48/50PG20-28 Single Package Rooftop Units with COMFORTLINK TMControls and PURON® (R-410A) Refrigerant Controls, Start-Up, Operation, Service and Troubleshooting Instructions CONTENTS SAFETY CONSIDERATIONS ............................... Page 2 GENERAL .................................................. 2 BASIC CONTROL USAGE ................................ 2-5 ComfortLink TM Control ..................................... 2 Scrolling Marquee .........................................
CONTENTS (cont) Page ENTHALPY SENSORS RETURN/SUPPLY AIR TEMPERATURE SENSOR SPA(E HUMIDITY SENSOR ELECTRIC HEAT SERVICE ............................................... 85-92 Cleaning .................................................. 85 Lubrication ............................................... 86 Manual Outdoor Air Damper .............................. 87 Economizer Adjustment .................................. 87 Evaporator Fan Service and Replacement .................
Scrolling Marquee -- This device is the keypad imerface used to access the control information, read sensor values, and test the unit. The Scrolling Marquee is located in the main control box and is standard on all units. The Scrolling Marquee display is a 4-key, 4-character, 16-seglnent LED (light-emitting diode) display module. The display also contains an Alarm Stares LED. See Fig. 1.
System PilotTM Device -- The System Pilot (33PILOT01) device is a component of Ca_cier's 3VTM system and serves as a user-interface and confimlration tool for all Carrier communicating devices. The System Pilot device can be used to install and commission a 3V zoning system, linkage compatible air source, universal controllei; and all other devices operating on the Canier comlnunicating network.
Table 2 -- Scrolling Marquee Menu Display Structure RUN STATUS Auto View of Run Status (VIEW) SERVICE TEST Service Test TEMPERATURES Mode (TEST) ¢ Software Version Numbers (VERS) ¢ Test ¢ Test ¢ ¢ Modes (MODE) 4, Cooling Status (COOL) ¢ Refrigerant Temperatures (REFT} Condenser Rressu_A (SCRA) 4, Occupied Cool Setpoint (OCSR) 4, Unoccupied Setpoint (UCSP) 4, Cool Cooling Suction Pressure B (SSRB) 4, Occupied Heat Setpoint (OHSP) (COOL) 4, Control A INPUTS Fans (FANS) Component
START-UP various motor pulley settings. To alter tan performance, see Evaporator Fan Performance Adjustment section on page 87. Use the t'ollowing information and Start-Up Checklist on page CL-1 to check out unit PRIOR to start-up. Unit Preparation -- Check that unit Ms been installed in accor&mce with these installation instructions and all applicable codes. Compressor MountingCompressors are internally spring mounted. Do not loosen or remove compressor holddown bolts.
connected to a 208-v power supply, the transformers (TRAN 1, TRAN2 and TRAN3) must be rewired by moving the wire fiom the 230-volt connection and moving to the 200-volt terminal on the primary side of the transibnner. Rei}r to unit label dia_am for additional inforlnation. Orifice Change (48PG Only) -- This unit is factory assembled for heating operation using natural gas at aal elevation lfom sea level to 2000 ft.
Table 4 -- Fan Performance -- 48PGE20 -- Vertical Supply/Return AVAILABLE AIRFLOW EXTERNAL 0.4 0.2 (Cfm) 1,53 Rpm 677 Bhp 1.80 Rpm Bhp 5000 607 Rpm 740 Bhp 206 779 247 819 293 wg) 0.8 1.0 Rpm 797 Bhp 231 833 274 872 322 Rpm 850 Bhp 257 884 301 921 350 958 405 998 466 5500 652 1.90 719 219 6000 699 2.32 763 263 6500 746 2.79 8O7 312 861 344 911 375 7000 794 3.33 851 368 904 402 952 434 7500 842 3.93 897 4.30 947 4.
Table 5 -- Fan Performance --48PGF20 AVAILABLE AIRFLOW (Cfm) 0.2 Rpm EXTERNAL 0.4 Supply/Return STATIC PRESSURE (in. wg) 0.8 0.6 Rpm 677 Bhp 1.80 Units 1.0 5000 607 Bhp 1.53 5500 652 1.90 719 2.19 6000 699 232 763 6500 746 279 807 2.63 3.12 7000 794 333 851 3.68 904 4.02 7500 842 393 897 4.30 947 4.65 8000 891 4.59 943 4.98 991 5.35 1036 5.71 8500 940 5.32 B 990 5.72 1036 6.11 1080 649 99O 612 C 1037 6.54 1082 6.
Table 6 -- Fan Performance -- 48PGD24 -- Vertical Supply/Return AVAILABLE AIRFLOW (Cfm) EXTERNAL 0.4 0.2 Rpm 7O3 Bhp 211 Rprn 764 Bhp 240 744 253 8O3 284 786 301 842 333 3.17 828 353 883 388 813 3.74 871 412 924 4.48 8,000 859 4.36 915 4.77 966 515 8,500 906 5.05 959 547 1008 587 9,000 962 5.81 1004 625 1051 667 9,500 999 6.63 1049 709 1094 753 10,000 1047 7.53 1094 800 1138 846 5,500 Rpm 633 Bhp 1.82 6,000 677 2.21 6,500 722 2.
Table 7 -- Fan Performance -- 48PGE24 -- Vertical Supply/Return AVAILABLE AIRFLOW (Cfm) 0.2 Rpm EXTERNAL 0.4 5,500 652 Bhp 1.90 6,000 699 232 6,500 746 279 7,000 794 7,500 Rpm (in. wg) 0.6 0.8 719 763 2.63 819 2.93 872 322 807 3.12 861 3.44 911 375 333 851 3.68 904 4.02 952 434 842 393 897 4.30 947 4.65 994 5.00 1038 533 8,000 891 4.59 943 4.98 991 5.35 1036 5.71 1079 607 8,500 940 532 990 5.72 1036 6.11 1080 6.
Table 8 -- Fan Performance -- 48PGF24 -- Vertical Supply/Return AVAILABLE AIRFLOW (Cfm) 0.2 EXTERNAL 0.4 Rpm 719 Bhp 219 Rprn 763 263 819 807 312 861 293 344 3.33 851 368 904 402 842 3.93 897 4.30 947 8,000 891 4.59 943 4.98 991 4.65 535 8,500 940 6.32 990 572 1036 611 9,000 990 6.12 1037 654 1082 695 9,500 1039 7.00 1085 743 1128 785 10,000 1089 7.95 1133 840 1174 883 5,500 Rpm 652 Bhp 1.90 6,000 699 2.32 6,500 746 2.
Table 9 -- Fan Performance -- 48PGD28 -- Vertical Supply/Return AVAILABLE AIRFLOW (Cfm) 0.2 Rprn 6,500 750 Bhp 2.84 797 3.38 7,500 845 3.99 8,000 892 4.65 8,500 939 5.38 9,000 986 6.17 1033 10,000 10,500 Rprn A A 0.8 Rpm 854 Bhp 349 899 409 945 476 Bhp 379 941 985 Rprn 943 Bhp 412 441 982 474 509 1024 543 1030 586 1067 620 1076 669 1112 705 1122 760 1157 798 1203 899 1249 1008 B 3.77 4.42 948 5.13 991 551 995 5.91 1038 632 1042 6.
