Product data

G. Filters:
Unit shall have filter track with factory-supplied cleanable filters.
H. Electrical Requirements:
Unit shall operate on 115 v (009), 208 v (012-024), or 230 v (012-024), 60 Hz power
supply as specified on the equipment schedule. Power and control connections shall
have terminal block connections.
I. Operating Characteristics:
J. Refrigerant Lines:
The 009 and 012 units shall have rotatable refrigerant lines for penetration through
the wall using flare connections. All units shall have flare connections and a 90-
degree suction elbow shall be provided for rear connection.
K. Special Features (Field Installed):
1. Condensate Pump:
The condensate pump shall remove condensate from the drain pan when gravity
drainage cannot be used. Pump shall be designed for quiet operation. Pump shall
consist of two parts: an internal reservoir/sensor assembly, and a remote sound-
shielded pump assemble. The lift capability of the condensate pump shall be 1 to
10 ft (009 size unit) or 3 to 25 ft (0012-024 size units). A level sensor on the
condensate pan shall stop cooling operation if the level in the condensate pan is
unacceptable.
2. Charcoal Filter Kit:
Kit shall include active charcoal filter(s) and required collectors and/or frames.
Filters shall aid in removing volatile organic compounds and micro-particles from
the air in the conditioned space.
Indoor Outdoor ARI Capacity ARI Air * Air * Air ** Sound Rating (dba)
Unit Unit C/O H/P CFM Enterin
g
Enterin
g
Enterin
g
SEER HSPF Indoor Indoor Outdoor Outdoor
Btuh Btuh Condenser Evaporator Evaporator Power Pressure Power Pressure
40QNE009-1 38BK-003-1 8,700 9,000 252 95 Deg. F 80Deg. F 67 Deg. F 10 6.8 50.6 42.3 63.4 55.1
40QNH012-3 38BK012-3 11,100 11,700 300 95 Deg. F 80Deg. F 67 Deg. F 10 6.8 54.0 45.7 62.8 54.5
40QNH018-3 38BK018-3 17,300 16,400 485 95 Deg. F 80Deg. F 67 Deg. F 11 6.8 58.6 50.3 67.2 58.9
40QNH024-3 38BK024-3 23,200 21,000 520 95 Deg. F 80Deg. F 67 Deg. F 11 6.8 61.7 53.4 63.3 55.0
* Dry Bulb Note: For alternate air entering conditions see the Carrier Product Selector
** Wet Bulb