Product data

HWError Code.doc 02/09/01
Check CN1 plug for voltage
If voltage is recorded at the CN1 plug and LED does not flash, replace
board.
Insufficient cooling,
Insufficient Heating
(Heat Pump)
Check for blocked air filter – clean filter
Outdoor unit obstructed – remove obstruction
Check temperature setting – use remote to change temperature
Fan speed too low – change fan speed
Check operation mode – Change to cooling mode
Check for open windows and doors
Error code 6 (reversing valve
malfunction) for cooling only
systems
Check indoor thermistor
Check refrigerant charge
Check FJ1 switch on main circuit board (s/b off)
Unit stops during operation
Off timer is operating
Room temperature has reached set point