38GVM / 40GVM Multi---Split High---Wall Ductless Split System 38GVM --- Size 18k, 24k, 30k, 36k and 42k 40GVM --- Size 9k, 12k, and 18k Product Data INDUSTRY LEADING FEATURES / BENEFITS AN INEXPENSIVE AND CREATIVE SOLUTION TO DESIGN PROBLEMS. The 38GVM/40GVM ductless inverter driven multi--split system provides individual comfort control for up to 5 separate zones. Two, three, four or five space--saving High Wall ductless fan coils are matched with one outdoor heat pump.
38/40GVM INVERTER TECHNOLOGY - COMFORT FAST INSTALLATION The inverter driven compressor is designed to run at various input power frequencies (Hz) which controls the motor speed of the compressor. Even Temperature – The control package, including the inverter, monitors outdoor and indoor temperatures as they relate to the selected indoor set point and adjusts the speed of the compressor to match the load and keep the system operating continuously rather than cycling and creating temperature swings.
MODEL NUMBER NOMENCLATURE INDOOR UNIT 40 GVM 009 3 --- --- --- Voltage 3 --- 208/230 ---1 ---60 Fan Coil Unit Nominal Capacity 009 --- 3/4 Ton 012 --- 1 Ton 018 --- 1 ---1/2 Ton 38/40GVM Unit Type GVM --- Multi High Wall OUTDOOR UNIT 38 GVM 2 18 --- --- --- 3 Voltage 3 --- 208/230 ---1 ---60 Outdoor Unit Unit Type GVM --- Heat Pump Nominal Capacity 18 --- 1 ---1/2 Tons 24 --- 2 Tons 30 --- 2 ---1/2 Tons 36 --- 3 Tons 42 --- 3 ---1/2 Tons Number of Ports 2 --- Ports 3 --- Ports 4 --- Por
38/40GVM STANDARD FEATURES AND ACCESSORIES Ease of Installation Mounting Bracket Low Voltage Controls Comfort Features Microprocessor Control Wireless Remote Control Rapid Cooling and Heating Automatic Air Sweep Cold Blow Prevention Continuous Fan Auto Restart Function Auto Changeover Energy Saving Features Inverter Driven Compressor Sleep Mode 24 Hour Stop/Start Timer Safety And Reliability Indoor Unit Freeze Protection 3 Minute Compressor Time Delay High Compressor Discharge Temperature Low Voltage Prote
DIMENSIONS -- INDOOR H D W A08289 Unit Size 9k 12k 18k W In. (mm) 33.3 (846) 33.3 (846) 37.0 (940) H In. (mm) 10.7 (272) 10.7 (272) 11.7 (297) D In. (mm) 7.1 (180) 7.1 (180) 7.9 (201) Net Operating Weight Lbs. (Kg) 22.0 (10) 22.0 (10) 29.0 (13) 38/40GVM Fig. 2 – Indoor Unit Dimensions DIMENSIONS - OUTDOOR 12.4 (316) 35.4 (899) 14.4 (378) 23.5 (596) 32.1 (815) 13.5 (343) 21.7 (550) Unit: in. (mm) A12552 Fig.
DIMENSIONS - OUTDOOR (CONTINUED) 13.4 (341) 37.2 (946) 15.6 (396) 38/40GVM 27.6 (700) 35.1 (892) 14.5 (368) 22.0 (560) Unit: in. (mm) A12553 Fig. 4 – 38GVM024/030 024 Weight, lb (kg): Gross -- 146 (66.2) / Net -- 135 (61.2) 030 Weight, lb (kg): Gross -- 148 (67.1) / Net -- 137 (62.1) 39.1 (994) 24.0 (610) 6.0 (153) 14.6 (370) 7.0 3.0 (177) (76) 16.8 (427) 15.6 (395) 3.8 (96) 13.8 (350) 31.1 (789) 36.2 (920) Unit: in. (mm) A12554 Fig.
DIMENSIONS - OUTDOOR (CONTINUED) 42.8 (1087) 7.5 (191) 24.8 (631) 38/40GVM 14.3 (362) 4.8 3.0 (121) (76) 17.3 (440) 15.8 (401) 3.9 (99) 17.7 (450) 43.4 (1103) 40.0 (1015) Unit: in. (mm) A12555 Fig. 6 – 38GVM042 Weight, lb (kg): Gross -- 247 (112.3) / Net -- 225 (102.3) CLEARANCES -- INDOOR CEILING 6" (0.15m) min. 5" (0.13m) min. 5" (0.13m) min. 6' (1.8m) FLOOR A07891 Fig.
