Product data
Duct Free Systems - Physical Data - 40 Series Satellite Units
Cooling Models
40HD024 40HD036 40HD048
Nominal Capacity (Tons)
2 3.0 4.0
Operating Weight
88 129.8 132
Moisture Removal (pts/hr)
Refrigerant Type
R-22 R-22 R-22
Metering Device
AccuRater AccuRater AccuRater
Charge (Lbs) Note #1
5.5/4.4 6.3/5.8 7.8/7.9
Indoor Fan (Direct Drive)
High RPM/CFM 1150/800 1150/1226 1150/1610
Med RPM 1095 1065 1065
Low RPM 1000 920 920
Air Throw ft (high fan) N/A N/A N/A
Motor Watts (high) 1.11 2.27 2.27
Blower Wheel
Quantity 1 2 2
Size 8 x 8 8 x 8 8 x 8
Indoor Coil Data
Face Area (sq ft) 2.23 3.64 4.36
No Rows 3 3 3
FPI 13 13 13
Circuits 3 5 6
Filters (Disposable)
(qty) Hood (1) 16 x 20 x 1 (1) 16 x 20 x 1 (1) 16 x 20 x 1
(qty) Filter Rack (1) 12 x27 x 1 (2) 12 x 25 x 1 (2) 12 x 25 x 1
Refrigerent Lines
Liquid Line (Flare) 3/8" od 3/8" od 3/8" od
Vapor Line (Sweat) 5/8" od 3/4" od 7/8" od
Max Length, Lift & Drop Note #3 Note #3 Note #3
Condensate Drain
Dia 1" MPT 1" MPT 1" MPT
Controls (Microprocessor)
Remote (Wireless I/R) Yes Yes Yes
Freeze Protection Yes Yes Yes
Defrost Method n/a n/a n/a
Warm Start n/a n/a n/a
Auto Change Over n/a n/a n/a
Auto Restart Yes Yes Yes
Diagnostics Yes Yes Yes
Timer Mode (Start/Stop) 24 Hr 24 Hr 24 Hr
Test Mode Yes Yes Yes
Dehumidification Mode Yes Yes Yes
Fan Speeds H/M/L/Auto H/M/L/Auto H/M/L/Auto
Control Voltage 115v 115v 230v
System Voltage 115v 115v 208/230v
Air Sweep
Horizontal n/a n/a n/a
Vertical n/a n/a n/a
Finish
Galvanized Galvanized Galvanized
N/A = Not Available
Notes:
1) Cooling only units are shipped with a full factory charge in the outdoor unit based on
25' of refrigerent lines. Heat Pump units are shipped with a holding charge. Matched with HDC/HDL.
2) See Applications Data Section for long line lengths
3) See matching condenser for line lengths
Rev /
4) Cooling AccuRater in indoor unit. Heating AccuRater in outdoor unit.
02/15/02