Installation guide
NOTE:Iflinelengthisbeyond80fl (24.4m)orgreaterthan20fl
(6m)verticalseparation,SeeLongLineGuidelineforspecial
chargingrequirements,
MAINTENANCE
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal iniury
or death.
Before installing, modifying, or servicing system, main
electrical disconnect switch nmst be in the OFF position.
There may be more than 1 disconnect switch. Lock out and
tag switch with a suitable warning label.
LUBRICATION
Compressor
Compressor contains factory oil charge; replace oil when lost. Use
Mobile 3MA-POE oil.
CLEANING COILS
Coil should be washed out with water or blown out with
compressor air. Note that the blow-thru design causes dirt and
debris to build up on the inside of the coils. Clean coil annually or
as required by location and outdoor air conditions. Inspect coil
monthly and clean as required. Fins are not continuous through
coil sections. Dirt and debris may pass through first section,
become trapped between the row of fins and restrict condenser
airflow. Use a flashlight to deternfine if dirt or debris has collected
between coil sections. Clean coil as follows:
1. Turn off unit power.
2. Using a garden hose or other suitable equipment, flush coil
from the outside to remove dirt. Be sure to flush all dirt and
debris from drain holes in base of unit. Fan motors are wa-
terproof.
TROUBLESHOOTING
I
[
CON [ACTOR OPEN
FAULTY POWER ]
SUPPLY
DEFECT VE LOW- I
VOLTAGE
TRANGFORMER
OPEN CONTROL I
CIRCUIT
DEFECT VE ]TIME RELAY
CON_ACIOR OR
COIL DEFEC I IVE
LOOSE ELECTRCALCONNECTION
LINE PRESSURE
SWITCli
I
COMPRESSOR
WILL NOT RUN
I
!
CONTACTQR GtOSED J
COMPRESSOR POWER ]
SUPPLY OPEN
AT COMPRESSOR
FAULTY START GEAR(SINGLE PHASE}
OPEN, SHORTED OR
MOYOR WINDINGS
GROUNDED COMPRESSOR
CAPACITOR
NO COODNG OR
INSUFF CIENT DOOLING
I
1
J
ouTooo......... OO ELEADA,1
OR OYCUNG ON ]
OVERLOAD FAN MOTOR
OUTDOOR AIR
RESTRICTED OR MOTOR DEFECTIVE
RECIRCU_T NG ,,
RESTRICTED DISCHARGE NCORRECT OUTDOOR
:1
I _%%,%o#O%N_&OT
PRESSURE LOW HEAD PRESSURE LOW SUPERHEAI
__1 __i __1
DIRTY AIR ] I ..... TIVE] I
FILTERS COMPRESSOR VALVES UNiT OVERCHARGED i
NDOOR COIL INTERNAL PRESSURE BVRASSd YPE
FROSTED REUEF OPEN METERING DEVICE
OVERCHARGE OR I
NONCONDENSABLES
N SYS[EM
LOW REFRIGERANT ]
CHARGE
TOO HIGH OR LOW
CAPACITOR
{ COM ....... ]
BEARINGS
FAULTY
SLIGHTLY LOW ]ON REFRIGERANT
LIQU_D LINE ]SLIGHTLY RESTRICTED
BYPASS-TYPE
METERING DEVCE
RESTRFCTED
NCORRECT ]
BYPASS-TYPE
ME [ERING DEVICE
INDOOR BLOWER MOFOR
ON OVERLOAD
DEFECTIVE OR CYCUNG
HIGH SUPERHEAT 1
Fig. 6 - Troubleshooting the Cooling Cycle