Product data
H. Electrical Requirements:
Unit shall operate on 115-v (009 & 012), or 208/230 v (012-024), 60 Hz power
supply as specified on the equipment schedule. Power and control connections shall
have terminal block connections.
I. Operating Characteristics:
Note:
Air Entering Condenser 95 deg F (Dry Bulb)
Air Entering Evaporator 80 deg F (Dry Bulb)
Air Entering Evaporator 67 deg F (Wet Bulb)
J. Refrigerant Lines:
The 009 and 012 units shall have rotatable refrigerant lines for penetration through
the wall using flare connections. All units shall have flare connections and a 90-
degree suction elbow shall be provided for rear connection.
K. Special Features (Field Installed):
1. Condensate Pump:
The condensate pump shall remove condensate from the drain pan when gravity
drainage cannot be used. Pump shall be designed for quiet operation. Pump shall
consist of two parts: an internal reservoir/sensor assembly, and a remote sound-
shielded pump assemble. The lift capability of the condensate pump shall be 1 to
10 ft (009-size unit) or 3 to 25 ft (0012-024 size units). A level sensor on the
condensate pan shall stop cooling operation if the level in the condensate pan is
unacceptable.
2. Charcoal Filter Kit:
Kit shall include active charcoal filter(s) and required collectors and/or frames.
Filters shall aid in removing volatile organic compounds and micro-particles from
the air in the conditioned space.
Nominal Indoor Outdoor ARI ARI Sound Rating (dBa)
Capacity Unit Unit Capacity CFM SEER EER Indoor Indoor Outdoor Outdoor
Tons Btuh Power Pressure Power Pressure
0.75 40QNB009-1 38AN-009-1 8,500 215 10.5 9.7 50.4 42.1 62.3 54
1 40QNB012-1 38AN-012-1 11,000 300 10.5 9.3 54 45.7 63.1 54.8
40QNB012-3 38AN-012-3 11,600 302 11.0 10.1 54 45.7 63.1 54.8
1.5 40QNB018-3 38HDC018-3 17,300 480 11.3 10.4 57.6 49.3 66.1 57.8
38HDL018-3 16,200 480 11.0 9.7 57.6 49.3 59.5 51.2
38HDL018-3 17,600 550 11.7 10.4 59.5 51.2
2 40QNB024-3 38HDC024-3 22,600 550 12.0 10.8 62.5 54.2 65.5 57.2
38HDL024-3 22,600 550 11.3 11.3 63.2 54.9