Duct Split System Data Sheet
14
AIR FLOW DATA
System size 9 12 18 24 36 48
Indoor (CFM)
High 380 380 480 810 1180 1470
Medium 340 340 440 650 940 1180
Low 290 290 400 590 680 940
Outdoor (CFM) 945 945 1050 1390 2940 4240
SOUND PRESSURE
System size 9 12 18 24 36 48
Cooling operation Indoor Sound
Pressure
dBa (L/M/H) 30/33/36 30/34/38 34/37/38 43/45/48 46/50/52 41/44/46
Heating operation Indoor Sound
Pressure
dBa (L/M/H) 30/33/36 30/34/38 34/37/39 44/45/48 46/49/51 40/43/45
Outdoor sound pressure level dBa 55.5 56 59 62 65 65
SOUND POWER
System size 9 12 18 24 36 48
Cooling operation Indoor Sound Power dBa (L/M/H) 39/42/45 39/43/47 43/46/48 53/55/58 56/60/62 51/54/56
Heating operation Indoor Sound Power dBa (L/M/H) 39/42/45 39/43/47 43/46/48 54/55/58 56/59/61 50/53/55
Outdoor sound power level dBa 65 66 69 72 75 75
ELECTRICAL DATA
UNIT
SIZE
OPER. VOLTAGE
MAX / MIN*
COMPRESSOR OUTDOOR FAN INDOOR FAN MCA
MAX FUSE
CB AMP
253 / 187
V-PH-HZ RLA V-PH-HZ FLA HP W V-PH-HZ FLA HP W
9
208-230/1/60
5.3
208-230/1/60
3 0.053 40
208-230/1/60
1.03 0.07 55
15 15
12 5.7
3 0.053 40 1.03 0.07 55
15 15
18 7.3
3 0.067 50 0.83 0.12 90
15 20
24 8.8
3 0.16 120 0.83 0.12 90
15 25
36 13.5
3 0.16 120 1.263 0.2 150
30 50
48 13.4
3 0.11 85 2.23 0.32 240
35 55
*Permissible limits of the voltage range at which the unit will operate satisfactorily .
LEGEND
FLA - Full Load Amps
LRA - Locked Rotor Amps
MCA - Minimum Circuit Amps
RLA - Rated Load Amps