Table 10 -- Fan Performance -- 48PGE28 -- Vertical Supply/Return AVAILABLE AIRFLOW (Cfm) 6,500 0.2 A Rpm 775 EXTERNAL 0.4 Bhp 299 826 358 878 424 8,000 929 8,500 A Rpm 825 Bhp 330 Rpm A STATIC PRESSURE 0.
Table 11 -- Fan Performance -- 48PGF28 --Vertical AVAILABLE AIRFLOW (Cfm) 0.2 Rprn 6,500 Bhp 2.99 775 A 7,000 826 3.58 7,500 878 929 4.24 4.98 8,500 981 5.78 9,000 1033 9,500 1085 6.67 7.64 10,000 1137 8.69 10,500 1190 9.82 11,000 1242 11,500 12,000 8,000 EXTERNAL 0.4 A Rpm 825 STATIC PRESSURE Bhp 3.30 A 0.8 Rpm 871 Bhp 360 918 966 423 494 1015 572 1064 1114 658 751 3.92 925 975 4.61 1026 6.20 1076 1128 7.12 8.12 1164 854 1179 9.20 1230 10.
Table 12 -- Fan Performance -- 50PG20 --Vertical AVAILABLE AIRFLOW (Cfm) 0.2 Rpm EXTERNAL STATIC PRESSURE 0.6 (in. wg) Rpm 682 Bhp 1.82 0.4 5000 533 Bhp 1.27 5500 571 6000 610 6500 Rpm Rpm 611 Bhp 1.54 1.57 643 1.86 711 215 1.92 676 2.21 74O 252 650 2.31 712 261 772 7000 691 275 748 308 7500 732 324 788 8000 775 379 8500 817 9000 860 773 244 8OO 282 293 829 8O5 339 357 839 824 412 4.40 863 4.74 5.06 904 5.
Table 13- Fan PerformanceAVAILABLE AIRFLOW (Cfm) 0.2 50PG24EXTERNAL 0.4 5,500 Rpm 571 Bhp 1,57 6,000 610 6,500 650 7,000 Rpm STATIC PRESSURE 0.6 643 Bhp 1.86 Rpm 711 Bhp 2.15 1.92 676 2.21 74O 2.52 2.31 712 2.61 772 2.93 691 2.75 748 3.06 8O5 7,500 732 3.24 786 3.57 8,000 775 3.79 824 4.12 8,500 817 4.40 863 9,000 860 5.06 9,500 903 10,000 947 (in. wg) 0.8 1.0 Bhp 2.44 8O0 2.82 3.25 883 3.58 3.39 829 859 3.73 911 4.07 839 3.91 891 4.
Table 14 -- Fan Performance -- 50PG28 --Vertical AVAILABLE AIRFLOW (Cfm) 0.
Table 15 -- Fan Performance -- 48PGD20 -- Horizontal Supply and Return Units AVAILABLE AIRFLOW (Cfm) 0.2 Rpm 5000 5500 862 Bhp 2.55 937 326 6000 1013 358 6500 1089 4.48 1166 552 1243 671 8000 1320 807 8500 1398 9.60 F 7000 G 7500 H EXTERNAL 0.4 Rpm Bhp 2.93 917 F G H 988 1060 3.56 1133 4.89 1207 5.96 1282 7.18 1356 8.57 F 3.96 G H STATIC PRESSURE 0.6 Rpm 969 Bhp 3.21 1036 3.53 1105 4.35 1175 5.31 1247 6.41 1319 7.66 1392 9.08 (in. wg) 0.8 1.
Table 16 -- Fan Performance -- 48PGE20 -- Horizontal Supply and Return Units AVAILABLE AIRFLOW 0.2 (Cfm) 5000 5500 6000 F 6500 Rpm 875 Bhp 2.74 962 3.38 1029 3.74 1106 4.67 7000 G 1184 5.75 7500 H 1262 7.00 1341 8.41 8000 EXTERNAL 0.4 Rpm 931 F G H Bhp 304 1003 332 1077 415 1151 511 1226 623 1302 750 1378 8.95 STATIC PRESSURE 0.6 Rpm F G H 984 Bhp 334 1053 370 1123 456 1194 556 1266 1340 (in. wg) 0.8 Rpm 1.
Table 17 -- Fan Performance -- 48PGF20 -- Horizontal Supply and Return Units AVAILABLE AIRFLOW (Cfm) 0.2 Rpm 5000 5500 875 Bhp 2.74 952 338 6000 1029 374 6500 1106 4.67 F Rpm F G 931 Bhp 3.04 1003 3.32 1077 4.15 1151 5.11 1226 6.23 G 1184 575 7500 H 1262 700 1302 7.50 1341 8.41 1378 8.95 H STATIC PRESSURE (in. wg) 0.6 7000 8000 EXTERNAL 0.4 F G H 1.0 0.8 Rpm 984 1035 Bhp 333 3.34 1053 3.70 1123 4.56 1100 409 1167 498 1194 5.56 1236 601 1266 6.
Table 18 -- Fan Performance -- 48PGD24 -- Horizontal Supply and Return Units AVAILABLE AIRFLOW (Cfm) 0.2 Rpm 937 Bhp 3.26 6,000 1013 3.58 6,500 1089 4.49 1166 5.52 1243 6.71 8,000 1320 8.07 8,500 1398 9.60 5,500 F 7,000 G 7,500 H EXTERNAL 0.4 F G H Rpm 988 Bhp 356 STATIC PRESSURE 0.6 Rprn F 1036 Bhp 353 1105 4.35 1175 531 1247 641 1060 396 1133 489 1207 596 1282 718 1319 766 1366 8.57 1392 9.08 G H (in. wg) 0.8 Rpm F G H 1.
Table 19 -- Fan Performance -- 48PGE24 -- Horizontal Supply and Return Units AVAILABLE AIRFLOW (Cfm) 0.2 Rpm 952 Bhp 338 6,000 1029 374 6,500 1106 4.67 5,500 F EXTERNAL 0.4 7,000 G 1184 575 7,500 H 1262 700 8,000 1341 8.41 Rpm F G H 1003 Bhp 3.32 1077 4.15 1151 5.11 1226 8.23 1302 7.50 1378 8.95 F G H STATIC PRESSURE 0.6 Rpm 1053 Bhp 3.70 1123 4.56 1194 5.56 1266 1340 (in. wg) 0.8 1.0 F Rpm 1100 Bhp 4.09 G 1167 4.98 1236 8.01 6.71 1306 7.19 8.
Table 20 -- Fan Performance -- 48PGF24 -- Horizontal Supply and Return Units AVAILABLE AIRFLOW 0.2 (Cfm) 5,500 F Rpm 952 Bhp 3.38 6,000 1029 3.74 6,500 1106 4.67 7,000 G 1184 5.75 7,500 H 1262 7.00 1341 8.41 8,000 EXTERNAL 0.4 F G H Rpm 1003 Bhp 332 1077 415 1151 511 1226 623 1302 750 1378 8.95 F G H STATIC PRESSURE 0.6 Rpm 1053 Bhp 370 1123 456 1194 556 1266 1340 F G (in. wg) 0.8 Rprn 1100 1.0 Bhp 409 Bhp 449 1210 541 1276 647 1344 7.
