Specification Sheet

8
CLEARANCES − OUTDOOR
A
D
B
Air-outlet
Air-inlet
C
E
A07894
Fig. 4 – Outdoor Unit Clearance
UNIT MINIMUM VALUE in. (mm)
A 24 (610)
B 24 (610)
C 24 (610)
D 4 (101)
E 4 (101)
NOTE: The outdoor unit must be mounted at least 2in. (50mm) above the maximum anticipated snow depth.