Specifications

CRLPKIT1004A00
Installation Instructions
48PD05---06, 48PG03---14
Gas Heating/Electric Cooling
Single Package Rooftop Units
LP (Liqui d Propane ) Gas Conversion Kit Accessory
LP GAS CONVERSION KIT USAGE AND CONTENTS
ACCESSORY PART NO. USAGE CONTENTS
CRLPKIT1004A00
48PG03-14
48PD05---06
11 Burner Orifices, Drill Size No. 50, 0.070 in.
11 Burner Orifices, Drill Size No. 51, 0.067 in.
11 Burner Orifices, Drill Size No. 52, 0.065 in.
8 Burner Orifices, Dril l Size No. 53, 0.060 in.
1LPConversionPlate
1 LP Conversion Responsibility Label
1 Warning Label
SAFETY CONSIDERATIONS
Installation and servicing of air--conditioning equipment can be
hazardous due to system pressure and electrical components. Only
trained and qualified service personnel should install, repair, or ser-
vice air--conditioning equipment.
When working on equipment, observe precautions in the literature,
tags and labels attached to the unit, and other safety precautions
that may apply.
Follow all safety codes. Wear safety glasses and work gloves.
Recognize safety information. This is the safety--alert symbol
.
When you see this symbol on the unit and in instructions or manu-
als, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and CAU-
TION. These words are used with the safety--alert symbol. DAN-
GER identifies the most serious hazards which will result in severe
personal injury or death. WARNING signifies a hazard which
could result in personal injury or death. CAUTION is used to iden-
tify unsafe practices which may result in minor personal injury or
product and property damage. NOTE is used to highlight sugges-
tions which will result in enhanced installation, reliability, or opera-
tion.
ELECTRICAL SHOCK, FIRE AND EXPLOSION
HAZARD
Failure to follow this warning could result in personal injury,
death or property damage.
Before beginning any modification, close main supply shutoff
valve. Be certain that the main line electrical disconnect switch
is in the OFF position and lockout tag is installed. Tag
disconnect switch and gas valve with suitable warning labels.
!
WARNING
ELECTRICAL SHOCK, FIRE AND EXPLOSION
HAZARD
Failure to follow this warning could result in personal injury
or death.
This unit is designed to operate at 3.5--in. wg (± 0.3 in.wg)
manifold pressure in high fire with LP gas. Exceeding this
pressure will cause explosion or injury.
!
WARNING
GENERAL
The LP Conversion Kit allows the unit to utilize a liquid propane
fuel supply in areas where natural gas is not available. The kit may
be used at elevations as high as 7000 ft.
For higher elevations, an accessory high altitude kit is
required.
IMPORTANT: The Accessory LP Conversion is not for use with
Low NOx units. If Low NOx units are converted to LP gas, the
Low NOx baffle must be removed. The units will no longer be
classified as Low NOx units. Use the LP Conversion Kit with
standard units only.
The Gas Input (Btuh) values will be affected by the change in
orifice sizes. (See Table 1.)