Table 21 -- Fan Performance -- 48PGD28 -- Horizontal Supply and Return Units AVAILABLE AIRFLOW (Cfm) 0.2 Rprn 6,500 Bhp 3.06 786 E 7,000 842 3.69 7,500 898 4.40 955 5.20 1012 6.08 1069 8,000 F 8,500 9,000 E F 871 925 979 4.61 5.40 1034 6.29 1090 1146 7.26 8.32 1202 9.49 1258 10.75 9,500 1127 10,000 1184 9.27 1242 10.52 11,000 1299 11,88 1315 12.11 11,500 1357 13.35 1372 13.58 H G Bhp 3.26 3.89 Rpm 819 H STATIC PRESSURE (in. wg) 0.6 7.05 8.
Table 22 -- Fan Performance -- 48PGE28 -- Horizontal Supply and Return Units AVAILABLE AIRFLOW 0.2 (Cfm) 6,500 Rpm 799 E EXTERNAL 0.4 Bhp 314 E Rpm 833 887 Bhp 335 400 F 941 474 Rpm E STATIC PRESSURE 0.6 921 425 972 499 1024 580 1055 608 1078 671 1132 771 1106 1158 1187 880 1211 908 1243 1000 1265 856 379 913 452 971 533 996 555 1029 624 1052 1087 723 9,500 1145 832 1108 1165 646 746 10,000 1203 950 1222 974 10,500 1261 1079 1279 1103 1299 11.
Table 23 -- Fan Performance -- 48PGF28 -- Horizontal Supply and Return Units AVAILABLE AIRFLOW (Cfm) 0.2 Rprn 6,500 E Bhp 3.14 799 Rpm E 833 Bhp 3.35 887 4.00 941 4.74 3.79 913 4.52 8,000 971 5.33 996 5.55 8,500 1029 8.24 1052 8.46 1087 7.23 1108 7.46 9,500 1145 8.32 1165 8.55 10,000 1203 9.50 1222 9.74 10,500 1261 10.79 1279 11.03 11,000 1320 12.18 1337 12.43 11,500 1378 13.68 7,500 9,000 F G H F G H STATIC PRESSURE (in. wg) 0.
Table 24 -- Fan Performance -- 50PG20 -- Horizontal Supply/Return AVAILABLE AIRFLOW (Cfm) 0.2 EXTERNAL 0.4 Rpm 642 Bhp 1.61 Rpm 7OO Bhp 184 0.8 1.0 5000 5500 619 1.71 682 1.96 737 221 6000 663 2.09 723 235 776 262 6500 708 253 765 280 816 308 863 335 9O6 3.63 7000 753 302 8O7 330 857 359 9O2 388 944 4.17 7500 800 358 85O 386 898 416 942 4.47 8000 847 420 894 4.48 940 4.60 982 511 8500 894 4,88 939 5.
Table 25 -- Fan Performance -- 50PG24 -- Horizontal Supply/Return AVAILABLE AIRFLOW (Cfm) 0.2 EXTERNAL 0.4 Bhp 1.71 Rpm 5,500 Rpm 619 6,000 663 6,500 7O8 7,000 682 Bhp 1.96 Rpm 737 Bhp 2.21 2.09 723 2.35 776 2.62 2.53 765 2.80 816 3.08 753 3.02 807 3.30 857 7,500 8OO 3.58 850 3.86 8,000 847 4.20 894 4.48 8,500 894 4.88 939 5.17 9,000 941 5.63 983 5.92 9,500 989 6.45 1029 6.74 10,000 1037 7.34 1075 7.63 AVAILABLE AIRFLOW (Cfm) 4.17 942 4.
Table 26 -- Fan Performance -- 50PG28 -- Horizontal Supply/Return AVAILABLE AIRFLOW (Cfm) 0.2 Rpm 759 6,500 EXTERNAL 0.4 Bhp Rpm 8O4 Bhp 317 853 377 903 443 953 STATIC PRESSURE 0.6 Rpm 844 Bhp 342 891 404 939 472 518 988 548 1003 599 1037 1054 689 1087 632 723 1137 E Units (in. wg) 0.8 1.
Table 28 -- Air Quantity Limits (50PG20-28 Units) ELECTRIC HEAT (Vertical) MINIMUM CFM ELECTRIC HEAT (Horizontal) MINIMUM CFM 4,500 5.400 3,756 4.800 Low Heat (25 kW) 3,750 3.750 High Heat (75 kW) 4,560 5.400 3,756 4.800 Low Heat (25 kW) 3,750 3.750 High Heat (75 kW) 4,560 5.400 3,756 4.800 3,750 3.
Table 29 -- Evaporator Fan Motor Specifications -- 48PG20-28 Units (cont) UNIT 48PG DRIVE Low Mid-Low Mid-High High Low Mid-Low Mid-High High ORIENTATION Vertical Vertical Vertical Vertical Horizontal Horizontal Horizontal Horizontal NOMINAL MAX BHP MAX BkW MAX AMPS 5 HP VOLTAGE 2O8 MAX WATTS 4578 87.5 537 4.01 158 5 5 23O 46O 5115 5115 87.5 87.5 6.00 6.00 4.48 4.48 154 77 5 575 5015 87.5 5.88 4.39 5 2O8 4578 87.5 5.37 4.01 158 5 23O 5115 87.5 6.00 4.
Table 30 -- Evaporator Fan Motor Specifications UNiT 50PG DRIVE Low Mid-Low Mid-High High ORIENTATION Vertical Vertical Vertical Vertical 24 Low Mid-Low Mid-High High Low Mid-Low Mid-High High Horizontal Horizontal Horizontal Horizontal Vertical Vertical Vertical Vertical 28 Low Mid-Low Mid-High High Horizontal Horizontal Horizontal Horizontal NOMINAL HP VOLTAGE MAX WATTS MAX BNP MAX BkW MAX AMPS 37 208 3700 858 426 3.17 10.
Table 31 -- Accessory/FlOP Static Pressure (in. wg)* -- 48/50PG20-28 Units CFM 4,500 Economizer 0.02 Humidi-MiZer COMPONENT(20, 24) Humidi-MiZer (28) I TM 8.03 004 -5,000 4,000 I 005 006 0.10 5,500 017 6,000 -- I 7,009 7,500 8,000 0.87 0.08 0.09 0.10 0.25 6,500 0.05 0.32 0.40 0.47 0.I3 0.21 0.29 CFM 9,909 Economizer Humidi-MiZer COMPONENT (20, 24) Humidi-MiZer (28) I 0.11 8.12 013 8,500 0.54 0.38 8.60 8.44 068 9,500 0.5I I 015 0.I6 074 10,009 059 .... 19,500 0.
Table 34 -- Fan Rpm At Motor Pulley Settings* -- 50PG20-28 50PG MOTOR DRIVE O _ 685 Range Vertical Mid-High Range Vertical High Range Vertical Low Range Vertical Mid-Low 20 and 24 (230 and 460 volt) Low Range HodzontN Mid-Low Range HodzontN Mid-High Range Horizontal High Range Horizontal Low Range Vertical 20 and 24 (575 Volt) Mid-Low Range Vertical Mid-High Range Vertical High Range Vertical Low Range HodzontN Mid-Low Range Mid-High Range Horizontal High Range HodzontN Horizontal
SERVICE Control Configuration ChecklistRefer to checklist CL- 1 for recording site specific unit control configurations. The Service Test function can be used to verify proper operation of compressors, heating stages, indoor tan, outdoor finis, power exhaust tans, economizer, and atann relay. Use of Service Test is recommended at initial system start up and during troubleshooting. See Table 36.
