Brochure
Includes Both
Controllers
Heat Pump with factory installed base pan heater – Variable Speed System
MA*R Series Ducted Single Zone Heat Pump with Inverter Technology
Outdoor Unit
208/230V
Indoor Unit
208/230V
Rated
Cooling
Btuh
Rated
Heating
Btuh
SEER
EER
40MBQB*D
40MBDQ
HSPF
Heating Capacity BTU's / % of rated
0.64
38MAQB18R--3
38MAQB24R--3
Max. External Static Pressure In. WG.
0.18
0.18
0.40
0.64
0.64
Controller Set Point Range
62°F to 86° Applicable to Heating Mode and Cooling Mode; Wired or Wireless Controllers
Factory Set Static Pressure In. WG
0.02
0.02
ECM Blwr Mtr Automatically Adjusts Uo To Max ESP
35A
Maximum Over-Current Protection
15A
15A
25A
30A
50A
50A
Minimum Circuit Ampacity
9A
9A
18A
20A
30A
9.26 lbs
Liquid Line Connection Size
1/4"
3/8"
Suction/Vapor Line Connection Size
3/8"
1/2"
5/8"
Precharged for 25ft of line set; oz/ft >25ft
Weigh in 0.16oz/ft >25ft
0.32oz/ft
Weigh in 0.43oz/ft>25ft
ODU Precharged R410a
3.31 lbs
3.31 lbs
4.30 lbs
5.73 lbs
6.72 lbs
Maximum Elevation / Lift
32 Feet
65 Feet
98 Feet
Minimum Line Set Length
10 Feet
10 Feet
10 Feet
Cooling Outdoor DB Min - Max °F
Outdoor Ambient -13°F to 122°F
Heating Outdoor DB Min - Max °F
Outdoor Ambient -22°F to 86°F
Maximum Line Set Length
82 Feet
98 Feet
213 Feet
9,000-50,000
Heating Cap. Range; Min-Max Btu/h
4,500-11,500
5,000-13,500
5,500-19,000
6,000-26,000
9,500-50,000
10,000-55,000
Cooling Cap. Range; Min-Max Btu/h
3,500-11,000
4,000-13,000
4,500-18,800
5,500-24,500
8,500-38,000
17317100A33862
Cooling Only Wireless Remote Control
Non-Programmable
Misc. Operational Data
9,000
12,000
18,000
24,000
36,000
48,000
17317100A11945
Programmable Cooling Only Wired Controller
Includes 19ft cable / max 66ft
17401204000769
Indoor unit includes integrated condensate lift pump. Drain line connection 25mm or 0.98" outside diameter.
Carrier Duct-Free System Accessories Compatible With 40MBQB & 40MBDQ Ducted IDU's
Accessory Model
Description
Notes
KSACN0501AAA
Programmable Wired Wall Mount Controller
Includes 19ft cable / max 66ft
KSACN0101AAA
Non-Programmable Wired Wall Mount Controller
Includes 19ft cable / max 66ft
17401204001601
19ft Extension Cable Kit for KSCAN0101AAA
Sold separately through RCD
19ft Extension Cable Kit for KSCAN0501AAA & 17317100A11945 (through RCD)
24,650 / 48%
Indoor unit is powered from outdoor unit.
Indoor Conditions DB 69°F
8.5
10.5
25,300 / 67%
17,570 / 46%
14,680 / 39%
38MBRQ48A--3
40MBDQ48---3
48,000
51,000
17.4
38MBRQ36A--3
40MBDQ36---3
36,000
38,000
15.5
8.9
10.3
34,000 / 67%
27,120 / 53%
40MBQB24D--3
24,000
24,000
20.5
12.5
11.5
25,042 / 104%
16,520 / 69%
15,250 / 64%
40MBDQ24---3
24,000
24,000
20.5
12.5
12.5
25,042 / 104%
16,520 / 69%
15,250 / 64%
40MBQB18D--3
16,500
18,000
19.6
12.5
10.5
18,920 / 105%
12,509 / 69%
11,650 / 65%
40MBDQ18---3
16,500
18,000
19.6
12.5
11.0
18,920 / 105%
12,509 / 69%
11,650 / 65%
8,114 / 81%
38MAQB12R--3
40MBQB12D--3
11,500
12,000
19.0
12.5
10.5
12,300 / 103%
8,562 / 71%
7,790 / 65%
38MAQB09R--3
40MBQB09D--3
9,000
10,000
19.0
13.0
11.1
11,068 / 111%
8,353 / 84%
Outdoor Unit
208/230V
Indoor Unit
208/230V
Rated
Cooling
Btuh
Rated
Heating
Btuh
SEER
EER
HSPF
Heating Capacity BTU's / % of rated
At 5°F
Outdoor
Ambient
At -13°F
Outdoor
Ambient
At -22°F
Outdoor
Ambient