Compressor Short Cycling Protection
There is a time delay of 3 minutes between compressor turning off and turning back on.
Indoor Coil Freeze Protection (Cooling or Dehumidification Mode Only)
If the indoor coil temperature is less than or equal to 32 F for 10 minutes after the compressor has started, then the
compressor and outdoor fan are turned off. The indoor fan continues to run at the user-selected speed until the indoor coil
reaches 44 F. At that time, the compressor and outdoor fan will restart.
Indoor Coil High Temperature Protection (Heat Pump Systems Only)
If indoor coil temperature is greater than or equal to 135 F, the outdoor fan shuts down. The outdoor fan will restart
automatically when the indoor coil temperature drops to 120 F. MORE ON NEXT PAGE