Spec sheet
11
COOLING PERFORMANCE NON−DUCTED COMBINATIONS
MODEL
COOLING OUTDOOR CONDITIONS (DB)
Indoor Conditions -13F
(-25C)
-4F
(-20C)
0F
(-17C)
5F
(-15C)
17F
(-8C)
47F
(8C)
77F
(25C)
86F
(30C)
95F
(35C)
104F
(40C)
113F
(45C)
122F
(50C)
DB WB
18
69.8F
(21C)
59F
(15C)
TC 19.12 19.86 19.66 19.26 18.87 20.69 21.78 19.94 17.92 12.00 11.58 9.89
SC 15.11 15.49 15.34 15.03 14.72 16.14 17.00 15.95 15.23 12.00 11.58 9.89
Input 1.37 1.41 1.48 1.53 1.57 1.60 1.63 1.79 1.96 1.47 1.52 1.32
75.2F
(24C)
62.6F
(17C)
TC 20.54 21.45 21.23 20.81 20.38 22.35 23.52 21.54 19.35 12.96 12.51 10.13
SC 15.35 15.61 15.29 15.40 15.28 16.98 18.35 17.01 15.87 11.53 11.88 9.93
Input 1.40 1.46 1.53 1.58 1.62 1.65 1.68 1.84 2.01 1.50 1.54 1.35
80.6F
(27C)
66.2F
(19C)
TC 21.91 22.46 22.18 22.53 22.85 24.15 25.11 23.85 21.54 14.82 14.22 10.40
SC 16.44 16.85 16.64 18.05 17.14 18.11 18.33 17.89 16.16 14.52 14.08 10.40
Input 1.41 1.45 1.51 1.58 1.62 1.65 1.68 1.88 2.05 1.52 1.57 1.36
89.6F
(32C)
73.4F
(23C)
TC 23.89 24.48 24.18 24.56 24.91 26.32 27.37 26.00 23.48 16.15 15.50 11.34
SC 17.20 17.63 17.65 18.17 18.68 19.22 22.44 21.84 20.19 15.18 14.88 11.11
Input 1.46 1.50 1.56 1.63 1.67 1.72 1.73 1.93 2.14 1.57 1.62 1.41
24
69.8F
(21C)
59F
(15C)
TC 31.96 32.76 32.58 32.60 32.15 32.75 32.44 26.94 24.46 19.98 17.56 15.45
SC 22.38 22.94 22.81 22.82 22.51 22.93 25.47 22.82 21.70 19.42 17.21 15.45
Input 2.26 2.32 2.31 2.34 2.36 2.38 2.41 2.26 2.50 2.39 2.58 2.62
75.2F
(24C)
62.6F
(17C)
TC 34.53 35.39 35.19 35.21 34.72 35.37 35.04 29.10 26.42 21.58 18.96 16.69
SC 24.17 24.77 24.63 24.65 24.31 24.76 26.28 23.86 22.72 19.42 18.02 16.52
Input 2.30 2.36 2.35 2.38 2.40 2.42 2.45 2.30 2.54 2.43 2.60 2.66
80.6F
(27C)
66.2F
(19C)
TC 36.25 37.15 37.24 37.08 37.51 37.68 37.53 35.39 32.75 24.71 23.96 20.15
SC 25.38 26.01 26.07 25.96 26.26 26.38 26.95 26.08 25.06 22.09 23.84 20.05
Input 2.20 2.25 2.28 2.34 2.35 2.41 2.47 2.75 3.04 2.48 2.62 2.74
89.6F
(32C)
73.4F
(23C)
TC 38.78 39.75 39.85 39.68 40.14 40.32 40.16 37.87 35.04 26.44 25.64 21.56
SC 27.15 27.83 27.89 27.77 28.09 30.64 32.93 32.19 31.19 24.32 24.61 21.56
Input 2.26 2.32 2.35 2.38 2.42 2.48 2.54 2.82 3.11 2.55 2.69 2.81
30
69.8F
(21C)
59F
(15C)
TC 39.15 40.12 40.28 39.54 39.18 40.81 39.79 37.98 36.16 28.21 26.56 23.46
SC 27.40 28.08 28.20 27.68 27.43 30.61 31.57 30.73 29.86 26.40 26.18 23.12
Input 3.08 3.16 3.18 3.12 3.21 3.24 3.28 3.62 3.99 3.13 3.25 2.66
75.2F
(24C)
62.6F
(17C)
TC 40.32 41.32 41.49 40.73 40.36 42.03 41.38 41.02 39.05 30.47 28.68 25.34
SC 28.23 28.93 29.04 28.51 28.25 31.53 33.93 36.10 35.15 28.03 27.25 24.83
