Spec sheet

19
AIR FLOW DATA
OUTDOOR MULTI-ZONE
SYSTEM SIZE 18 24 30 36 48
Outdoor (CFM) 1390 2130 2130 2130 3500
SOUND PRESSURE
OUTDOOR MULTI-ZONE
SYSTEM SIZE 18 24 30 36 48
Outdoor Sound Pressure Level DB(A) 62.4 63.4 62.3 63 64
SOUND POWER IN OCTAVE BANDS
Frequency (Hz) 63 125 250 500 1000 2000 4000 8000
2 ZONE 18K
Cooling dB(A)
53.9 52.0 55.4 48.9 44.5 40.4 36.3 30.8
Heating dB(A)
57.0 55.8 59.3 52.8 49.5 45.2 41.6 38.6
3 ZONE 24K
Cooling dB(A) 62.0 63.2 58.5 56.0 54.7 49.3 46.3
41.8
Heating dB(A) 64.4 65.9 65.4 58.5 57.7 52.7 50.3 52.2
4 ZONE 30K
Cooling dB(A) 58.4 60.1 58.3 52.6 51.0 47.6 44.2 38.7
Heating dB(A) 62.1 62.7 61.8 56.4 55.5 51.5 49.8 46.0
4 ZONE 36K
Cooling dB(A) 67.9 64.6 58.7 58.3 55.4 50.3 44.7 38.5
Heating dB(A) 65.1 61.8 62.4 59.0 56.7 52.2 45.5 41.6
5 ZONE 48K
Cooling dB(A) 68.4 65.8 58.6 58.3 55.5 51.8 45.3 44.2
Heating dB(A) 68.5 62.3 62.4 61.3 59.1 54.0 48.7 44.0
OUTDOOR UNIT SOUND PRESSURE TEST CONDITIONS
Fig. 10 Outdoor Unit Sound Pressure Test Conditions
NOTE: H=0.5 x Height of the outdoor unit.
INDOOR CONDITION OUTDOOR CONDITION
DB WB DB WB
Cooling 80.6F (27C) 66.2F (19C) 95F (35C) 75.2F (24C)
Heating 68F (20C) 59F (15C) 44.6F (7C) 42.8F (6C)