Brochure
NOMINAL CAPACITY SEER EER HSPF INDOOR OUTDOOR
LINE SET SIZES
LIQUID X
SUCTION
MIN LINE
LENGTH
PRE
CHARGE
LENGTH
MAX
LINE
LENGTH
ADDITIONAL
CHARGE
MAX
LIFT
MCA /
MOCP
BASEPAN
HEATER
Warranty
With
Registration
WIRELESS
REMOTE
WIRED
CONTROLLER
9,000/ Gray ID
30.5
15.8 10.3
40GRQB09B--3 38GRQB09---3
1/4 X 1/2 10' 25' 82' .20 Oz/Ft. 33' 12A/15A Factory Installed 10 YEARS Included N/A
9,000/White ID
30.5
15.8 10.3
40GRQB09H--3 38GRQB09---3
1/4 X 1/2 10' 25' 82' .20 Oz/Ft. 33' 12A/15A Factory Installed 10 YEARS Included N/A
12,000/Gray ID
23.0
12.8 10.3
40GRQB12B--3 38GRQB12---3
1/4 X 1/2 10' 25' 82' .20 Oz/Ft. 33' 13A/20A Factory Installed 10 YEARS Included N/A
12,000/White ID
23.0
12.8 10.3
40GRQB12H--3 38GRQB12---3
1/4 X 1/2 10' 25' 82' .20 Oz/Ft. 33' 13A/20A Factory Installed 10 YEARS Included N/A
18,000/Gray ID
21.0
12.5 10.3
40GRQB18B--3 38GRQB18---3
1/4 X 5/8 10' 25' 82' .20 Oz/Ft. 33' 19A/30A Factory Installed 10 YEARS Included N/A
18,000/White ID
21.0
12.5 10.3
40GRQB18H--3 38GRQB18---3
1/4 X 5/8 10' 25' 82' .20 Oz/Ft. 33' 19A/30A Factory Installed 10 YEARS Included N/A
Performance
TM
High Wall 1:1 Heat Pump
9,000 - 115Volt 24.5
15.0 11.2
40MAQB09B--1 38MAQB09R--1
1/4 X 3/8 10' 25' 82' .16 Oz/Ft. 32' 15A/20A Factory Installed 10 YEARS Included Optional
12,000 - 115 Volt 22.0
13.0 10.2
40MAQB12B--1 38MAQB12R--1
1/4 X 1/2 10' 25' 82' .16 Oz/Ft. 32' 15A/20A Factory Installed 10 YEARS Included Optional
30,000
19.8
11.5 9.4
40MAQB30B--3 38MAQB30R--3
3/8 X 5/8 10' 25' 164' .32 Oz/Ft. 82' 20A/30A Factory Installed 10 YEARS Included Optional
36,000
16.0
8.6 8.5
40MAQB36B--3 38MAQB36R--3
3/8 X 5/8 10' 25' 164' .32 Oz/Ft. 82' 25A/35A Factory Installed 10 YEARS Included Optional
9,000
25.0
14.5 11.2
40MAQB09B--3 38MAQB09R--3
1/4 X 3/8 10' 25' 82' .16 Oz/Ft. 32' 9A/15A Factory Installed 10 YEARS Included Optional
12,000
22.5
12.5 12.0
40MAQB12B--3 38MAQB12R--3
1/4 X 1/2 10' 25' 82' .16 Oz/Ft. 32' 9A/15A Factory Installed 10 YEARS Included Optional
18,000
20.0
12.5 10.3
40MAQB18B--3 38MAQB18R--3
1/4 X 1/2 10' 25' 98' .16 Oz/Ft. 65' 18A/25A Factory Installed 10 YEARS Included Optional
24,000
20.5
13.0 10.3
40MAQB24B--3 38MAQB24R--3
3/8 x 5/8 10' 25' 98' .32 Oz/Ft. 65' 20A/30A Factory Installed 10 YEARS Included Optional
Performance
TM
Cassette 1:1 Heat Pump
9,000
20.0
13.0 10.8
40MBCQ09---3 38MAQB09R--3
1/4 X 3/8 10' 25' 82' .16 Oz/Ft. 32' 9A/15A Factory Installed 10 YEARS Included Optional
12,000
19.5
12.5 10.6
40MBCQ12---3 38MAQB12R--3
1/4 X 1/2 10' 25' 82' .16 Oz/Ft. 32' 9A/15A Factory Installed 10 YEARS Included Optional
16,000
20.0
12.5 10.5
40MBCQ18---3 38MAQB18R--3
1/4 X 1/2 10' 25' 98' .16 Oz/Ft. 32' 18A/25A Factory Installed 10 YEARS Included Optional
Performance
TM
Console 1:1 Heat Pump
9,000
20.0
12.5 11.6
40MBFQ09---3 38MAQB09R--3
1/4 X 3/8 10' 25' 82' .16 Oz/Ft. 32' 9A/15A Factory Installed 10 YEARS Included Optional
12,000
19.4
12.5 10.5
40MBFQ12---3 38MAQB12R--3
1/4 X 1/2 10' 25' 82' .16 Oz/Ft. 32' 9A/15A Factory Installed 10 YEARS Included Optional
Performance
TM
Ducted 1:1 Heat Pump
9,000
19.0
13.0 11.1
40MBQB09D--3 38MAQB09R--3
1/4 X 3/8 10' 25' 82' .16 Oz/Ft. 32' 9A/15A Factory Installed 10 YEARS Included Included
11,000
19.0
12.5 10.5
40MBQB12D--3 38MAQB12R--3
1/4 X 1/2 10' 25' 82' .16 Oz/Ft. 32' 9A/15A Factory Installed 10 YEARS Included Included
16,000
19.6
12.5 11.0
40MBDQ18---3
38MAQB18R--3
1/4 X 1/2 10' 25' 98' .16 Oz/Ft. 65' 18A/25A Factory Installed 10 YEARS Included Included
23,000
20.5
12.5 12.5
