Product data
Guide Specifications
Outdoor Cooling Only Units
Commercial (AN/HDC) Light Commercial (HDL) Condensing Units
HVAC Guide Specifications
Size range: ¾ to 5 Tons Cooling Capacity
Carrier Model Number: 38AN, 38HDC, 38HDL
Part 1 – General
1.01 SYSTEM DESCRIPTION
A. Outdoor-mounted, air-cooled split system outdoor section suitable for on-the-ground,
rooftop, wall hung, balcony, or under-deck installation. Unit shall consist of a hermetic
or rotary compressor, an air-cooled coil, propeller-type blow-thru outdoor fans,
accumulator, full refrigerant charge, and control box. Unit shall discharge air
horizontally as shown on the contract drawings. Units shall function as the outdoor
component of an air-to air cooling system.
B. Units shall be used in a refrigeration circuit matched to a duct-free cooling fan coil unit
or an approved ducted cooling fan coil unit.
1.02 QUALITY ASSURANCE
A. Unit construction shall comply with ANSI/ASHRAE 15, latest revision, and with the
NEC.
B. Units shall be constructed in accordance with UL standards.
C. Units shall be listed in the CEC directory.
D. Unit cabinet shall be capable of withstanding Federal Test Standard No. 141 (method
6061) 500-hour salt spray test.
E. Air-cooled condenser coils shall be leak tested at 350-psig-air pressure with the coil
submerged in water.
1.03 DELIVERY, STORAGE, AND HANDLING
Units shall be shipped in one piece and shall be stored and handled per unit
manufacturer’s recommendations.
1.04 WARRANTY
One-year parts, 5-year compressor limited warranty MORE ON NEXT PAGE