Product data

3
MORE ON NEXT PAGE
5. Filter needs cleaning status indication.
6. Automatic airsweep control to provide on or off activation of airsweep louvers.
7. Auto mode to provide modulating fan speed based on difference between temperature
setpoint and space temperature.
8. Fan only operation to provide air circulation when no cooling or heating is required.
9. Fan speed control shall be user-selectable: high, medium, low, or automatic operation
during all operating modes.
10. A time delay shall prevent compressor restart in less than 3 minutes.
11. Automatic heating-to-cooling changeover to provide automatic heating and cooling
operation. Control shall include deadband to prevent rapid mode cycling. (Heat Pump
Models)
12. Sleep set back.
13. Set temperature and room temperature displays.
14. Dehumidification mode
15. Fahrenheit or Celsius display
F. Filters:
Unit shall have filter track with factory-supplied cleanable filters.
G. Electrical Requirements:
Unit shall operate on 208v or 230v 60 Hz power supply. Power and control connections
shall have terminal block connections.
H. Operating Characteristics:
Cooling Only Console & Under Ceiling
Nominal Indoor Outdoor ARI Capacities ARI Sound Rating (dBa)
Capacity Unit Unit C/O H/P CFM SEER HSPF Indoor Outdoor
Tons
Btuh Btuh Pressure Pressure
1.5 40CG-018---3 38CG-018---3 18,000 - - 650 10.0 -- 38.0 49.0
2.0 40CG-024---3 38CG-024---3 23,400 - - 800 10.0 -- 40.0 49.0
2.5 40CG-030---3 38CG-030---3 30,000 - - 800 10.0 -- 40.0 49.0
Cooling Only Console & Under Ceiling Multi Split
Nominal Indoor Outdoor ARI Capacities ARI Sound Rating (dBa)
Capacity Unit Unit C/O H/P CFM SEER HSPF Indoor Outdoor
Tons
Two Sections One Section
Btuh Btuh Pressure Pressure
2.5 40CG-030---3 38SC-030---3 30,000 - - 800 10.0 -- 40.0 51.0
Heat Pump Console & Under Ceiling
Nominal Indoor Outdoor ARI Capacities ARI Sound Rating (dBa)
Capacity Unit Unit C/O H/P CFM SEER HSPF Indoor Outdoor
Tons
Btuh Btuh Pressure Pressure
1.5 40CS-018---3 38CS-018---3 18,000 18,000 650 10.0 6.8 38.0 49.0
2.0 40CS-024---3 38CS-024---3 23,400 23,400 800 10.0 6.9 40.0 49.0
2.5 40CS-030---3 38CS-030---3 30,000 31,000 800 10.0 6.8 40.0 49.0
Heat Pump Console & Under Ceiling Multi Split
Nominal Indoor Outdoor ARI Capacities ARI Sound Rating (dBa)
Capacity Unit Unit C/O H/P CFM SEER HSPF Indoor Outdoor
Tons Btuh Btuh Pressure Pressure
2.5 40CS-030---3 38SB-030---3 30,000 31,000 800 10.0 6.8 40.0 51.0
CFM - Cubic Feet Per Minute HSPF - Hating Seasonal Performance Factor SEER - Seasonal Energy Efficiency Rating
C/O - Cooling Only H/P - Heat Pump