Heating System User Manual

UNIT SIZE
48MPD,E
WEIGHT A B C D E F
lb kg mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in.
62L 16,810 7624 3505 11- 6 957 3-1
11
16
5909 19-4
5
8
1203 3-11
3
8
13 011 42-8
1
4
14 256 46-9
1
4
70M 18,060 8190 3647 11-11
9
16
1165 3-9
7
8
6166 20-2
3
4
1264 4- 1
3
4
13 297 43-7
1
2
14 542 47-8
1
2
NOTES:
1. Dimensions in [ ] are in millimeters.
2. Center of gravity includes exhaust fan and high heat options. Unit weight does not include exhaust fan or high
heat options.
3. High heat add: 260 lb [118 kg]
Exhaust fan add: 1675 lb [761 kg] on 62L
1775 lb [807 kg] on 70M
4. Unit clearances:
Top Do not restrict condenser fans, control box end 68-09.
Sides 68-09 (except on return fan equipped units 108-09).
Economizer end 68-09 (except power exhaust units 108-09).
For smaller service and operational clearances, contact Carrier Application Engineering Department.
5. Downshot ducts designed to be attached to accessory roof curb. If unit is mounted on dunnage, it is recommended
the ducts be supported by cross braces as done on the accessory roof curb.
Fig. 3 Base Unit Dimensions, 48MP62L, 70M