Installation guide

Table 3--Superheat Charging
OUTDOOR EVAPORATOR ENTERING AIR TEMPERATURE (°FWB)
TEMP
(OF) 50 52 54 56 58 60 62 64 66 68 70 72 74
55 9 12 14 17 20 23 26 29 32 35 37 40 42
60 7 10 12 15 18 21 24 27 30 33 35 38 40
65 -- 6 10 13 16 19 21 24 27 30 33 36 38
70 -- -- 7 10 13 16 19 21 24 27 30 33 36
75 -- -- -- 6 9 12 15 18 21 24 28 31 34
80 .... 5 8 12 15 18 21 25 28 31
65 ...... 8 11 15 19 22 26 30
90 ...... 5 9 13 16 20 24 27
95 ....... 6 10 14 18 22 25
100 ........ 8 12 15 20 23
105 ........ 5 9 13 17 22
110 .......... 6 11 15 20
115 .......... 8 14 18
--Where a dash appears, do not attempt to charge system under these conditions or refngerant slugging may occur Charge must be weighed in.NOTE:
Superheat °F is at low-side service pod,
SUPERHEAT
i E..ivl I-
(°F)
0
2
4
6
8
10
12
14
16
18
2O
22
24
26
28
30
32
34
36
38
4O
Table 4---Required Suction-Line Temperature
61,5
35
37
39
41
43
45
47
49
51
53
55
57
59
61
63
65
67
69
71
73
75
64.2
37
39
41
43
45
47
49
51
53
55
57
59
61
63
65
67
69
71
73
75
77
SUCTION
67.1
39
41
43
45
47
49
51
53
55
57
59
61
63
65
67
69
71
73
75
77
79
PRESSURE AT SERVICE PORT (PSIG)
70.0
41
43
45
47
49
51
53
55
57
59
61
63
65
67
69
71
73
75
77
79
81
73.0 76.0 79.2
43 45 47
45 47 49
47 49 61
49 51 53
51 53 55
53 55 57
85 57 59
57 59 61
59 61 63
61 63 65
63 65 67
65 67 69
67 69 71
69 71 73
71 73 75
73 75 77
75 77 79
77 79 81
79 81 83
81 83 85
83 85 87
82.4
49
51
53
55
57
59
61
63
65
67
69
71
73
75
77
79
81
83
85
87
89
76
45
43
41
39
37
35
33
31
29
27
26
25
23
85.7
51
53
55
57
59
61
63
65
67
69
71
73
75
77
79
81
83
85
87
89
91
Copyright 1999CARRIER Coq3. 7310 W. Morris St. Indianapolis, IN 46231 38tkb5si
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 101 Catalog No. 563-754 Printedin U.S.A. Form 38TKB-5SI 8
Pg
11
m98 Replaces:38TKB-3SI