Product data

ARI* Capacities High Wall Applications
Indoor Outdoor Std. Net Cooling Total SEER EER Heating Heating Heating Heating Heating
Section Section CFM BTUH kW High High High Low Low
BTUH COP HSPF BTUH COP
40QNB009 38AN009 215 8,500 0.88 10.5 9.7 --- --- --- --- ---
40QNB012-1 38AN012-1 300 11,000 1.18 10.5 9.3 --- --- --- --- ---
40QNB012-3 38AN012-3 302 11,600 1.15 11.0 10.1 --- --- --- --- ---
40QNB018 38HDC018 480 17,300 1.66 11.3 10.4 --- --- --- --- ---
40QNB018 38HDL018 480 16,200 1.67 11.0 9.7 --- --- --- --- ---
40QNB024 38HDL018 550 17,600 1.69 11.7 10.4 --- --- --- --- ---
40QNB024 38HDC024 550 22,600 2.09 12.0 10.8 --- --- --- --- ---
40QNB024 38HDL024 550 22,600 2.00 11.3 11.3 --- --- --- --- ---
40QNE009 38BK009 252 8,700 0.95 10.0 9.2 9,000 3.20 6.80 5,120 2.20
40QNE012 38BK012 302 12,500 1.28 10.5 9.8 12,500 3.00 6.80 7,190 2.30
40QNE018 38BK018 455 17,300 1.71 11.5 10.1 16,900 2.85 6.80 10,100 2.05
40QNE024 38BK024 525 23,200 2.23 11.0 10.4 21,400 2.90 6.80 12,700 2.20
40QNH012 38BK012 300 11,100 1.17 10.0 9.5 11,700 2.70 6.80 7,400 2.16
40QNH018 38BK018 485 17,300 1.71 11.0 10.1 16,400 2.84 6.80 9,600 2.04
40QNH024 38BK024 520 23,000 2.21 11.0 10.4 21,000 2.92 6.80 12,700 2.20
Legend
* Air Conditioning & Refrigeration Institute
COP Coefficient of Performance
db Dry Bulb
HSPF Heating Seasional Performance Factor
wb Wet Bulb
Notes:
1) Ratings are net values reflecting the effects of circulating fan heat. Supplemental electric heat is not included. Ratings are based on:
Cooling Standard: 80 deg F db, 67 deg F wb air entering evaporator and 95 deg F db air entering condenser
High Temperature Heating Standard: 70 deg F db air entering evaporator and 47 deg F db, 43 F wb air entering condenser
Low Temperature Heating Standard: 70 deg F db air entering evaporator and 17 deg F db, 15 F wb air entering condenser
2) Total kW is for total system, including compressor and outdoor and indoor fan motors.
3) Ratings are based on 25 ft of interconnecting refrigerent lines.
4) All system ratings are based on fan coil units operating at high fan speed. Consult Physical Data
tables for airflows at all available fan speeds.
Rev "A"
01/12/02