Table 35 -- Setting an Occupied Time Schedule -- Weekdays Only for 7:30 to 22:30 DISPLAY MENU TIMECLOCK SCH.L SUB-SUB MODE PER.1 KEYPAD ENTRY [] [] [] [] [] [] [] [] [] [] [] [] [] [] [] [] [] [] [] [] [] [] [] [] [] [] [] [] [] [] [] [] [] [] [] [] [] [] [] [] [] [] [] [] ITEM DISPLAY ITEM EXPANSION Local Occupancy OCC.I COMMENT Schedule Period Occupied Time 00.00 Scrolling 00.00 Hours Flash 07.00 Select 07.00 Change 07.30 Select 07.30 Change OCC. I 07.30 UNC.1 00.
Table 36 -- Service Test Modes and Submodes Directory DISPLAY MENU/ SUB-MENU/NAME SERVICE TEST EXPANDED NAME VALUES UNITS TEST MAINTENANCE Field Service Test Mode On/Off Test Independent Outputs Economizer Position Test Calibrate Economizer Power Exhaust 1 Test Power Exhaust 2 Test Alarm Retay Test Crankcase Heat Test FANS IDF OFC1 OFC2 OFC3 Test Fans Indoor Fan Test Outdoor Fan 1 Test Outdoor Fan 2 Test Outdoor Fan 3 Test On/Off On/Off On/Off On/Off Off Off Off Off COOL CMRA CMRB CMRC OROV Te
IAQ Switch -- For units with the economizer option or accessory and the ECB control board, the IAQ switch input is provided on the field connection terminal board (TB2). The IAQ Switch Input configuration, Configuration-->AIR.Q --->I!.CEidentifies the nonnatly open or nonnatly closed status of this input when the indoor air quality value is low (good) and also selects the unit response to this input.
Shut Down on IDF Failure (IDF..F) This conli_ration applies only ifa tan switch is installed and configured. A YES value wilt enable diagnostic Alert T409 to shut down the unit when incorrect tan status is sensed. A NO value will still permit Alert T409 but will not cause unit shutdown. The factory default value is YES. Economizer Installed (ECEN) This confimlration identifies if an economizer is installed. A YES value enables economizer operation. A NO value disables economizer operation.
Indoor Fan -- The indoor thn is controlled by the indoor tan relay output (Outputs--->FA?_i9--->IDF)on the MBB (main base board) control, wNch then operates the indoor tan contactor. The indoor fan may operate during cooling with compressors mode, fiee cooling with outdoor air mode, heating mode, or for ventilation with outdoor air mode. ensure proper time delays and SAT control when the economizer is cooling. Cooling begins when the Y1 input is energized.
Two methods are used to add and relnove stages of cooling for units with more than one compressor. The first method causes the unit to operate around its steady-state number of stages. For example, if the correct number of stages is between 0 and 1, this method wilt cause the first stage to cycle. If the correct number of stages is between 1 and 2, this method will cause the second stage to cycle. The second method causes the unit to find the steady-state nulnber of stages.
If theindoor tancontrol isconfigured tocyclewiththeheating demand ((bnfiguration---_UNIr_OC.FN = No) the is satisfied, the MBB will mm off HT. 1 which will turn off gas to the main burners. thn will stop after a conligured delay, (bnfiguration---_ HEAT---_FOD.G Factory dethutt value is 45 seconds. If the IGC temperature limit switch opens within 10 minutes of the end of the gas heating, the next thn off delay wilt be extended by 15 seconds. The maximum delay is 3 minutes.
The control uses rvvomethods to add a stage of heating. The first method will add a stage of heating when the Heating Demand (Operating Modes-+HEAT---aqPT-+ DMD.H) plus the change in heat demand (Operating Modes -+HEAT_SPT-+TRD.H) times the Heat Thermal Lag Factor (Operating Modes-+HEAT---)_7PT-+H.LAG) is greater than the SPT Heat Demand (+) Level (Operating Modes-+ HEAT---_qPT -+HT..PD ). DMD.H + TRD.H * H.LAG > HT..PD indoor tan wilt follow the HT. 1 output.
SPACE SENSOR CONTROL If theunitis in cooling, operating underspace tcnnperature control, theeconomizer is available forcooling, andnocompressors areoperating, the economizer willcontrol theSATtoeither Setpoints--->LCgP or Free Cooling ((bnfiguration--+E_DN--+UEFC), Free Cooling Preoccupancy Time (Configuration--_E(ON--_FC. TM) and Free Cool Low Ternp Limit ((bnfiguration--_ ECON--_FC.LO). (bnfiguration--_E_ON--_UEFC = 0 (Disabled) When UEFC = 0, unoccupied fiee cooling is disabled.
Outdoorfan controlfor Humidi-MiZer sTstem units includes aMotonnaster(r9 variable-speed control ofsome orall outdoor Pans, depending onunitmodelsize.TheMotonnaster control automatically adjusts theoutdoor fanspeed tomaintain approximately 80to100Fcondenser temperature forcircuitA atalloutdoor mnbient temperatures. Some modelsizeshave additional on!offstaging ofsome outdoor fans.Thisstaging is controlled by bothoutdoor temperature andcondenser coil temperature.
RH2.x ) I} _,-_,_ CLOSED VALVE OPEN VALVE [_ METERING DEVICE 3-WAY VALVE INDOOR ENTERING AIR Fig. 8 -- Hot Gas Reheat Mode (Reheat2) -- Humidi-MiZer Space Humidity Switch (Configuration --yUNIT--yRH.SVV) Set to 1 for use of a normally open switch, or 2 tbr normally closed switch. The switch is wired to field connection terminal board terminals labeled HUMDISTAT. TM System multiple circuits in Reheat2 mode.
REHEAT MODESELECTION PROCESSSelection ofthe reheat modeforeach refi-igerant circuitisdetermined fiomthe space humidity(tiomRHsensor or switchinput)andthe circuitcooling delnand (fiomspace temperature sensor orthermostat input).Table 42shows theconesponding circuitmode andoutput status forthedifferent demand combinations. Figure9 showsthevalvelocations of Humidi-MiZer TM equipped units.
\ \ \\\ \\\\ \\\\\\\\\\ \ _\\\\\ \\\ \\\\\\\\\ \ 8 _9 PLACES PLACES ON 020 \ \ 0_ O_ 628 _s Et_CHS_E Fig. 10- Wind Baffle Dimensions relnove contaminants and CO 2generated by sources other than people. The ECMN should be set to an economizer position that brings in enough flesh air to remove contaminants and CO2 generated by all sources including people. The ECMN value is the design value for maximum occupancy. The ComJbrtLink control will begin to open the damper tiom the AQ.