40MBDQ24---3 38MAQB24R--3
3/8 X 5/8 10' 25' 98' .32 Oz/Ft. 65' 20A/30A Factory Installed 10 YEARS Included Included
36,000
16.5
9.0 11.5
40MBDQ36---3 38MBRQ36A--3
3/8 X 5/8 10' 25' 213' .43 Oz/Ft. 82' 30A/50A Factory Installed 10 YEARS Included Included
48,000
17.4
9.2 10.3
40MBDQ48---3 38MBRQ48A--3
3/8 X 5/8 10' 25' 213' .43 Oz/Ft. 82' 35A/50A Factory Installed 10 YEARS Included Included
Installation Note :
Comfort
TM
High Wall 1:1 Heat Pump
9,000 - 115Volt 16.0
11.0 9.0
40MHHQ09---1 38MHRQ09A--1
1/4 X 3/8 10' 25' 82' .16 Oz/Ft. 32' 13A/20A N/A 10 YEARS Included Optional
12,000 - 115 Volt 16.8
10.8 9.0
40MHHQ12---1 38MHRQ12A--1
1/4 X 1/2 10' 25' 82' .16 Oz/Ft. 32' 13A/20A N/A 10 YEARS Included Optional
9,000
16.0
10.5 9.0
40MHHQ09---3 38MHRQ09A--3
1/4 X 3/8 10' 25' 82' .16 Oz/Ft. 32' 8A/15A N/A 10 YEARS Included Optional
12,000
17.0
10.9 9.0
40MHHQ12---3 38MHRQ12A--3
1/4 X 1/2 10' 25' 82' .16 Oz/Ft. 32' 10A/15A N/A 10 YEARS Included Optional
17,000
16.0
11.0 9.0
40MHHQ18---3 38MHRQ18A--3
1/4 X 1/2 10' 25' 98' .16 Oz/Ft. 65' 15A/20A N/A 10 YEARS Included Optional
22,000
16.8
10.5 9.0
40MHHQ24---3 38MHRQ24A--3
3/8 X 5/8 10' 25' 164' .32 Oz/Ft. 65' 18A/25A N/A 10 YEARS Included Optional
Comfort
TM
High Wall 1:1 Cooling Only
9,000 - 115Volt 16.6
11.6 N/A
40MHHC09---1 38MHRC09A--1
1/4 X 3/8 10' 25' 82' .16 Oz/Ft. 32' 13A/20A N/A 10 YEARS Included Optional
12,000 - 115 Volt 17.3
10.7 N/A
40MHHC12---1 38MHRC12A--1
1/4 X 1/2 10' 25' 82' .16 Oz/Ft. 32' 13A/20A N/A 10 YEARS Included Optional
9,000
16.0
10.6 N/A
40MHHC09---3 38MHRC09A--3
1/4 X 3/8 10' 25' 82' .16 Oz/Ft. 32' 7A/15A N/A 10 YEARS Included Optional
12,000
16.5
10.8 N/A
40MHHC12---3 38MHRC12A--3
1/4 X 1/2 10' 25' 82' .16 Oz/Ft. 32' 7A/15A N/A 10 YEARS Included Optional
18,000
17.0
10.5 N/A
40MHHC18---3 38MHRC18A--3
1/4 X 1/2 10' 25' 98' .16 Oz/Ft. 65' 11A/15A N/A 10 YEARS Included Optional
24,000
17.5
10.9 N/A
40MHHC24---3 38MHRC24A--3
3/8 X 5/8 10' 25' 164' .32 Oz/Ft. 65' 16A/25A N/A 10 YEARS Included Optional
Control Wiring
Kit Number
KSAIC0101115
KSAIC0101230
01-DLS-026-01
1 to 1 Performance
TM
&
Comfort
TM
Series ONLY
Mid-Tier High Wall
SEN-INS-CAR-03
208/230-1
© Carrier Corporation 2017
SUBJECT TO CHANGE WITHOUT NOTICE
07/2017
Sensibo®
Mid-Tier Ducted
SEN-INS-CAR-01
24 Volt Interface
Volt-Ph
Mid-Tier Cassette & Floor Console
SEN-INS-CAR-02
115-1
Performance
TM
Ducted 1:1 Heat Pump
Heating Capacity: 36K = 71% & 48K = 75% of Rated Capacity @ 5° F
The 38MBRQ Ducted systems require a shielded, stranded communication circuit between the indoor and outdoor units
Standard Heating Capacity Systems
* Warranty registration required except in CA and Quebec. In Commercial applications, Warranty is 7 Years P/C with Registration
See installation Instructions 14/3 Stranded Wire with Ground is the required Control wiring between the indoor and outdoor units
High Heating Systems - 100% of Rated Capacity @ 5° F
Single Zone Quick Reference Guide
Ductless Systems
*This Sheet is not intended to replace the Installation Instructions. It is a reference guide only. Always reference the Installation Instructions*
Infinity® High Wall 1:1 Heat Pump
High Heating Systems - 100% of Rated Capacity @ 0° F
Standard Heating Capacity Systems
Performance
TM
High Wall 1:1 Heat Pump
High Heating Systems - 100% of Rated Capacity @ 5° F
High Heating Systems - 100% of Rated Capacity @ 5° F
Ceiling Cassette Grille 40MBQB01C--- Required and Sold Separately
High Heating Systems - 100% of Rated Capacity @ 5° F