer system, input at wire
harness plug 19 (PL 19)
PL 19-3 24 VAC source for dry contact
PL 19-5 24 VAC signal tbr Fire Shutdown
PL 19-4 24 VAC power for indoor fan contactor control
circuit
NOTE: For 48 series units with Humidi-MiZer system, if the
indoor fan must be shut down without any delay upon Fire
Shutdown input, then the factory julnper between PL 19-3 and
PL19-4 must be replaced with a norlnally closed contact when
there is no atann (open with atann).
Alarm Output- The alarln output is provided on the
field connection terminal board (TB2) to indicate a current
atann status. The output will be 24VAC if a current atann
exists.
C 24 VAC comlnon
X 24 VAC signal output
Outdoor Enthalpy- For units with the economizer
option or accessory and the ECB control board, the outdoor
enthalpy input is provided on the field connection terminal
board (TB2). The Enthalpy Switch confignration, (bnfigura-
tion---_E{DN--+EN..SW, identifies the nonnalty open or
normally closed status of this input when the outdoor enthalpy
is low.
6 24 VAC source for dry contact
7 24 VAC signal input