Cassette Ductless Data Sheet
14
AIR FLOW DATA
SYSTEM SIZE
CASSETTE
9K 12K 18K
HIGH 380 400 420
MEDIUM 320 340 350
LOW 260 280 290
OUTDOOR (CFM) 945 945 1050
SOUND PRESSURE
SYSTEM SIZE
CASSETTE
9K 12K 18K
Cooling operation Indoor Sound Pressure dBa (L/M/H) 34/39/44 36/39/42 46/48/50
Cooling operation Indoor Sound Pressure dBa (L/M/H) 31/37/42 37/39/42 46/47/49
Outdoor sound pressure level dBa 55.5 56 59
SOUND POWER
SYSTEM SIZE
CASSETTE
9K 12K 18K
Cooling operation Indoor Sound Power dBa (L/M/H) 43/48/53 45/48/51 56/58/60
Heating operation Indoor Sound Power dBa (L/M/H) 40/48/51 46/48/51 56/57/59
Outdoor sound power level dBa 65 66 69
ELECTRICAL DATA
UNIT
SIZE
OPER. VOLTAGE MAX / MIN* COMPRESSOR OUTDOOR FAN INDOOR FAN MCA
MAXFUSECB
AMP
V-PH-HZ RLA V-PH-HZ FLA HP W V-PH-HZ FLA HP W
9K
253 / 187
208-230/1/60
5.3
208-230/1/60
3.0 0.053 40
208-230/1/60
0.146 0.061 46 15 15
12K 5.7 3.0 0.053 40 0.146 0.061 46 15 15
18K 7.3 3.0 0.067 50 0.146 0.061 46 15 20
*Permissible limits of the voltage range at which the unit will operate satis factorily
LEGEND
FLA - Full Load Amps
MCA - Minimum C ircuit Amps
RLA - Rated Load Amps