Specification Sheet

17
OUTDOOR UNIT SOUND PRESSURE TEST CONDITIONS
NOTE: H=0.5 x Height of outdoor unit
INDOOR CONDITION OUTDOOR CONDITION
DB WB DB WB
Cooling 80.6F (27C) 66.2F (19C) 95F (35C) 75.2F (24C)
Heating 68F (20C) 59F (15C) 44.6F (7C) 42.8F (6C)
ELECTRICAL DATA
Cooling Only
Outdoor Unit Size 9K 12K 9K 12K 18K 24K
Volts-PH-Hz (115V) (115V) (208/230V) (208/230V) (208/230V) (208/230V)
Max – Min*
Oper. Voltage
127-104 127-104 253-187 253-187 253-187 253-187
Power Supply
MCA 13 13 7 7 11 16
MOCP 20 20 15 15 15 25
Compressor RLA 9 9.5 4.5 4.5 7 11
Outdoor Fan Motor
FLA 0.6 0.6 0.4 0.4 0.5 0.6
Rated HP 0.054 0.054 0.054 0.054 0.065 0.068
Output 40 40 40 40 48 45
Heat Pump
Outdoor Unit Size 9K 12K 9K 12K 18K 24K
Volts-PH-Hz (115V) (115V) (208/230V) (208/230V) (208/230V) (208/230V)
Max – Min*
Oper. Voltage
127-104 127-104 253-187 253-187 253-187 253-187
Power Supply
MCA 13 13 8 10 15 18
MOCP 20 20 15 15 20 25
Compressor RLA 9 9.5 5.5 6.8 10.5 12
Outdoor Fan Motor
FLA 0.7 0.7 0.4 0.4 0.6 0.6
Rated HP 0.043 0.043 0.043 0.043 0.065 0.085
Output 32 32 32 32 48 63
*Permissible limits of the voltage range at which the unit will operate satisfactorily.
LEGEND
FLA - Full Load Amps
MCA - Minimum Circuit Amps
RLA - Rated Load Amps