Input 3.13 3.21 3.23 3.17 3.26 3.29 3.33 3.67 4.04 3.18 3.30 2.71
80.6F
(27C)
66.2F
(19C)
TC 41.13 42.15 42.51 42.61 42.10 42.61 42.41 40.63 38.82 32.17 30.47 27.53
SC 28.79 29.51 29.76 29.83 29.47 31.96 32.30 31.45 30.57 28.30 30.18 27.25
Input 3.13 3.21 3.25 3.29 3.31 3.38 3.42 3.67 4.05 3.21 3.31 2.76
89.6F
(32C)
73.4F
(23C)
TC 44.41 45.52 45.91 46.02 45.47 46.02 45.80 43.88 41.93 34.74 32.91 29.73
SC 31.10 31.87 32.14 32.21 31.83 34.51 37.56 38.61 37.73 31.96 31.26 29.73
Input 3.19 3.27 3.31 3.35 3.37 3.44 3.48 3.73 4.11 3.27 3.37 2.82
36
69.8F
(21C)
59F
(15C)
TC 37.82 38.76 38.32 39.02 39.41 40.44 40.91 36.89 33.97 27.85 25.60 23.33
SC 26.47 27.13 26.82 27.31 28.38 30.33 31.91 30.25 28.88 24.50 23.55 22.40
Input 2.69 2.76 2.83 2.87 2.91 2.98 3.03 3.39 3.79 3.68 3.76 3.41
75.2F
(24C)
62.6F
(17C)
TC 38.96 39.93 39.47 40.19 40.59 41.65 42.54 39.84 36.69 30.07 27.65 25.20
SC 27.27 27.95 27.63 28.13 28.42 31.24 34.88 35.06 33.02 27.67 26.26 24.69
Input 2.74 2.81 2.88 2.92 2.96 3.03 3.08 3.44 3.84 3.73 3.81 3.46
80.6F
(27C)
66.2F
(19C)
TC 42.58 43.64 43.31 44.15 44.54 45.02 45.94 43.73 41.49 34.44 31.93 27.16
SC 29.81 30.55 30.32 30.91 31.18 33.77 35.83 34.99 35.26 31.00 30.33 26.62
Input 2.79 2.86 2.89 2.91 2.95 3.06 3.10 3.48 3.91 3.80 3.85 3.47
89.6F
(32C)
73.4F
(23C)
TC 45.98 47.13 46.78 47.68 48.10 48.63 49.61 47.23 44.80 37.20 34.48 29.34
SC 32.19 32.99 32.74 33.38 33.67 36.47 40.68 41.56 40.32 34.22 32.76 29.34
Input 2.85 2.92 2.95 2.97 3.01 3.12 3.16 3.54 3.97 3.86 3.91 3.53
48
69.8F
(21C)
59F
(15C)
TC 41.22 42.25 42.51 41.87 41.24 41.97 41.47 39.32 36.26 32.97 29.86 26.54
SC 28.86 29.58 29.76 29.31 28.87 30.64 37.24 36.86 35.53 32.97 29.86 26.54
Input 2.19 2.24 2.28 2.35 2.38 2.41 2.46 2.78 3.11 3.45 3.64 3.08
75.2F
(24C)
62.6F
(17C)
TC 44.52 45.63 45.91 45.22 44.54 45.33 44.79 42.47 39.16 35.61 32.25 28.66
SC 32.50 33.31 33.51 33.01 32.51 34.90 37.17 36.10 34.07 32.05 32.25 28.66
Input 2.25 2.31 2.35 2.42 2.45 2.48 2.53 2.85 3.18 3.52 3.71 3.15
80.6F
(27C)
66.2F
(19C)
TC 53.80 55.14 54.68 55.31 56.15 56.72 60.26 56.82 53.16 40.95 38.57 35.24
SC 40.35 41.36 41.01 42.12 42.11 42.54 46.04 44.49 42.79 37.95 38.57 35.24
Input 2.99 3.06 3.15 3.25 3.29 3.46 3.94 4.36 4.80 3.79 3.98 3.43
89.6F
(32C)
73.4F
(23C)
TC 56.49 57.90 57.41 58.08 58.96 59.56 63.27 59.66 55.82 43.00 40.50 37.04
SC 41.80 42.84 42.49 42.98 43.63 46.45 52.52 51.31 50.24 40.85 40.50 37.04
Input 3.05 3.13 3.22 3.32 3.36 3.53 4.01 4.43 4.87 3.86 4.05 3.50
LEGEND
DB - Dry Bulb
WB - Wet Bulb
TC - Total Net Cooling Capacity (1000 Btu/hour)
SC - Sensible Capacity (1000 Btu/hour)
Input - Total Power (kW)