---_ECMN or Configuration---_AIR.Q_OVR.P to provide economizer cooling. IA.CF = 3 (Control Minilnmn Position) When IA.CF = 3, an external 4 to 20 mA somce is used to set the minilnum position. The 4 mA signal corresponds to 0% and the 20 mA signal corresponds to 100%. In this mode, confignrations such as Configutvttion---_AIR.Q---_EC.MN and Configuration---_ AIR. Q---_AQ.MN are not used. If the indoor fian is not operating, the economizer position will be zero.
Compensated mode wilt stay on until the unit goes into the Occupied mode. The Start Bias Time will be written into the CCN Linkage Equipment Table if the unit is controlled in DAV mode. If the Unoccupied Economizer Free Cool mode is active when temperature compensated start begins, the Unoccupied Free Coot mode will be stopped. Configuration--+AIR.Q--+IA.FN= 2 (Always) The indoor tan performance for IA.FN = 2 is the sane as the perforlnance when IA.
Timed Override Hours (SCH.O_OV.EX) This displays the current number of hours left in an override. It is possible to cancel an override in pr%mess by writing "0" to this variable, thereby relnoving the override time left. SPY Override Enabled? (SCH.O_OV.SP) Ifa space sensor is present, then it is possible to ovm_ide an unoccupied period by pushing the override button on the T55 or T56 sensor. This option allows the user to disable tNs function by setting this configuration to NO.
Table 43 -- ComfortLink ALARM OR ALERT NUMBER T051 DESCRIPTION Compressor A1 Safety Trip Compressor A1 Current Compressor Compressor Compressor B1 Safety Trip Compressor B1 Current Detected T059 Compressor Cl T064 Compressor Cl Current Detected After Turnoff Circuit A Saturated Condensing Tamp Thermistor Failure T052 T055 TM Alarm Codes ACTION TAKEN BY CONTROL RESET METHOD PROBABLE Add Strike for Circuit A Automatic errorHigh-pressure switch open Compressor Turn off all compressors
Table 43 -- ComfortLink ALARM OR ALERT NUMBER T410 DESCRIPTION R-Wf Jumper Not InstNled R-Wf Jumper Service Test Must Be Installed to Run Heat In in Space Temp Mode T411 Thermostat Activated Y2 Input Activated T412 Thermostat Activated W2 Input Activated T413 Thermostat Y and W Inputs Activated Simultaneously T414 without without Yt Wl Economizer Damper Actuator Out of Calibration Economizer Limit Damper Actuator Torque Above Load Economizer Damper Actuator Hunting Excessivel_ Eco
andthereis nocurrent, verilyCSwiringandreplace if necessary. 4. Return toNormalmodeandobsmTe compressor operationtoverifythatcompressor current sensor is working andcoMenser/hns areenergized aftercompressor starts. 240 F (40 to 116 C). This alert wilt only occur if the unit is confimlred for a return air sensor. There is no control action as a result of this alert. This alert resets automatically.
return air,orstuck openeconomizer whentheambient temperatureislow. Alert Code T140 (Loss of Charge) See Alert Tll0. Alert Code T141 (Low Refrigerant Pressure) See Alert T133. Alert Code T142 (High Refrigerant Pressure) T126. See Alert Alert Codes T 143, T 144, T 145 (Failure to Pressurize) Alert codes T143, T144, and T145 are for circuits A, B, and C, respectively.
Alert Code T412 (W2 without Wl) This alert occurs in Thermostat mode when W2 is energized and Wl is not. Veri_ thermostat and thermostat wiring. When W2 turns On, the software wilt b&ave as if W1 and W2 are both On. When W2 turns Off, the sotgvare will b&ave as ifWl and W2 are both O1t_This alert resets automatically when W1 is turned On. Alert Code T413 (Y and W Simultaneously) This alert occurs in Thermostat mode when Y1 or Y2 is energized simultaneously with Wl or W2.
Table 44 -- Cooling PROBLEM Compressor and Fan Will Not Start. Service Analysis CAUSE REMEDY Power failure. Fuse btown or circuit breaker tripped CB3 Disconnect off Check CB1, CB2, and Power disconnect. Compressor time guard to prevent short cycling Thermostat or occupancy schedule set point not calting for Cooling Outdoor temperature too tow. Active alarm. Compressor Cycles (other than normally satisfying thermostat). Insufficient line voltage. Active alarm.
Table 45 -- Humidi-MiZer PROBLEM TM Service Analysis CAUSE Subcooling Reheat Mode Will Not Activate. Hot Gas Reheat Mode Will Not Activate. REMEDY General cooling mode problem No dehumidification demand. See Cooting Service Analysis (Table 44). See No Dehumidification Demand, below. Circuit RH1 valve is not open See RH1 Valve Operation, below General cooling mode probIem No dehumidification demand. See Cooting Service Analysis (Table 44). See No Dehumidification Demand, below.
Table 46 -- Economizer Service Analysis PROBLEM Damper Does Not Move. POSSIBLE CAUSE REMEDY Indoor Fan is off. Check for proper thermostat connection. Unit is not configured for continuous fan operation and the thermostat is not calling for heating or cooling. Unit is in Unoccupied mode and there is no call for heating or cooling. Tripped circuit breaker. No power to the unit. Unit is offvia CCN command.
A redLEDisprovided toindicate thefunction oftheboard. Seethetable below. LED STATUS On Continuously Blinking Off REFRIGERANT TEMPERATURES Condenser coil temperatures are measured with 5 kilo-ohin thermistors. These measurelnents provide an approximate saturated condensing telnperature tbr each circuit (SCT.A, SCT.B). Ensure that thermistors are placed at the correct location and axe snapped securely over the return bend so that contact is made between the thermistor and the tube.
Table 48 -- IGC Board LED Alarm Codes LED FLASH CODE DESCRIPTION ACTION TAKEN BY CONTROL RESET METHOD PROBABLE CAUSE -- -- -- -- Loss of power to the IGC Check 5 amp fuse on IGC, )ower to unit, 24V circuit breaker, transformer, and wiring to the IGC.
I I FLASH MOC_FIED - INDOOR (HEA_NG) F/_ D_.AY I 2 _ _C I_ i - OPENING OF UMff INDICATES _ Win-{ 3 FLASHES CLOSED- GAS FLAME VALVE SENSOR I CY_ 4 _ I 4 TIMES ON SINGLE CALL FOR - LIMFF HEAT SW_CH FOR INCO_ MOTORFAULT I 6 FLASNES.INDUCEDDRA_r 8en_x tot 60 second) I 7 FLASHES ROLLOUT - OPESNING SWITCH OF FAN I 8 _ HEAllNG 'Wl' FROM BASE CONTROL ON IGC * 1 MINUTE BOARD ENERGIZES 'W' LOCK-ON COMBUSTION RELAY ON IGC B ENERG_ED 1 IMMEDIATELY 2. DEFEC]/VE 24V TRANS. & _V_RE 4.
adjustments to IAQ and OAQ sensor readings. The space temperature may be COlTectedby entering either a calibration temperature value in SPT.C, or an oit;et temperature value in SPT.Z The supply-air temperature may be corrected by entering either a calibration temperature value in SAT.C, or an oit;et temperature value in SAT.!] Telnperamre corrections should only be made if sensor readings are compared to an accurate reference temperature measurelnent device.
