Product data
ARI* Capacities
Under Ceiling Applications
Indoor Outdoor Std. Net Cooling Total SEER EER Heating Heating Heating Heating Heating
Section Section CFM BTUH kW High High High Low Low
BTUH COP HSPF BTUH COP
40QAB024 38HDC018 500 18,000 1.64 12.0 11.0
40QAB024 38HDL018 500 18,000 1.71 11.6 10.5
40QAB024 38HDC024 600 22,800 2.07 12.0 11.0
40QAB024 38HDL024 600 23,000 2.06 11.0 11.2
40QAB036 38HDL030 840 29,000 2.98 10.3 9.7
40QAB036 38HDL036 840 34,000 3.53 10.1 9.6
40QAB036 38HDC036 840 34,000 3.25 12.0 10.5
40QAB036 38HDC030 840 30,000 2.73 12.0 11.0
40QAB048 38HDC048 1,200 47,000 4.37 12.0 10.8
40QAB048 38HDL048 1,200 45,500 4.61 10.8 9.9
40QAB060 38HDC060 1,600 58,000 5.18 12.0 11.2
40QAB060 38HDL060 1,600 58,500 6.15 10.8 9.5
40QAE024 38QR018C 500 19,000 1.90 11.0 10.0 17,000 3.2 7.2 9,800 2.1
40QAE024 38QR024C 525 24,000 2.40 11.0 10.0 22,600 3.0 7.3 12,500 2.0
40QAE036 38QR030C 870 30,000 2.94 11.0 10.2 28,000 3.3 7.4 15,600 2.2
40QAE036 38QR036C 870 34,600 3.39 11.5 10.2 33,000 3.3 7.2 19,000 2.2
40QAE036 38QR036C ! 870 36,000 3.67 11.0 9.8 34,400 3.0 6.8 19,800 2.0
40QAE048 38QR048C 1,100 48,000 5.00 10.2 9.6 45,500 3.2 7.3 28,200 2.2
40QAE060 39QR060C 1,600 58,000 5.85 11.0 9.9 57,500 3.2 7.4 32,000 2.2
Legend
* Air Conditioning & Refrigeration Institute
COP Coefficient of Performance
db Dry Bulb
HSPF Heating Seasional Performance Factor
wb Wet Bulb
! 3 Phase Unit
Notes:
1) Ratings are net values reflecting the effects of circulating fan heat. Supplemental electric heat is not included. Ratings are based on:
Cooling Standard: 80 deg F db, 67 deg F wb air entering evaporator and 95 deg F db air entering condenser
High Temperature Heating Standard: 70 deg F db air entering evaporator and 47 deg F db, 43 F wb air entering condenser
Low Temperature Heating Standard: 70 deg F db air entering evaporator and 17 deg F db, 15 F wb air entering condenser
2) Total kW is for total system, including compressor and outdoor and indoor fan motors.
3) Ratings are based on 25 ft of interconnecting refrigerent lines.
4) All system ratings are based on fan coil units operating at high fan speed. Consult Physical Data
tables for airflows at all available fan speeds.
01/09/02