Specifications

9
Table 4 — Additional Analog Inputs
LEGEND
Table 5 — Main Base Board and Economizer Control Board Outputs
LEGEND
Table 6 — CCN Communication Bus Wiring
INPUT
PIN
CONNECTION
POINT
TERMINAL
CONNECTION
POINT
COMMENT
T55
Space Temperature (SPT)
J8 1,2 (MBB) TB3 7,8 Part No. = CEC0121448-01
T56
Space Temperature (SPT) and Space
Temperature Offset (SPTO)
J8 1,2,3 (MBB) TB3 7,8,9 Part No. = CEC0121503-01
Indoor Air Quality (IAQ)
J5 2,3 (ECB) TB5 2,3
Outdoor Air Quality (OAQ)
J5 3,5 (ECB) TB5 3,4
ECB
Economizer Control Board
MBB
Main Base Board
OUTPUT
PIN
CONNECTION
POINT
DESCRIPTION
C.A1
J10 11 (MBB) First compressor of Circuit A
C.B1
J10 9 (MBB) First compressor of Circuit B
C.C1
J10 6 (MBB) First compressor of Circuit C
IFC
J10 21 (MBB) Request for indoor fan. IGC controls the Indoor Fan Motor (48HG only)
Fan Power
J10 3 (MBB) Allows indoor fan to operate
OFC1
J10 19 (MBB) Controls outdoor fan motor 1
OFC2
J10 16 (MBB) Controls outdoor fan motor 3 and 6 (also 2 and 5 on size 028 units)
OFC3
J10 13 (MBB) Controls outdoor fan motor 4
W1
J10 27 (MBB) Request for first stage of heating. IGC controls heating (48HG only).
W2
J10 25 (MBB) Second stage of heating.
ALARM
J10 23 (MBB) TB4 7,8
Economizer Power
J8 18 (ECB) ECB can turn off the power to the actuator
Economizer Control Signal
J7 1, 3 (ECB) Belimo Communication Protocol
PE_1
J8 3 (ECB) Power Exhaust Motor No. 1
PE_2
J8 6 (ECB) Power Exhaust Motor No. 2
ECB
Economizer Control Board
IFC
Indoor-Fan Contactor
IGC
Integrated Gas Controller
MBB
Main Base Board
OFC
Outdoor-Fan Contactor
MANUFACTURER
PART N O.
Regular Wiring Plenum Wiring
Alpha
1895
American
A21451 A48301
Belden
8205 884421
Columbia
D6451
Manhattan
M13402 M64430
Quabik
6130
Run Status
Service Test
Temperature
Pressures
Setpoints
Inputs
Outputs
Configuration
Time Clock
Operating Modes
Alarms
Alarm Status
ENTER
MODE
ESCAPE
Fig. 7 Scrolling
Comfort
Link Display