Table 50 -- Temperature (°F) vs ResistanceNoltage Drop Values for OAT, SAT, and SPT Thermistors (10K at 25 C Resistors) TEMP (F) -25 -24 -23 -22 -21 -20 -t9 -t8 -17 -t6 -15 -t4 -13 -t2 -11 -!0 -9 -8 -7 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 2O 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 5O 51 52 53 54 55 56 57 58 59 6O VOLTAGE DROP (V) 4.758 4.750 4.741 4.733 4.724 4.715 4.705 4.696 4.686 4.676 4.665 4.655 4.644 4.633 4.621 4.609 4.
Table 51 -- Temperature (°F) vs. Resistance/Voltage TEMP (F) -25 -24 -23 -22 -21 -20 -19 -18 -17 -16 -15 -14 -13 -12 -11 -10 -9 -8 -7 -6 -5 -4 -3 -2 -t 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 VOLTAGE DROP (v) 3.699 3.689 3.679 3.668 3.658 3.647 3.636 3.624 3.613 3.60I 3.588 3.576 3.563 3.550 3.536 3.523 3.509 3.494 3.480 3.465 3.450 3.434 3.418 3.402 3.386 3.369 3.352 3.335 3.
Table 52 -- Pressure (psig) vs. Voltage Drop Values for Suction Pressure Transducers PRESSURE (psig) 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 62 64 66 MAJOR VOLTAGE DROP (V) 0.465 0.485 0.505 0.524 0.544 0.564 0.583 0.603 0.623 0.642 0.662 0.682 0.702 0.721 0.741 0.761 0.780 0.800 0.820 0.839 0.859 0.879 0.898 0.918 0.938 0.958 0.977 0.997 1.017 1.036 1.056 1.076 1.095 1.
E I! I U) ., 22 E 0 ] 0 11, I o ,m 4,a .=! E o U_ 0 0 I I: 0 .
i i I I L 71
_ ELECIRIC 1 HEAT LAREL OF_3 OF_6 Fig.
I OPTION I!F DEPENDENT _LN SEE 1 _LN<_ LABEL_ FIELDJ TB1 HACR Frqq CSAI _(__YEL CONPA1 (__BLU CA1 DU2 F I CCHNI I _ _ K!>t2N EQUIP GND IFC _BLK PL4 2 _YEL PLV 3 PL4 1 {_BLU IFV YEL 1 %N%N NLRI IRT NLRI OT TPL21 5 OFCI _(_ PL5 3 QT YEL_YEL I_]_BLU-(eYEL@ K P_21 P_2_ P_FAN BRNp_LL _ PLIO YEL_ PL6 3 CONNECT APPROPR[ATE VINE TO UNIT VOLTAGE QT_ _ PL13 __:RENL OPV, ORN YEL_ PL CAP1 ZOM230,460V OFM1 | 2 TNVNI _YEL OFV2 _4 ONLY) YEL OFM5 I_ONLYI CONNECT APPROPRIAT
8 J_ zc ooooo_ bz w w 0 2 o o_ q E o_ 74
E t_ 1t.
RED LED - STATUS GREEN -\ LEN LED (LOCAL YELLOW LED CCN (CARRIER COMFORT EQUIPMENT NETWORK) Z INSTANCE / JUMPER NETWORK) (SET TO 1) STATUS CCN FFFFrmDEB Fm J8 Fig.
RED LED STATUS GREEN LED-LEN (LOCAL EQUIPMENT NETWORK) L- m Fig.
RED LED-STATUS 0 UUUUUU., :4 LH33WPOO2A 1088-12 Fig.
17 I 14 J1O (_ I I J11 RUN TEST I J12 SEPARATION OF CIRCUITS TO EACH 24V TRANSFORMER MUST BE MAINTAINED 1 2 3 4 5 6 7 8 9 10 R Y1 Y2 W1 W2 G C X I......... I 1 T55IFANSTATOSl 1 2 2 3 1 2 LEN Fig.
Scrolling Marquee Display i This device is the keypad interface used to access rooftop information, read sensor values, and test the unit. See Fig. 26. The Scrolling Marquee display is a &key, 4-charactm; 16-segment LED (light-emitting diode) display. Eleven mode LEDs are located on the display as well as an Alarm Status LED. See Scrolling Marquee section on page 2 for further details. Accessory Navigator TM Display i The accessory hand-held Navigator display can be used with the 48/50PG series units.
CCN BUS J ROOFTOP UNIT BUiLDiNG SUPERVISOR NETWORK OPTIONS UNIT ROOFTOP _ UNIT ROOFTOP j._ LEGEND HEATING/COOLING CCN SITE -REMOTE GATEWAY AUTODtAL j UNITS -- CCN CL DAV HVAC ----- TCU -- Carrier Comfort Network@ ComfortLink TM ControIs Digital Air Volume Heating, Ventilation, and Air Conditioning Terminal Control Unit TO ADDITIONAL I _ MINALS I / I ,,Z / I/" EQUIPMENT NON HvAcCARRtER L_ COMFORT CONTROLLER AIR DISTRIBUTiON-DiGITAL AiR VOLUME Fig.
Field-Installed SMOKE DETECTORS The Slnoke detectors are fieldinstalled accessories. These detectors can detect smoke in either the return air (part no. CRSMKDET001D00) or supply and return air (part no. CRSMKSUP001B00). When installing either detectoi; the unit must be configured for tire shutdo,am by setting Configuration-->UNIr-->FS.SW to normally open (1) or nonnalty closed (2). NOTE: When a Humidi-Mizer TM system is installed, the inputs to the fire shutdown are moved to the control harness.
CLEARANCE HOLES FOR (2) #8 MOUNTING SCREWS ON CENTERLINE _ x',x / jr,--,----,=!--_] V 1 CCN COM 328 4.50 , SENSOR WIRING JUMPER _TERMINALS AS SHOWN U j o NOTE: Dimensions are in inches. Fig. :30 -- Space Temperature Sensor _'/ Mounting coo,_ w_._ \, Fig. 32 -- T-56 Space Temperature (PIN 33ZCT56SPT) _X i . Sensor Wiring /.'/ T58 © 2" / S 4\ 5 \ \ \_ _ SENSOR 24 VAC 6 t _ -W-HT-(G-N-D)L', BLKX )_',j _ CCN COM SEN / BLK (GND) ' ' (-) .....
I TB2-T55 I ] RED ,I ] BLK RED RED BLK BLK 7 I I I RED I _I_ r -_ BLK I SENSOR SPACE 1 SENSOR TEMPERATURE AVERAGING RED [] -_ BLK [] BLK I ? U J U TO MAIN BASE BOARD TB2-T55 RED r 2 -- SENSOR3 4 T-55 SENSOR SENSOR4 APPLICATION RED RED BLK BLK I TO MAIN BASE BOARD I SENSOR I SENSOR 2 SENSOR 3 _,Ii2 II LEGEND TB -- ,_ Terminal Block RED RED 4 Factory Wiring Field Wiring _ SENSOR 4 SENSOR _i i_ il = RED BLK SPACE TEMPERATURE BLK 7 SENSOR
SERVICE This will make cleaning eftbrts more difficult. Surfi_ce loaded fibers must be completely removed prior to using low velocity clean water rinse. Periodic Clean Water Rinse A periodic clean water rinse is very beneficial for coils that axe applied in coastal or industrial environruents. However, it is very iruportant that the water rinse is made with very low velocity water streaan to avoid daruaging the tin edges. Monthly cleaning as desca-ibedbelow is recoruruended.
