Spec Sheet

12
AIR FLOW DATA
SYSTEM SIZE
9K 12K 9K 12K 18K 24K 30K
(115V) (115V) (208-230V) (208-230V) (208-230V) (208-230V) (208-230V)
Indoor (CFM)
Turbo 380 380 380 380 680 870 870
High 360 360 360 360 650 780 780
Medium 290 300 290 300 450 620 620
Low 210 210 210 210 310 520 520
Outdoor
(CFM)
1200 1200 1200 1200 1390 2130 2130
AIR THROW DATA
Unit Capacity Max Approximate Air Throw ft. (m) Approximate Air Throw ft. (m) range
9K, 12K 23 (7) 11 (3.5) - 23 (7)
18K 30 (9) 13 (4) - 30 (9)
24K 36 (11) 16 (5) - 36 (11)
30K 36 (11) 16 (5) - 36 (11)
SOUND PRESSURE
System Size
9K 12K 9K 12K 18K 24K 30K
(115V) (115V) (208-230V) (208-230V) (208-230V) (208-230V) (208-230V)
Indoor Sound Pressure cooling mode (at
different speeds)
dBa 42/34/27 42/34/27 42/34/27 42/34/27 46.5/40/33 50/45/39 50/45/39
Indoor Sound Pressure heating mode (at
different speeds)
dBa 40/33/26 41/34/27 40/33/26 41/34/27 45/39/32 47/44/38 47/44/38
Outdoor sound pressure level dBa 55.5 56 55.5 56 59 60 63
ELECTRICAL DATA
UNIT
SIZE
OPER. VOLTAGE
MAX / MIN*
COMPRESSOR OUTDOOR FAN INDOOR FAN
MCA
MAX FUSE
CB AMP
V/PH/HZ RLA V/PH/HZ FLA HP W V/PH/HZ FLA HP W
9K
127 / 104 115/1/60
5.3
115/1/60 0.14 0.053 40 115/1/60 0.17 0.027 20 15 20
12K 5.7
9K
253 / 187 208-230/1/60
5.3
208-230/1/60
0.42 0.053 40
208-230/1/60
0.07 0.027 20 15
15
12K 5.70 0.42 0.053 40 0.07 0.027 20 15
15
18K 7.3 0.95 0.067 50 0.17 0.077 58 15 20
24K 8.8 0.47 0.16 120 0.23 0.080 60 15 25
30K 13.5 1.21 0.16 120 0.23 0.080 60 20 30
*Permissible limits of the voltage range at which the unit will operate satisfactorily.
LEGEND
FLA - Full L o a d Amps
MCA - Minimum Circuit Amps
RLA - Rated Load Amps