Product data

Awake Mode — The awake timer will turn the unit on when the timer reaches zero minutes. The unit will start in
the same mode and at the same selected temperature as when the system shut off. If the room temperature is not
within approximately 5° F of the set point 40 minutes before start-up, the unit runs before the awake timer reaches
zero to achieve the set point temperature at start-up.
Automatic Operation Mode for Cooling Only Systems — The unit samples the air in the room. Based on the
room temperature, the unit selects one of the following modes:
Cooling Mode — If the room temperature is more than 82.4 F with a preset temperature of 78.8 F.
Dry Mode — If the room temperature is more than 75.2 F and less than 82.4 F with a preset temperature
of 77 F.
Fan Only Mode — If the room temperature is less than 75.2 F. the preset temperature can be changed by
±4° F using the remote control.
Automatic Operation Mode for Heat Pump Systems — The operation mode will be determined after 20
seconds of room monitoring (to determine the room temperature and the outdoor air temperature).
Test Mode — The test mode can be selected by setting the slide switch on the fan coil unit to TEST position. The
slide switch is located on the front of the unit. The fan coil unit will start immediately (there is no compressor time
delay when using test mode) in cooling mode with an infinitely low set point. The indoor fan speed will be at the
high setting, and the swing louvers will be on (moving up and down).
NOTE: The unit cannot be controlled by the remote controller until the slide switch is returned to the REMOTE
position.
Emergency Mode — This mode is only to be used if the remote controller is lost, damaged, or the batteries are
discharged. To initiate emergency mode, manually move the slide switch on the fan coil unit to the EMER position.
The unit is automatically operated in cooling or heating mode according to room temperature. Emergency operation
settings are as follows:
1. Operation mode: AUTO
2. Fan Speed: AUTO
3. Cooling set point: 77 F
4. Timer Mode: Continuous NOTE: The unit cannot be controlled by the remote controller
until the slide switch is returned to the REMOTE position. MORE ON NEXT PAGE