NOTE:DoNOTUSEwaterin excess of 130F,astheenzymaticactivitywillbedestroyed. 5. Thoroughly applyTotaline enviropanentalty scumcoil cleaner solution toallcoilsurfaces including finnedarea, tubesheets andcoilheaders. 6. Holdgarden sprayer nozzle close tofinnedareas andapplycleaner withavertical, up-and-down motion. Avoid spraying in horizontal pattern tominimize potential for findamage. 7. Ensure cleaner thoroughly penetrates deepintofinned areas. 8. Interiorandexterior finnedareas mustbethoroughly cleaned. 9.
2. Cover areain tiontoftheunitservice panel withaterry clothshoptoweltoabsorb lubricant spillsandprevent run-oft;.Towelwilt alsoprotectdropcloth fiomtears caused bytoolsorcomponents. 3. Place terrycloth shoptowelinside theunitdirectly under components tobeserviced toprevent spillsthrough the bottom oftheunit. 4. Perform therequired service. 5. Remove anddispose ofanyoilcontalninated material per localcodes. FANSHAFTBEARINGS Lubricate bearings atleastevery6 lnonths withsuitable bearing _ease.
Evaporator Fan Belt Tension Adjustment -- To adjust belt tension: 1. Turn offunit power. 2. Slide out fan deck to service position as shown in Evaporator Fan Service and Replacement section above. 3. Loosen tan motor bolts. Verify Sensor Performance -- Verit) that thermistor, transducer, and switch inputs (see Tables 50-52) are reading correctly. These values can be accessed through the Scrolling Marquee display in the Temperatures, Pressures, and Inputs menus.
TO USE THE COOLING CHARGING CHART, STANDARD UNITS Use the above temperature and pressure readings, and find the intersection point on the cooling chaNing chart. If intersection point on chart is above line, add refiigerant. If intersection point on chart is below line, carefully recover some of the charge. Recheck suction pressure as charge is adjusted.
Recovery cylinder service pressure rating must be 400 psig. Puron systems should be charged with liquid refiigerant. Use a comlnercial-type metering device in the manifold hose. Manifold sets should be 750 psig high-side and 200 psig low-side with 520 psig tow-side retard. Use hoses with 750 psig selwice pressure rating. Leak detectors should be designed to detect HFC refiigerant.
10. Lift bumer/mmlifold assembly out of unit. CLEANING AND ADJUSTMENT 1. Relnove burner rack tiom unit as descTibed in Main Burner Relnoval section above. Main Burners (48PG Only) -- For all applications, main burners are ti_ctory set and should require no adjustment. MAIN BURNER REMOVAL 1. Shut off (field-supplied) lnanual main gas vatve. 2. 3. 4. 5. 6. 2. Inspect burners, and if dirty, remove burners tiom rack. 3. Using a soft brush, clean burners and crossover port as required. 4. Adjust spark gap.
Filter Drier -- Replace whenever ref-igerant system is exposed to atmosphere. Only use factory specified liquid-line tilter driers with working pressures no less than 650 psig. Do not install a suction-line ftter drier in liquid line. A liquid-line flter drier designed for use with Puron,_R)refi-igerant is required for ca& circuit. Fuses are also located in the control box and teed power to the condenser fan motors. Always replace blown fuses with the correct size fuse as indicated on the unit fuse label.
APPENDIX A--LOCAL DISPLAY AND CCN TABLES MODE -- RUN STATUS ITEM RUN STATUS VIEW HVAC OCC SAT ALRM TIME EXPANSION CCN TABLE/ SUB-TABLE UNITS STATUS Auto View of Run Status HVAC Mode Status VERS MBB ECB MARQ Currently Occupied Supply Air Temperature Current Alarms &Aterts Time of Day Software Version Numbers CESR131320-xx-xx CESR131249-xx-xx CESR131171-xx-xx HRS A1 A2 B1 CI CCH IDF OFC,1 OFC,2 OFC.3 HT,1 HT,2 PE,1 PE,2 ALRM CRC RH2,A RH2.
APPENDIX ITEM RUN STATUS (cont) COOL (cont) CIR.B CMP, B TG.B CS,B1 RH2.B SST.B SSP.B SCT.B SCP.B CIR,C CMP, C TG.C1 CS.C1 RH2.C SST.C SSP.C SCT.C SCP.C HEAT DMD.H AVL.H REQ.H IDF HT.1 TG.H1 HT.2 TG.H2 ECON EC.CP EC.AP EC.MP IAQ.S IAQ OAT ENTH OAQ PE,1 PE.2 (LON_DATA = CCN only) A -- LOCAL MODE- DISPLAY AND CCN TABLES RUN STATUS (cont) EXPANSION Refrigerant Circuit B Compressors B Timeguard B Compressor B1 Feedback Reheat2 Valve B,C Sat. Suction Temp B Suction Pressure B Sat.
APPENDIX A -- LOCAL DISPLAY AND CCN TABLES (cont) MODE -- SERVICE TEST ITEM SERVICE TEST TES T EXPANSION RANGE UNITS CCN TABLE/ SUB-TABLE DEFAULT MAINTENANCE Field Service Test Mode On/Off Test Independent Outputs Economizer Position Test Calibrate Economizer Power Exhaust 1 Test Power Exhaust 2 Test Atarm Relay Test Crankcase Heat Test 0 to 100 On/Off On/Off On/Off On/Off On/Off FANS IDF OFC.1 OFC.2 OFC.
APPENDIX A -- LOCAL DISPLAY AND CCN TABLES (cont) MODE -- SET POINTS DISPLAY MENU/ SUB-MENU/NAME EXPANDED NAME VALUES UNITS CCNTABLE/ SUB-TABLE DEFAULT SETPOINT SETPOINTS OCSP UCSP OHSP UHSP GAP STO.R RH. SP RH. DB RH. HB CA.LO CB.
APPENDIX ITEM CONFIGURATION DISP EXPANSION LOCAL DISPLAY AND CCN TABLES MODE -- CONFIGURATION RANGE UNITS DEFAULT Display Configuration Metric Display Language Selection PROT PSWD TEST Password Enab]e Service Password Test Display LEDs (cont) CCN TABLEISUB-TABLE SERVICE METR LANG UNIT S.DLY U.CTL A -- CCN POINT PAGE NO.
APPENDIX A -- LOCAL DISPLAY AND CCN TABLES MODE -- CONFIGURATION ITEM CONFIGURATION EXPANSION I RANGE UNITS (cont) (cont) DEFAULT CCN TABLE/SUB=TABLE CCN POINT PAGE NO. (cont) COOL (cont) CIR, B CS,B1 BI .FN Circuit B B1 Current Sensing B Circuit Level 1 Fans Enable/Disable 0 to 7 B2,FN B Circuit Level 2 Fans 0 to 7 B3,FN B Circuit Level 3 Fans Oto 7 CIR.C CS,C1 C1.
