I. Operating Characteristics:
ARI
Capacities
Sound Rating (dBa) Indoor Unit Outdoor
Unit
C/O
Btuh
H/P
Btuh
ARI
CFM
Air*
Entering
Condenser
Air*
Entering
Evaporator
Air**
Entering
Evaporator
SEER
HSPF
Indoor
Power
Indoor
Pressure
Outdoor
Power
Outdoor
Pressure
38QR-018C-3 19,000 17,000 500 95 Deg. F 80 Deg. F 67 Deg. F 11.0 7.2 57.2 48.9 67.2 58.9 40QAE024-331
38QR-024C-3 24,000 22,600 525 95 Deg. F 80 Deg. F 67 Deg. F 11.0 7.3 66.3 58.0
38QR-030C-3 30,000 28,000 870 95 Deg. F 80 Deg. F 67 Deg. F 11.0 7.4 68.4 60.1 65.9 57.6
38QR-036C-3 34,600 33,000 870 95 Deg. F 80 Deg. F 67 Deg. F 11.5 7.2 66.2 57.9
40QAE036-321
38QR-036C-5,6 36,000 34,000 870 95 Deg. F 80 Deg. F 67 Deg. F 11.0 6.8 71.5 63.2
40QAE048-321 38QR-048C-3,5,6 48,000 45,500 1,100 95 Deg. F 80 Deg. F 67 Deg. F 10.2 7.3 67.3 59.0 73.0 64.7
40QAE060-311 38QR-060C-3,5,6 58,000 57,500 1,600 95 Deg. F 80 Deg. F 67 Deg. F 11.0 7.4 70.1 61.8 73.6 65.3
* Dry Bulb Note: For alternate air entering conditions see the Carrier Product Selector
** Wet Bulb
J. Special Features (Field Installed):
1. Internal Condensate Pump:
The condensate pump shall remove condensate from the drain pan when gravity
drainage cannot be used. The lift capability of the condensate pump shall be 20
inches. Float control shall be in the condensate sump to shut unit down in case of
pump malfunction.
2. Fresh Air Intake Kit:
Kit shall include filter and duct connections to provide for outdoor ventilation air
(must be used with Power Ventilation Kit).
3. Indoor Guard Kit:
Kit shall include a guard for the discharge grille to prevent objects from entering
the air sweep mechanism.
4. Electronic Programmable Thermostat:
Thermostat shall be commercial grade and shall provide 7-day, 4-event
scheduling. Integral sub-base shall be included. Thermostat shall also provide 3-
speed fan switchover capability, air sweep auto changeover, and shall not require
a battery to retain memory.
5. Power Ventilation Kit:
Kit must be used with the accessory fresh air kit when fresh air must be ducted in.
The kit will overcome duct static to provide a constant supply of ventilation air.
Kit consists of booster fan and adjustable speed control to properly balance fan to
achieve required airflow rate.