Product data

FAULT CODES
Table 6 – Indicator Lamps Troubleshooting
LAMP STATUS INDICATION CORRECTIVE ACTION
POWER flashes 10 seconds
after A/C start-up (with or
without other signal lamps)
Communication problem
Check connection between indoor
(TAC-440) and outdoor (TAC-420)
units (for TAC-400, ANC)
Check connection between TAC-
444 and TAC-460 (for TAC-404)
POWER, COMPRES, and
PRESSURE lamps flash.
Thermistor failure
Check TH-1 for correct resistance
Check for proper connection
between TH-1 and TAC-444
Replace TH-1 if necessary
POWER, COMPRES, and
IMPEDANCE lamps flash
Thermistor failure
CHECK TH-2 for correct resistance
Check for proper connection
between TH-2 and TAC-444
Replace TH-2 if necessary
POWER lamp flashes and
PRESSURE is lit, AIR CON is
Off
Low Pressure
Check if the filters are clean
Check TH-1 and TH-2 for correct
resistance
Check cooling system for normal
operation
POWER AND PRESSURE
lamps flash, AIR CON is Off
High Pressure
In Heat mode: Check if the
evaporator is blocked (Check if
filters are clean)
Check TH-2 (in Heating mode) or
TH-3 (in Cool mode) for correct
resistance
Check cooling system for normal
operation
FILTER is lit
Filter cleaning
Clean all filters
POWER, IMPEDANCE lamps
flash, COMPRES is lit
Low voltage
Check power supply voltage
Check electrical connections
Replace TAC-444
POWER lamp flashes,
IMPEDANCE and COMPRES
lamps lit, AIR CON lamp
flashes after A/C startup
Voltage failure at startup
Check power supply voltage
Check electrical connections
Replace TAC-444
POWER lamp flashes,
IMPEDANCE and COMPRES
are lit before A/C startup
High voltage
Check power supply voltage
Check electrical connections
Replace TAC-444
POWER lamp flashes,
IMPEDANCE and COMPRES
are lit, AIR CON is lit after A/C
startup
High voltage during compressor
operation
Check power supply voltage
Check electrical connections
Replace TAC-444
MORE ON NEXT PAGE