APPENDIX ITEM CONFIGURATION I A -- LOCAL DISPLAY AND CCN TABLES MODE -- CONFIGURATION (cont) RANGE EXPANSION UNITS DEFAULT (cont) CCN TABLE/SUB-TABLE CCN POINT PAGE NO. (cont) HMZR REHT HumJdimizer Humidimizer Config Equipped HMZR CFG Yes/No R, DEC R.INC RH.FN RF, LV R_ON Reheat2 Stage Decr Time Reheat2 Stage _ncr. Time Reheat Fan Control Reheat20DP Fan On Level Reheat20DF Fan On Tamp O to 999 O to 999 Yes/No 0to3 O to 100 secs secs R,_OF Reheat20DF O to 100 F RA.LO RA.LR RA.HP RB.
APPENDIX ITEM CONFIGURATION I A -- LOCAL DISPLAY AND CCN TABLES MODE -- CONFIGURATION (cont) RANGE EXPANSION UNITS DEFAULT (cont) CCN TABLE/SUB=TABLE CCN POINT PAGE NO. (cont) AIR.Q IA.CF Air Quality Configuration IAQ Analog input Config IAQ_CFG IA.FN IAQ Analog ILCF IAQ Switch Input Config ILFN IAQ Switch Fan Config AQ.MN EC.MN OVR.P OA.CF Econo Min IAQ Position Econo Minimum Position IAQ Override Position OAQ Analog Input Cfg OAQ.L AQD.L AQD.H DF.ON DF.OF 1.4M 1.20M O.4M O.
APPENDIX LOCAL DISPLAY AND CCN TABLES MODE -- TIME CLOCK EXPANSION ITEM TIME CLOCK TIME TiME DATE MNTH DOM YEAR DAY A -- RANGE UNITS DEFAULT (cont) CCN POINT CCN TABLE/ SUB-TABLE CONFIGURATION Time of Day Hour and Minute Current Date Month of Year Day of Month Year Day of Week DST Daylight Savings Config Daylight Savings Start: Start Month Start Week Start Day Minutes to Add Daylight Savings Stop: Stop Month Stop Week Stop Day Minutes to Subtract STR.M STR.W STR.D M.ADD STP.M STP.W STP.D M.
APPENDIX ITEM OPERATING MODE SYS HVAC OCC T.OVR LINK C.LOC H.LOC E.LOC A -- LOCAL DISPLAY AND CCN TABLES MODE -- OPERATING MODES EXPANSION RANGE CCN TABLE/ SUB-TABLE UNITS MODES MAINTENANCE Control Modes System Mode HVAC Mode Linkage Active Comp Cool OAT Lockout Heat OAT Lockout Econ Coo{ OAT Lockout COOL COOL OK.CL MS.TG OK.EC OK.MC C.LOC CA.LO CB.LO CC.LO AVL.C REQ.C ACT.C CMP.A CMP.B CMP.C ST, A ST, B ST, C RLEV SAT SAT SA,DM SA,PD SA,ND SAT, U SAT, L SA,TR SA,DR SPT SPT DMD.C TRD.C CL.
APPENDIX ITEM OPERATING ECON EC,EN EXPANSION MODES RANGE Economizer Economizer MAINTENANCE ECONDIAG Diagnostic InstaNed Currently Occupied Indoor Fan Relay In Cooling Mode? Econo Cool OAT Lockout Econo Cool Hi Temp Limit Econo Cool Lo Temp Limit Free Cool Low Temp Limit Econo Cool Entb Lockout Econo Cool Max Position Econo Minimum Position IAQ DCV Mode Econo Min IAQ Position IAQ Override Mode IAQ Ovedde Position OAQ Lockout Mode OAQ Lockout Limit Lo Refrig Press Override Econo Commanded Position Eco
APPENDIX HUMIDI-MIZER B -TM CONTROL MODES WITH SYSTEM AND ECONOMIZER Thermostat input shown tbr cooling demand (versus temperature sensor and set point). Humidistat input shown for dehumidification demand (versus relative humidity sensor and set point). Economizer cooling availability is dependent on outdoor temperature or enthalpy.
Copyright 2006 Carrier Corporation Manufacturer reserves the right to discontinue, Catalog No. 04-53480028-01 or change at any time, specifications or designs Printed in US.A. Form 48/50PG-5T without notice and without Pg 106 6-06 incurring obligations.
CONTROL SET POINT AND CONFIGURATION Model Number: Serial Number: Date: Technician: So.rare Versions: MBB: CESR131320-ECB: CESR131249-MARQ: INDICATE Control Type: Set Points: LOG Thermostat Cooling Heating CESR131171-- UNIT SETTINGS BELOW / T-55 Space Temp. / T-56 Space Temp. / T-58 Space Temp. Occupied: Unoccupied: Occupied: Unoccupied: MODE -- CONFIGURATION ITEM CONFIGURATION DISP METR LANG PROT PSWD TEST UNIT S.DLY U.
MODE -- CONFIGURATION ITEM CONFiGURATiON (cont) COOL (cont) SAT SA.PD SA.ND SAT,U SAT,L SPT CLPD CLND C.LAG CIR.A CS.AI CS,A2 A!,FN I EXPANSION Supply Air Temperature SAT Cool Demand (+) Level SAT Cool Demand (-) Level Minimum SAT Upper Level Minimum SAT Lower Level Space Temperature SPT Cool Demand (+) Level SPT Cool Demand (-) Level Cool Thermal Lag Factor Circuit A A1 Current Sensing A2 Current Sensing A Circuit Level 1 Fans (cont) RANGE 0.5 to 10 AF --I0 to --0.5 ^F 35.0 to 65.0 dF 35.0 to 65.
MODE -- CONFIGURATION ITEM CONFIGURATION OFC (cont) 3.OFF I (cont) RANGE EXPANSION DEFAULT (cont) HMZR REHT Fan Lev3 Off Temperature 0 to 100 F no Humidi-MiZer FLOP: 55 Humidi-MiZer FLOP: 78 (2O) 62 (24) 62 (28) Humidimizer Humidimizer Yes/No Config Equipped Reheat2 Stage Decr. Time Reheat2 Stage Incr. Time Reheat Fan Control Reheat20DF Fan On Level Reheat20DF Fan On Temp 0 to 999 secs No: no Humidi-MiZer FlOP Yes: Humidi-MiZer FlOP 6O 0 to 999 secs Yes/No 0to 3 300 Yes 2 0 to 100 F RF.
MODE -- CONFIGURATION ITEM CONFIGURATION ECON (cont) FC.TM FC.LO PE,EN PE.1 PE,2 EN.SW E,TRV E,MXB E,MXM E,MXT E,DBD EC,P EC,I EC,D EC.DT AIR.
MODE -- CONFIGURATION ITEM CONFIGURATION TRIM SPT.C SPT.T SAT.C SAT.T RAT.C RAT.T CCN CCN.A CCN,B BAUD BROD B.TIM B,OAT B.GS B,ACK SCH.O SCH.N HOL.G OV.TL OV. EX OV.SP I (cont) RANGE EXPANSION Sensor Calibration Space Temp Calibration Space Temp Trim Supply Air Temp Calib. Supply Air Temp Trim Return Air Temp Calib.
UNIT START-UP CHECKLIST MODEL NO.: SERIAL NO.: DATE: TECHNICIAN: I.