HVAC Guide Specifications:
40CG and 38CG Cooling Only System -
1 ½, 2, and 2 ½ Tons Capacity
40CS and 38CS Heat Pump System -
1 ½, 2, and 2 ½ Tons Capacity
40CG and 38SC Cooling Only Two-Zone System -
2 ½ Tons Capacity
40CS and 38SB Heat Pump Two-Zone System -
2 ½ Tons Capacity
Part 1 – General
1.01 SYSTEM DESCRIPTION
A. Outdoor-mounted, air-cooled split system. Outdoor section suitable for on the ground, rooftop,
balcony, or under-deck installation. Unit shall consist of a hermetic compressor, an air-cooled
coil, propeller-type draw-through outdoor fan, full refrigerant charge, and control box. Unit shall
discharge air horizontally. Units shall function as the outdoor component of an air-to-air cooling
system.
B. Indoor direct expansion fan coil that can be, console or under-ceiling mounted. Fan coil
shall be shipped complete with heat exchanger coil, fan, fan motor, piping connectors,
electrical controls, infrared remote control system, wall and ceiling mounting brackets.
Fan shall be centrifugal blower type with air intake in the bottom of the unit and discharge
In the front. Automatic, motor-driven vertical air sweep shall be provided standard.
1.02 QUALITY ASSURANCE
A. Unit construction shall comply with ANSI/ASHRAE 15, latest revision, and with the NEC.
B. Unit shall be rated with the matching outdoor unit per ARI Standards 210/240.
C. Units shall be constructed in accordance with UL standards.
D. Units shall be listed in the CEC directory.
E. Unit cabinet shall be capable of withstanding 500-hour salt spray test.
F. Air-cooled condenser coils shall be leak tested at 350-psig.
G. Units will be certified for use in Canada
1.03 DELIVERY, STORAGE, AND HANDLING
Units shall be stored and handled per unit manufacturer’s recommendations. (MORE)