Product data

Duct Free Systems - Electrical Data - 40 Series Cassette Units
Model Voltage Voltage Fan Heater Power Minimum
V-Ph-60Hz Min Max FLA kW FLA MCA MOCP FLA Wire Size
40QKB024-3 208/230-1 187 253 0.44 -- -- 0.55 15.0 0.44 14
40QKB036-3 208/230-1 187 253 .44/.44 -- -- 1.10 15.0 0.88 14
40QKE024-3 208/230-1 187 253 0.44 1.80 * 7.50 0.6/9.4 15/15 7.94 14/14
40QKE036-3 208/230-1 187 253 0.78 2.70 * 11.25 1.0/15.0 15/15 12.80 14/14
40QKE048-3 208/230-1 187 253 1.04 2.70 * 11.25 1.3/15.0 15/15 12.03 14/14
Notes:
1) Two MCA, MOCP, and minimum wire size values are shown for units with separate unit and heater circuits.
Th
e
fi
rs
t
va
l
ue app
li
es
t
o
th
e un
it
c
i
rcu
it
an
d
th
e secon
d
app
li
es
t
o
th
e
h
ea
t
er c
i
rcu
it
.
2)
T
wo
f
an mo
t
ors are use
d
on
th
e
QKB036
,
QKE036
AND
QKE048
Legend
* Separate unit and heater circuits required
FLA - Full Load Amps
LRA - Locked Rotor Amps
MCA
-
Mi
n
i
mum
Ci
rcu
it
A
mps
MOCP - Maximum Overcurrent Protection Amps. (Fuse or Heating, Air Conditioning, and Refrigeration Circuit Breaker
Duct Free Systems - Electrical Data - 40 Series Hydronic Cassette Units
Model - Voltage Fan (Note #1) System Power
No of Pipes V-Ph-60Hz Min Max Speed Watts FLA MCA MOCP
High 120 0.6
40WKN004-2 208/230-1 253 187 Med 85 0.5 15 15
Low 75 0.4
High 120 0.6
40WKN008-2 208/230-1 253 187 Med 85 0.5 15 15
Low 75 0.4
High 120 0.6
40WKM010-2 208/230-1 253 187 Med 85 0.5 15 15
Low 75 0.4
High 120 0.6
40WKM010-4 208/230-1 253 187 Med 90 0.4 15 15
Low 70 0.4
High 275 1.2
40WKN016-2 208/230-1 253 187 Med 185 0.8 15 15
Low 160 0.7
High 275 1.2
40WKN020-2 208/230-1 253 187 Med 185 0.8 15 15
Low 160 0.7
High 275 1.2
40WKN020-4 208/230-1 253 187 Med 190 0.8 15 15
Low 165 0.7
Notes:
1)
N
om
i
na
l
HP
1/16
2) Two fan motore are used on the WKN016 and WKN020
Legend
FLA
-
F
u
ll
L
oa
d
A
mps
LRA
-
L
oc
k
e
d
R
o
t
or
A
mps
MCA
-
Mi
n
i
mum
Ci
rcu
it
A
mps
R
ev
"A"
MOCP - Maximum Overcurrent Protection Amps. (Fuse or Heating, Air Conditioning, and Refrigeration Circuit Breaker
01/09/02