Duct Split System Data Sheet

10
HEATING PERFORMANCE DATA
Model
Heating Outdoor conditions (DB)
Indoor Conditions DB 53.6F(12C) 44.6F(7C) 39.2F(4C) 32F(0C) 24.8F(-4C) 19.4F(-7C) 17F(-8C) 5F(-15C)
9
59F(15C)
TH 11.18 11.08 10.89 10.65 9.87 9.11 8.27 6.71
Input 0.73 0.79 1.04 1.01 0.96 0.9 0.84 0.8
64.4F(18C)
TH 11.06 10.82 10.65 10.54 9.63 8.84 8.01 5.46
Input 0.78 0.8 1.08 1.03 0.98 0.94 0.9 0.82
69F(20.5C)
TH 10.84 10.55 10.48 10.32 9.43 8.55 7.95 4.29
Input 0.8 0.81 1.11 1.05 1 0.98 0.96 0.84
71.6F(22C)
TH 10.62 10.32 10.21 10.11 9.23 8.41 7.89 4.11
Input 0.82 0.83 1.15 1.07 1.02 1.02 0.92 0.86
12
59F(15C)
TH 11.78 12.72 12.42 11.32 10.4 9.54 8.9 5.75
Input 0.79 1.01 1.05 1.1 1.02 1 0.98 0.83
64.4F(18C)
TH 12.05 12.65 12.32 11.34 10.3 9.32 8.81 6.14
Input 0.83 1.37 1.4 1.26 1.22 1.27 1.01 0.91
69F(20.5C)
TH 12.27 12.6 12.12 11.32 10.2 9.12 8.43 6.49
Input 0.83 1.1 1.12 1.19 1.19 1.25 1.03 0.98
71.6F(22C)
TH 11.14 12.41 12.01 11.21 10 9.02 8.21 6.01
Input 0.85 1.15 1.16 1.21 1.23 1.31 1.05 1
18
59F(15C)
TH 23.16 20.54 19.42 17.56 16.5 14.28 12.08 9.39
Input 1.58 1.49 1.48 1.58 1.46 1.4 1.35 1.21
64.4F(18C)
TH 22.41 20.08 18.66 16.89 16.1 13.94 12.06 9.16
Input 1.62 1.55 1.55 1.61 1.52 1.45 1.4 1.29
69F(20.5C)
TH 21.71 19.67 17.93 16.26 15.6 13.62 12.07 8.95
Input 1.67 1.62 1.63 1.65 1.58 1.5 1.45 1.38
71.6F(22C)
TH 21.01 18.97 17.23 15.56 14.9 12.92 11.37 8.25
Input 1.72 1.67 1.68 1.7 1.63 1.55 1.5 1.43
24
59F(15C)
TH 28.6 27.79 25.85 23.56 23.4 23.22 23.16 18.93
Input 2 2.25 2.24 2.21 2.2 2.23 2.24 2.17
64.4F(18C)
TH 27.62 27.61 24.52 23.54 23.4 22.52 20.45 17.45
Input 2.24 2.45 2.35 2.35 2.32 2.23 2.21 2.16
69F(20.5C)
TH 29.09 29.25 26.75 24.63 23 21.85 19.61 16.38
Input 2.39 2.74 2.64 2.58 2.42 2.25 2.2 2.18
71.6F(22C)
TH 26.87 27.52 24.21 23.41 22.5 21.67 19.54 16.24
Input 2 2.25 2.24 2.21 2.2 2.23 2.24 2.17
36
59F(15C)
TH 51.98 50.41 44.98 37.74 36.3 35.22 34.87 27.92
Input 3.85 4.31 4.09 3.83 3.89 3.94 3.95 3.71
64.4F(18C)
TH 49.72 49.76 45.75 40.41 36.9 34.3 33.43 26.79
Input 3.83 4.53 4.36 4.16 4.01 3.9 3.87 3.6
69F(20.5C)
TH 47.47 49.1 46.52 43.08 37.5 33.38 32 25.66
Input 3.82 4.76 4.64 4.49 4.14 3.88 3.8 3.49
71.6F(22C)
TH 46.56 48.84 46.82 44.14 37.8 33.01 31.42 25.2
Input 3.81 4.85 4.74 4.62 4.19 3.87 3.76 3.44
48
59F(15C)
TH 58.98 58.14 53.9 48.25 36.7 35.34 34.38 28.09
Input 4.33 4.89 4.9 4.9 4.43 4.46 4.46 4.13
64.4F(18C)
TH 56.5 53.86 51.15 47.54 37.1 34.77 33.57 27.45
Input 4.51 4.72 4.87 5.06 4.7 4.6 4.57 4.23
69F(20.5C)
TH 54.39 50.22 48.81 46.94 37.4 34.27 32.89 26.91
Input 4.67 4.57 4.84 5.2 4.93 4.72 4.66 4.31
71.6F(22C)
TH 53.19 48.16 47.48 46.59 37.6 33.98 32.5 26.6
Input 4.75 4.48 4.82 5.27 5.05 4.78 4.71 4.35
LEGEND
DB - Dry Bulb
TH - Total Net Heating C a pacity (1000 Btu/hour)
Input - T otal Power (kW)