CLEARANCES - OUTDOOR 20 (508) minimum space above top of unit 11.8 (300) minimum space on air inlet side 38/40GVM 11.8 (300) minimum distance from wall 24.0 (610) minimum space on service valve side 78 (2000) minimum space in front of air outlet Unit: in. (mm) A112556 Fig. 8 – 38GVM018, 024, 030 40 (1000) minimum space above top of unit 19.7 (500) minimum space on air inlet side 19.7 (500) minimum distance from wall 24.
PHYSICAL DATA -- 38GVM Outdoor Unit 38GVM 218 324 430 System Voltage Control Voltage Rated Cooling Capacity (Btuh) Cooling Cap. Range Min --- Max Btuh Rated Heating Capacity (Btuh) Heating Cap.
PHYSICAL DATA -- 40GVM 38/40GVM Indoor Unit 40GVM System Voltage Control Voltage Electrical Connections Nominal Cooling Capacity (Btuh) Nominal Heating Capacity (Btuh) Operating Weight lb (kg) Refrigerant Type Metering Device (At Outdoor Unit) Moisture Removal Rate (pints/hr) Indoor Fan RPM/CFM (Super High) --- Cooling RPM/CFM (High) --- Cooling RPM/CFM (Medium) --- Cooling RPM/CFM (Low) --- Cooling RPM/CFM (Super High) --- Heating RPM/CFM (High) --- Heating RPM/CFM (Medium) --- Heating RPM/CFM (Low) ---
APPLICATION DATA UNIT SELECTION Outdoor Unit Model The commercial application will tend to be more steady during the normal day time hours, and will go to low load levels after normal business hours. If it is anticipated that the system will be required to run at the maximum load point for the majority of the time, the next larger system capacity should be selected. The tables below are guidelines for selecting the proper size for the application.
APPLICATION DATA CONTINUED Outdoor Unit Model Cooling Capacity (Btu/h) 38GVM436 9K + 9K Zone 2 11,089 12,283 11,089 11,089 16,719 9,758 21,734 10,236 10,236 13,307 13,307 12K + 18K 10,577 13,648 12,693 16,378 18K + 18K 13,648 13,648 16,378 16,378 9K + 9K + 9K 8,189 8,189 8,189 9,008 9,008 9,008 9K + 9K + 12K 6,995 7,336 10,236 7,694 8,069 11,260 9K + 18K 12K + 12K 8,530 7,506 Zone 3 Zone 4 Zone 5 Zone 3 Zone 4 9K + 9K + 18K 7,165 7,165 15,354 8,598 8,598 18
UNIT MOUNTING (INDOOR) METERING DEVICES Mounting Bracket – The fan coil units are furnished with mounting bracket to hang the unit. Support – Adequate support must be provided to handle the weight of all fan coils. Refer to the Physical Data section for weights, and the base unit dimensional drawings. Unit Leveling – For reliable operation, units should be level in all planes. Clearances – Minimum clearance as shown in Fig. 7.
DRAIN CONNECTIONS Install drains to meet the local sanitation codes. If adequate gravity drainage cannot be provided, a field installed condensate pump accessory should be used. Refer to the Installation Instructions of the condensate pump for detailed specifications. NOTE: The high wall fan coils have internal condensate trap. An external trap is not required. Drain connections may be routed through alternate locations as shown in Fig. 11.
AIR THROW DATA Model Number Approximate Air Throw ft. (m) Medium High Low 40GVM009 --- --- ---3 40GVM012 --- --- ---3 40GVM018 --- --- ---3 18 (5.5) 19 (5.8) 25 (7.6) 21 (6.4) 21 (6.4) 29 (8.8) Turbo 24 (7.3) 24 (7.3) 32 (9.8) 27 (8.2) 27 (8.2) 35 (10.7) SOUND RATINGS Outdoor Units Sound Power dBA 66/66 66/66 66/66 69/69 68/68 Sound Pressure dBA 56/56 56/56 56/56 59/59 58/58 Indoor Units Low Sound Power dBA 36.0 38.0 45.
GUIDE SPECIFICATIONS HORIZONTAL DISCHARGE OUTDOOR UNITS Size Range:1--1/2, 2, 2--1/2, 3 and 3--1/2 Ton Nominal Cooling and Heating Capacity Carrier Model Number: 38GVM PART 1 – GENERAL 38/40GVM 1.01 System Description A. Outdoor air--cooled split system compressor sections suitable for on--the--ground, rooftop, wall hung or balcony mounting.
GUIDE SPECIFICATIONS INDOOR WALL--MOUNTED DUCT--FREE UNITS Size Range: 3/4, 1 and 1--1/2 Ton Nominal Cooling and Heating Capacity Carrier Model Number: 40GVM 1.01 System Description Indoor, wall-mounted, direct expansion fan coils are matched with heat pump outdoor units. 1.02 Agency Listings Unit shall be rated per AHRI Standards 210/240 and listed in the AHRI directory as a matched system. 1.
38/40GVM Copyright 2013 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231 Edition Date: 07/13 Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 18 Catalog No.