Specification Sheet

19
AIR FLOW DATA
UNIT SIZE
9K
(115V)
12K
(115V)
9K
(208/230V)
12K
(208/230V)
18K
(208/230V)
24K
(208/230V)
30K
(208/230V)
36K
(208/230V)
Outdoor (CFM) 1200 1200 1200 1200 1390 2130 2130 2130
SOUND PRESSURE
Estimated sound pressure level when
38MAR unit is paired with High Walls Indoor
9K
(115V)
12K
(115V)
9K
(208/230V)
12K
(208/230V)
18K
(208/230V)
24K
(208/230V)
30K
(208/230V)
36K
(208/230V)
Outdoor sound pressure level
(heat pump models)
dBa 52.5 52.5 55.5 56 57.5 60.5 60.5 60.5
Estimated sound pressure when 38MAR unit is paired with the Indoor Cassette
9K
(208/230V)
12K
(208/230V)
18K
(208/230V)
Outdoor sound pressure level (heat pump models) dBa 54 56 59
Estimated sound pressure when 38MAR unit is paired with the Indoor Console
9K
(208/230V)
12K
(208/230V)
Outdoor sound pressure level (heat pump models) dBa 57 56
Estimated sound pressure when 38MAR unit is paired with Ducted
Indoor
9K
(230V)
12K
(230V)
18K
(208/230V)
24K
(208/230V)
Outdoor sound pressure level (heat pump models) dBa 56 56 58 59
OUTDOOR UNIT SOUND PRESSURE TEST CONDITIONS
NOTE: H=0.5 x Height of outdoor unit
INDOOR CONDITION OUTDOOR CONDITION
DB WB DB WB
Cooling 80.6F (27C) 66.2F (19C) 95F (35C) 75.2F (24C)
Heating 68F (20C) 59F (15C) 44.6F (7C) 42.8F (6C)
ELECTRICAL DATA
MAR OUTDOOR UNIT SIZE 9K 12K 9K 12K 18K 24K 30K 36K
Power Supply
Volts-PH-Hz 115-1-60 115-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60
Max – Min*
Oper. Voltage
126-104 126-104 253-187 253-187 253-187 253-187 253-187 253-187
MCA 15 15 9 9 18 20 20 25
Max Fuse/
CB AMP
20 20 15 15 25 30 30 35
Compressor
Volts-PH-Hz 115-1-60 115-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60
RLA 9 9 5.25 5.65 12.3 14 15 17
*Permissible limits of the voltage range at which the unit will operate satisfactorily.
LEGEND
FLA - Full Load Amps
MCA - Minimum Circuit Amps
RLA - Rated Load Amps